VERY IMPORTANT SET-UP INSTRUCTIONS!
USING A COMBUSTION ANALYZER, THE FOLLOWING RATINGS
WILL BE VERY HELPFUL IN SETTING UP
3" PVC
INTAKE | 12" MIN. |
|
8" MIN.
EXHAUST
FOR NATURAL GAS - CO2 READING SHOULD BE BETWEEN 9 1/2% & 10 1/2% O2 READING SHOULD BE BETWEEN 3 1/2% & 4 1/2 %
CO READING SHOULD BE UNDER 10 PPM
FOR PROPANE GAS - CO2 READING SHOULD BE BETWEEN 10 1/2% & 11 1/2% O2 READING SHOULD BE BETWEEN 3 1/2% & 4 1/2 %
CO READING SHOULD BE UNDER 10 PPM
23
FLOOR MOUNTED
3" ABSPIPE SUPPORT MIN. 84"
REQ'D
FIGURE 1 - SIDE VENTING
SIDE VIEW
MAINTAIN 12" MIN.
(18" MIN. FOR CANADA) CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24" ABOVE ROOF
10' |
|
| 24" MIN. |
| |||
|
|
| |||||
- 0" MIN. |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| |||
|
|
|
|
|
MAINTAIN 12" MIN.
(18" MIN. FOR CANADA) CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL. MAXIMUM OF 24" ABOVE ROOF
3" PVC
|
| HOT | 3" PVC | HOT |
|
|
INTAKE |
|
|
|
|
| |
3" PVC |
|
|
|
|
| |
|
|
|
|
|
| |
| 3" CONCENTRIC |
|
|
|
|
|
| VENT KIT |
|
|
|
|
|
|
|
| INTAKE |
| INTAKE | 3" ABS |
|
|
|
| MIN. 84" | ||
| 1" MIN. |
|
|
|
| |
|
|
|
|
| REQ'D | |
|
|
|
|
|
| |
EXHAUST | 3" ABS | COLD | EXHAUST | COLD | EXHAUST |
|
|
|
| ||||
| MIN. 84" | FLOOR MOUNTED |
|
| FLOOR MOUNTED |
|
| REQ'D | 3" ABS |
|
| ||
|
| PIPE SUPPORT |
| PIPE SUPPORT |
| |
|
|
| MIN. 84" |
|
|
|
| FIGURE 2 - SIDE VENTING |
| REQ'D |
| FIGURE 4 |
|
| FIGURE 3 - VERTICAL ROOF VENTING |
|
| |||
| SIDE VIEW | FRONT VIEW |
| VERTICAL ROOF VENTING W/ CONCENTRIC VENT KIT |