Rheem HE119-160LP, HE45-160LP, HE45-130N, HE45-100LP, HE45-100N Friction Loss Equivalence Tables

Page 10

FRICTION LOSS EQUIVALENCE TABLES

3" VENTED MODELS

 

 

 

2" VENTED MODELS

 

AFTER THE FIRST 10' OF 3" ONLY

 

 

 

 

4" EQUIVALENT TABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FITTING

 

EQUIVALENT

 

FITTING

 

EQUIVALENT

 

FITTING

 

EQUIVALENT

DESCRIPTION

 

FEET OF PIPE

 

DESCRIPTION

 

FEET OF PIPE

 

DESCRIPTION

 

FEET OF PIPE

3" 90˚

 

5'

 

 

2" 90˚

 

 

 

 

5'

 

4" 90˚

 

 

3'

3" 45˚

 

3'

 

 

2" 45˚

 

 

 

 

3'

 

4" 45˚

 

 

1'

3" Coupling

 

0'

 

 

2" Coupling

 

 

0'

 

4" Coupling

 

 

0'

3" Tee

 

0'

 

 

2" Tee

 

 

 

 

0'

 

4" Tee

 

 

0'

3" Pipe

 

1' = 1'

 

 

2" Pipe

 

 

 

1' = 1'

 

4" Pipe

 

 

1' = 1'

3" Concentric vent kit

 

3'

 

 

2" Concentric vent kit

 

 

3'

 

 

 

 

 

 

3" V1000 vent kit

 

0'

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTING EXAMPLES (NOTE: SHOWN AS INTAKE & EXHAUST PIPE FITTINGS ADDED TOGETHER

 

* = MINIMUM VENT LENGTH

 

 

 

 

 

** = MAXIMUN VENT LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRAND TOTAL

 

 

TOTAL COMBINED

 

 

 

 

 

EQUIVALENT

 

 

 

 

VENT LENGTH

 

 

VENT LENGTH

 

 

 

 

 

FRICTION LOSS

 

TOTAL FRICTION

(FEET) WITH

 

 

(FEET) INTAKE &

 

QTY. OF 90˚

 

(FEET) FOR EACH

 

LOSS FOR

FITTING FRICTION

 

 

EXHAUST

 

ELBOWS

 

ELBOW

 

ELBOWS

LOSS ADDED

 

 

 

*12

 

 

2

 

 

5

 

 

10

 

22

 

 

 

20

 

 

2

 

 

5

 

 

10

 

30

 

 

 

20

 

 

3

 

 

5

 

 

15

 

35

 

 

 

20

 

 

4

 

 

5

 

 

20

 

40

 

 

 

20

 

 

5

 

 

5

 

 

25

 

45

 

 

 

20

 

 

6

 

 

5

 

 

30

 

50

 

 

 

20

 

 

7

 

 

5

 

 

35

 

55

 

 

 

20

 

 

8

 

 

5

 

 

40

 

60

 

 

 

20

 

 

9

 

 

5

 

 

45

 

65

 

 

 

20

 

 

10

 

 

5

 

 

50

 

70

 

 

 

20

 

 

11

 

 

5

 

 

55

 

75

 

 

 

20

 

 

12

 

 

5

 

 

60

 

80

 

 

 

20**

 

 

13

 

 

5

 

 

65

 

85**

 

 

 

30

 

 

3

 

 

5

 

 

15

 

45

 

 

 

30

 

 

4

 

 

5

 

 

20

 

50

 

 

 

30

 

 

5

 

 

5

 

 

25

 

55

 

 

 

30

 

 

6

 

 

5

 

 

30

 

60

 

 

 

30

 

 

7

 

 

5

 

 

35

 

65

 

 

 

30

 

 

8

 

 

5

 

 

40

 

70

 

 

 

30

 

 

9

 

 

5

 

 

45

 

75

 

 

 

30

 

 

10

 

 

5

 

 

50

 

80

 

 

 

30**

 

 

11

 

 

5

 

 

55

 

85**

 

 

 

40

 

 

3

 

 

5

 

 

15

 

55

 

 

 

40

 

 

4

 

 

5

 

 

20

 

60

 

 

 

40

 

 

5

 

 

5

 

 

25

 

65

 

 

 

40

 

 

6

 

 

5

 

 

30

 

70

 

 

 

40

 

 

7

 

 

5

 

 

35

 

75

 

 

 

40

 

 

8

 

 

5

 

 

40

 

80

 

 

 

40**

 

 

9

 

 

5

 

 

45

 

85**

 

 

 

50

 

 

3

 

 

5

 

 

15

 

65

 

 

 

50

 

 

4

 

 

5

 

 

20

 

70

 

 

 

50

 

 

5

 

 

5

 

 

25

 

75

 

 

 

50

 

 

6

 

 

5

 

 

30

 

80

 

 

 

50**

 

 

7

 

 

5

 

 

35

 

85**

 

 

 

60

 

 

3

 

 

5

 

 

15

 

75

 

 

 

60

 

 

4

 

 

5

 

 

20

 

80

 

 

 

60**

 

 

5

 

 

5

 

 

25

 

85

 

 

 

70**

 

 

3

 

 

5

 

 

15

 

85

 

10

Image 10
Contents With Installation Instructions for the Contractor USE & Care ManualSpecifications Liquefied Petroleum Models If LP GAS is Present or SuspectedN G E R Location Local Installation RegulationsTemperature and Pressure Relief Valve Expansion TankSpecial Instructions for Booster Installations Domestic Water ConnectionsElectrical Connection GAS ConnectionPipe / Fittings When Using 3 Vent Pipe Venting When Using 3 Vent PipeFor Longer Vent Lengths When Using 3 Vent Pipe For Longer Vent Lengths When Using 2 Vent Pipe Special Venting Instructions Using 2 Vent PipePipe / Fittings When Using 2 Vent Pipe Cleaner / CementFriction Loss Equivalence Tables Control Description Start UP ProcedureTemperature SET Point Adjustment Procedure Never Purge from the T&P ValveMaintenance Thermostat Differential Adjustment ProcedureStatus Indicators Internal WiringCorrosive Atmospheres Failure to OperateFuel Conversions CondensateReplacement Parts not Shown Components of the AdvantagePlusIf There WAS no Ignition GAS Valve AdjustmentT E S If Ignition WAS PoorStatus Indications Under Normal Conditions Status Indications Under Normal Operating Conditions Ignitor Lockout No Incoming Line Voltage or 24 VoltPossible Cause Remedy Ignition Lockout ECO Switch OpenPossible Cause Control Health Temperature Probe FaultCombustion AIR Blockage Page Integrated Water Heater Control Very Important SET-UP Instructions Venting Samples AdvantagePlus with Storage Tank Sequence of Operations Water is heating Verify flame presence through sight window Green LED on Main Trouble Shooting Guide Most Common Advantageplus Installation Concerns