Rheem HE119-130LP, HE45-160LP Special Venting Instructions Using 2 Vent Pipe, Cleaner / Cement

Page 9

or two 45 degree elbows. Then use a 4" x 3" PVC or 4" x 3" ABS reducing coupling. Then proceed with PVC 4" NON FOAM CORE pipe and fittings for both the intake and exhaust piping. On 4" piping you may go an addi- tional 125 equivalent feet of pipe and fittings, combined total length. The 4" fittings have a friction loss allowance as follows:

4" 90 degree = 3' and a 4" 45 degree = 1'.

The total maximum venting length can be 125', plus the first 10' of each 3", and a maximum fitting allowance of the 3", total two 90 degree or four 45 degree before increasing to 4". Total equivalent would be 30' of 3" plus 125' of 4". Never use different pipe sizes for intake and exhaust.

SPECIAL VENTING INSTRUCTIONS USING 2" VENT PIPE

(ONLY MODELS WITH INPUTS OF 100,000 BTU AND 130,000 BTU ARE CERTIFIED FOR 2" VENTING) HE45-100, HE45-130, HE80-130, HE119-130

For inlet air supply, top pipe on the right of the shroud, use 2 inch PVC schedule 40. It is very important that you plan the location properly, to eliminate long pipe

runs and excessive fittings. Inlet pipe size must not be reduced. Do not combine the inlet air with any other inlet pipe, including an inlet to an additional similar appliance. The joints must be properly cleaned, primed and cement- ed. The piping must also be properly supported as per local and national standard plumbing codes. It is impor- tant that the piping be clean and free from burs, debris, ragged ends and particles of PVC.

For exhaust piping, lower pipe on the right of the shroud, use 2 inch PVC schedule 40 NON FOAM CORE. Use 2 inch ABS NON FOAM CORE or 2 inch CPVC schedule 40 or 80 only when required to meet local venting codes. Exhaust piping should be sloped back to the connection on the AdvantagePlus, at least 1/4 inch per foot of pipe, to remove the condensate that forms within the pipe. The total combined length of pipe, (inlet air piping plus exhaust piping) including allowances for elbows, should not exceed 85 equivalent feet. The total combined length of pipe, including allowances for elbows, should not be less than 22 equivalent feet (minimum length of 12 feet of piping, including allowances for elbows, on the inlet and the exhaust). Choose your vent termination locations carefully. You must make certain that exhaust gas does not re-circulate back into the air inlet pipe. You must place your vent terminations in an open area, according to the venting guidelines section on page 8.

PIPE / FITTINGS WHEN USING 2" VENT PIPE

All inlet air and exhaust venting may use standard PVC

schedule 40 piping, conforming to ASTM D-1785, and fit- tings conforming to ASTM D-2466, or ABS pipe conform- ing to ASTM D-3965 and ASTM D-2661, and fittings con- forming to ASTM D-3311 and ASTM D-2661. (NEVER use cellular foam core pipe on exhaust piping)

FOR LONGER VENT LENGTHS WHEN USING 2" VENT PIPE

You may use 3 inch venting on both the intake and exhaust to lower the pressure drop and provide addition- al vent length. It is imperative when using 3 inch venting to follow these instructions carefully. For longer vent lengths, the first 10 feet of both the intake and exhaust piping must be 2 inches. For the first 10 foot use 2 inch PVC schedule 40 NON FOAM CORE, 2 inch ABS NON FOAM CORE or 2 inch CPVC schedule 40 or 80 plus one 90 degree or two 45 degree elbows. Then use a 2" x 3" reducing coupling of like material. Then proceed with 3 inch PVC schedule 40 NON FOAM CORE, 3 inch ABS NON FOAM CORE or 3 inch CPVC schedule 40 or 80 pipe and fittings for both the intake and exhaust piping. On 3 inch pipe you may go an additional 125 equivalent feet of pipe and fittings, combined total length. The total combined equivalent vent length would be 30 equivalent feet of 2-inch vent and 125 equivalent feet of 3-inch vent, for a maximum equivalent vent length of 155 feet. Never use different pipe sizes for intake and exhaust.

CLEANER / CEMENT

Cement for all venting must be ALL PURPOSE Cement, and must conform to ASTM D-2235, D-2564 and F-493, and cleaner for the piping and fittings must conform to ASTM F-656.

NOTE:

THE METHODS DESCRIBED ARE SUGGESTED GENERIC METHODS ONLY. SPECIFIC JOB SITE OBSERVATIONS AND SIZING MAY REQUIRE ALTER- NATE INSTALLATION METHODS. CONSULT THE FACTORY WITH SPECIFIC JOB REQUIREMENTS FOR ADDITIONAL RECOMMENDATIONS.

VERY IMPORTANT SET-UP INSTRUCTIONS!

IF YOU HAVE A COMBUSTION ANALYZER, THE FOL- LOWING RATINGS WILL BE VERY HELPFUL IN SET- TING UP YOUR ADVANTAGE PLUS:

FOR NATURAL GAS -

CO2 reading should be between (9 1/2% – 10%) O2 reading should be between (3 1/2% – 4 1/2%) CO reading should be under 10 PPM

FOR PROPANE GAS -

CO2 reading should be between (10 1/2% – 11 1/2%) O2 reading should be between (3 1/2% – 4 1/2%) CO reading should be under 10 PPM

9

Image 9
Contents USE & Care Manual With Installation Instructions for the ContractorSpecifications If LP GAS is Present or Suspected Liquefied Petroleum ModelsN G E R Temperature and Pressure Relief Valve Local Installation RegulationsLocation Expansion TankDomestic Water Connections Special Instructions for Booster InstallationsGAS Connection Electrical ConnectionVenting When Using 3 Vent Pipe Pipe / Fittings When Using 3 Vent PipeFor Longer Vent Lengths When Using 3 Vent Pipe Pipe / Fittings When Using 2 Vent Pipe Special Venting Instructions Using 2 Vent PipeFor Longer Vent Lengths When Using 2 Vent Pipe Cleaner / CementFriction Loss Equivalence Tables Temperature SET Point Adjustment Procedure Start UP ProcedureControl Description Never Purge from the T&P ValveStatus Indicators Thermostat Differential Adjustment ProcedureMaintenance Internal WiringFuel Conversions Failure to OperateCorrosive Atmospheres CondensateComponents of the AdvantagePlus Replacement Parts not ShownT E S GAS Valve AdjustmentIf There WAS no Ignition If Ignition WAS PoorStatus Indications Under Normal Conditions Status Indications Under Normal Operating Conditions No Incoming Line Voltage or 24 Volt Ignitor LockoutPossible Cause Remedy ECO Switch Open Ignition LockoutPossible Cause Temperature Probe Fault Control HealthCombustion AIR Blockage Page Integrated Water Heater Control Very Important SET-UP Instructions Venting Samples AdvantagePlus with Storage Tank Sequence of Operations Water is heating Verify flame presence through sight window Green LED on Main Trouble Shooting Guide Most Common Advantageplus Installation Concerns