6.2Dry Contact Interface (optional card)

DB9 Male Connector Outline

(facing connector)

Pin #

 

Description

I/O Type

1

UPS fail, relay contact, normally open, active close.

output

2

Summary alarm, relay contact, normally open, active close.

output

 

One of the following signals activate this signal:

 

 

1)

Output fault

 

 

2)

Bus fault

 

 

3)

Over temperature

 

 

4)

Overload

 

 

5)

Over Charging

 

 

6)

Battery test fail

 

 

7)

Charger failure

 

3

GND for secondary

 

4

Remote shutdown

input

 

• Short Pin 4 & Pin 5: Remote Output Shutdown

 

 

 

 

 

• Remove short between Pin 4 & Pin 5: UPS switch back

 

 

 

to Inverter/Run

 

5

Common

 

6

Bypass active, normally open, active close

output

7

Battery low, normally open, active close

output

8

No connection

input

9

Utility fail, normally open, active close (Requires 2 seconds

output

 

for pin to activate)

 

Note: Vcc Voltage is 9-12 Vdc.

Table 2 : DryContact Pin Out Signal Chart

19

Page 44
Image 44
Toshiba 1000 user manual Dry Contact Interface optional card, DB9 Male Connector Outline Facing connector