Harman Stove Company P61A manual Vent Configurations

Page 10

Venting

Outside air flex pipe goes here.

Flex pipe part#

1-00-08543 (25')

Inlet Cover part# 1-10-08542

Direct Vent Wall Passthrough Kit

(part #1-00-677077)

Vent Configurations:

Per national building codes, consideration must be given to combustion air supply to all combustion appli- ances. Failure to supply adequate combustion air for all appliance demands, may lead to back-drafting of those and other appliances.

When the appliance is side-wall vented: The air in- take is best located on the same exterior wall as the exhaust vent outlet and located lower on the wall than the exhaust vent outlet.

When the appliance is roof vented: The air intake is best located on the exterior wall oriented towards the prevailing wind direction during the heating season.

The outside air connection will supply the demands of the pellet appliance, but consideration must be given to the total house demand. House demand may con- sume some air needed for the stove, especially during a power failure. It may be necessary to add additional ventilation to the space in which the pellet appliance is located. Consult with your local HVAC professional to determine the ventilation demands for your house.

To install outside air use 2 3/8" I.D. non-combustible flex pipe. There is a break-away hole on the rear panel of the stove which must be removed before connect- ing the flex pipe. The pipe should be run outside and terminate to the side or below the vent pipe outlet so the flue outlet is more than 12" from the inlet cover. The maximum length run of this pipe is 15 feet. If a longer run is needed the size must be increased to 3". Inlet cover, part number 1-10-08542 should be used to keep birds, rodents, etc. out of the pipe.

You may choose to use the optional Direct Vent Wall Passthrough Kit (part #1-00-677077) which incorporates the venting passthrough and outside air inlet into one component.

To reduce probability of reverse drafting during shut-down conditions, Hearth & Home Technologies strongly recommends:

Installing the pellet vent with a minimum vertical run of five feet, preferably terminating above the roof line.

Installing the outside air intake at least four feet below the vent termination.

To prevent soot damage to exterior walls of the house and to prevent re-entry of soot or ash into the house:

Maintain specified clearances to windows, doors, and air inlets, including air conditioners.

Vents should not be placed below ventilated soffits. Run the vent above the roof.

Avoid venting into alcove locations.

Vents should not terminate under overhangs, decks or onto covered porches.

Maintain minimum clearance of 12 inches from the vent termination to the exterior wall. If you see

deposits developing on the wall, you may need to extend this distance to accommodate your installation conditions.

Hearth & Home Technologies assumes no responsibility for, nor does the warranty extend to, smoke damage caused by reverse drafting of pellet appliances under shut-down or power failure conditions.

10P61A Pellet Stove

Image 10
Contents Installation & Operating Manual Safety NoticePage Label Table of Contents Important Notes Assembly and Installation Room Sensor InstallationInstalling InstallationMobile Home Installation Venting With outside air installed, 6 feetAddition, the following must be observed Outside Air Negative Pressure, Shut-down, and Power FailurePL Vent, Must Be Used VentingVent Configurations #1 Preferred method #2 Preferred method#5 Installing into an existing #4 Installing into an existing chimneyFireplace chimney #6 Installing into an existing fireplace chimney #7 Installing into an existing chimneyMinimum flue vent configuration #8 Installing through the ceilingStatus light error messages Automatic Ignition ESP ControlRoom Temperature Mode Automatic IGNITION/OPERATIONFeed Adjuster Knob Stove Temperature ModeShut Down Procedure Turn Feed Adjuster to #4.4 Igniter Switch to Auto up positionTurn Mode Selector to OFF Automatic Start UPManual IGNITION/Operation Manual Start UP Igniter Switch to Manual down positionFill hopper with pellets and remove ashes as required.1 Low Draft Voltage Adjustment Low Draft Voltage AdjustmentGlass Replacement MaintenanceMinimizing Creosote Scraping the burn pot CleaningRemoving Ashes Disperse fly ash and soot into the room Not equipped with a fine dust filter may clogSoot and Fly Ash Maintenance Burn Pot Burn Pot Cleaning and MaintenanceMaintenance Cleaning the Feeder Body Safety FeaturesFire has Gone OUT- Check for status light Trouble-ShootingCleaning Burn Pot Curing PaintFuel Specifications Fuel and Fuel StorageOperation in Room Temp mode Operation in Stove Temp modeChanges to Maintenance Schedule 30 P61A Pellet Stove Direct Vent Wall Passthrough Kit Side Heat ShieldsHopper Extension -Part#1-00-08636 Decorative Slate OptionsWiring Diagram SpecificationsLimited Lifetime Warranty Hearth & Home Technologies IncWarranty Conditions This warranty is void ifService Parts Part number list on following#2 Pre Serial number 008085092 Feeder Assembly Stocked at depotAt depot #3 Post Serial number 008085803 Feeder AssemblyStocked Clean Out Cover Sets 00-06623 P61A Pellet Service & Maintenance Log P61A Pellet Stove 42 P61A Pellet Stove Page Proudly Printed On 100% Recycled Paper