Rheem HE80-199LP T E S, GAS Valve Adjustment, If There WAS no Ignition, If Ignition WAS Poor

Page 15

GAS VALVE ADJUSTMENT

Let the unit start to cycle and listen carefully to the igni- tion. If the ignition was quiet, the valve will need no adjustment. If it was a loud ignition, the unit rumbles, or there was no ignition at all, follow these steps:

IF THERE WAS NO IGNITION:

1.Make sure the gas valve is in the "on" position, gas is on to the unit, and the gas valve wiring harness is plugged into the gas valve and into the control board.

2.Turn the adjustment screw under the brass cap. Turn one full turn clockwise with a small flathead screwdriver. Turning the adjustment screw clockwise increases the amount of gas.

3.If the unit still does not ignite, turn the adjustment screw two full turns counterclockwise.

IF IGNITION WAS POOR:

1.Look at the color of the flame through the sight glass while the unit is running. If it is green or red in color, or the heater whistles on ignition, turn the adjustment screw counterclockwise at 1/8” turn intervals until the flame turns blue/light blue in color or the whistling at ignition stops. If the flame is very weak or pulsing, turn the adjustment screw clockwise until the flame steadies.

2.Put the gas valve adjustment screw cover back in place and tighten.

3.Put the AdvantagePlus cabinet door back into place.

 

LABEL

SEE SIDE WARNING

P

3

WR

 

 

 

M

1

 

1/2 PSI

PRESS MAX

 

C

2

 

OFF

Gas Valve

 

ON

Adjustment

Screw

PILOT ADJ

!CAUTION

THERE ARE NO USER SERVICEABLE PARTS WITH- IN THE CONTROL SYSTEM. TO MAINTAIN SAFETY AND PROPER APPLIANCE PERFORMANCE, REFER ALL TROUBLESHOOTING TO QUALIFIED SERVICE PERSONNEL.

TROUBLESHOOTING

The appliance controller has many inherent diagnostic and fault detection routines built into its operating soft- ware and hardware. These routines, along with the three digit LED display and nine LED status indicators present on the display panel, can greatly assist the service per- son in quickly pinpointing the source of problems that may occur with the appliance. In certain circumstances, multiple LED's may be lit or flashing to better pinpoint the problem. The following charts, diagrams, and informa- tion can be used during troubleshooting procedures. See also Trouble Shooting Guides and Sequence of Operations at the end of this Use and Care Manual.

N O T E S

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

________________________________________________________________________________

15

Image 15
Contents USE & Care Manual With Installation Instructions for the ContractorSpecifications If LP GAS is Present or Suspected Liquefied Petroleum ModelsN G E R Expansion Tank Local Installation RegulationsTemperature and Pressure Relief Valve LocationDomestic Water Connections Special Instructions for Booster InstallationsGAS Connection Electrical ConnectionVenting When Using 3 Vent Pipe Pipe / Fittings When Using 3 Vent PipeFor Longer Vent Lengths When Using 3 Vent Pipe Cleaner / Cement Special Venting Instructions Using 2 Vent PipePipe / Fittings When Using 2 Vent Pipe For Longer Vent Lengths When Using 2 Vent PipeFriction Loss Equivalence Tables Never Purge from the T&P Valve Start UP ProcedureTemperature SET Point Adjustment Procedure Control DescriptionInternal Wiring Thermostat Differential Adjustment ProcedureStatus Indicators MaintenanceCondensate Failure to OperateFuel Conversions Corrosive AtmospheresComponents of the AdvantagePlus Replacement Parts not ShownIf Ignition WAS Poor GAS Valve AdjustmentT E S If There WAS no IgnitionStatus Indications Under Normal Conditions Status Indications Under Normal Operating Conditions No Incoming Line Voltage or 24 Volt Ignitor LockoutPossible Cause Remedy ECO Switch Open Ignition LockoutPossible Cause Temperature Probe Fault Control HealthCombustion AIR Blockage Page Integrated Water Heater Control Very Important SET-UP Instructions Venting Samples AdvantagePlus with Storage Tank Sequence of Operations Water is heating Verify flame presence through sight window Green LED on Main Trouble Shooting Guide Most Common Advantageplus Installation Concerns