Rheem HE119-199LP Venting When Using 3 Vent Pipe, Pipe / Fittings When Using 3 Vent Pipe

Page 8

VENTING WHEN USING 3" VENT PIPE

(ONLY MODELS WITH INPUTS OF 100,000 BTU AND 130,000 BTU ARE CERTIFIED TO USE 2" VENT PIPE, SEE SPECIAL VENTING INSTRUCTIONS SECTION)

For inlet air supply, top pipe on the right of the shroud, use 3" PVC schedule 40. It is very important that you plan the location properly to eliminate long pipe runs and excessive fittings. Inlet pipe size must not be reduced.

Do not combine the inlet air with any other inlet pipe including an inlet to an additional similar appliance. The joints must be properly cleaned, primed, and cemented. The piping must also be properly supported as per local and national standard plumbing codes. It is important that the piping be clean and free from burs, debris, ragged ends, and particles of PVC.

For exhaust piping, lower pipe on the right of the shroud, use only ABS schedule 40 or CPVC schedule 40 or 80, NON FOAM CORE, in the first 84" (7 feet) of vent length. The balance of the inlet and exhaust piping may be PVC schedule 40, ABS schedule 40 or CPVC schedule 40 or 80, NON FOAM CORE ONLY, as required to meet local venting codes.

Exhaust piping should be sloped back to the connection on the AdvantagePlus, at least 1/4 inch per foot of pipe, to remove the condensate that forms within the pipe. The total combined length of pipe, (inlet air piping plus exhaust piping) including allowances for elbows, should not exceed 85 equivalent feet. The total combined length of pipe, including allowances for elbows, should not be less than 22 equivalent feet (minimum length of 12 feet of piping, including allowances for elbows, on the inlet and the exhaust). Choose your vent termination locations carefully. You must make certain that exhaust gas does not re-circulate back into the air inlet pipe. You must place your vent terminations in an open area, according to the following guidelines.

Venting Guidelines

1)Never vent into a walkway or patio area, or an alley, or otherwise public area less than 7' from the ground.

2)Allow four (4) feet below or four (4) feet horizontally from any door, window or gravity air inlet to the building or other appliance.

3)Never install a heat saver or similar product to cap- ture waste heat from exhaust.

4)Always have vent location at least 1' above maximum snow level.

5)Always have vent 1' above ground level, away from shrubs and bushes.

6)Follow local gas codes in your region or refer to National Fuel Gas Code, or Can B149.

7)Always have vent at least 3' from an inside corner of outside walls.

8)Maintain at least 4' clearance to electric meters, gas meters and exhaust fans or inlets.

9)Inlet air must be taken from outside of building next to exhaust outlet, no closer than 8".

10)Always place 1/2 inch x 1/2 inch 16 gauge galva- nized steel screen in the intake and exhaust openings to prevent foreign matter from entering the AdvantagePlus.

11)The vent system must be balanced by friction loss equivalent (See table on page 10).

12)The same method must be used for both intake and exhaust termination. DO NOT terminate one horizontal- ly and the other vertically.

13)Roof Venting: The vent intake and exhaust must be properly cleaned and glued, for pressure tight joints. Several methods for venting the AdvantagePlus can be found on pages 22 and 23. Use the layout as a guide- line. Certain site conditions such as multiple roof lines/pitches may require venting modifications-consult factory. The air inlet must be a minimum of 1' vertically above the maximum snow level or 24" whichever is greater. The air inlet must also be a minimum of 10' hor- izontally from the roof and terminated with a tee. The exhaust must be a minimum of 24" above the air inlet opening and terminated with a coupling. It is very impor- tant that there are no other vents, chimneys, or air inlets in any direction for at least 4'. All venting must be properly supported, as the AdvantagePlus is not intended to support any venting whatsoever. All pip- ing, glue, solvents, cleaners, fittings, and components must conform to ASTM (American Society for Testing and Materials), and ANSI (American National Standard Institute).

14)It is recommended that you use vent kits specifically designed for AdvantagePlus installations.

PIPE / FITTINGS WHEN USING 3” VENT PIPE

The first 84" (7’) of exhaust piping, must be of 3" ABS solid only (provided) or CPVC; (NEVER use cellular foam core pipe on exhaust piping), and conform to ASTM D-3965 for ABS or ASTM F-441 for CPVC, and fit- tings to ASTM D2661 & D3311 for ABS and ASTM F-439 for CPVC. The balance of exhaust piping, and all of intake piping, use standard 3" PVC schedule 40 or 3" ABS schedule 40, conforming to ASTM D2665, or ABS conforming to ASTM D-3965 & ASTM R-441 for ABS; and fittings conforming to ASTM D-2665 & D331. ABS may also be used for intake venting as long as pipe conforms to ASTM D3965 & D2661 and fittings meet ASTM D2661 & D3311.

FOR LONGER VENT LENGTHS WHEN USING 3” VENT PIPE

All venting must be 3", both intake and exhaust. NEVER use any piping less than 3", or different size pipe on the intake and exhaust. You may use 4" venting on both intake and exhaust to lower the pressure drop and provide additional venting length. It is imperative when using 4" venting to follow these instructions very carefully. For longer venting lengths, the first 10' of both the intake and exhaust piping are 3". For the intake, use 10' of 3" PVC plus one 90 degree or two 45 degree elbows. For the exhaust, use 10' of ABS solid NON FOAM CORE, or CPVC plus one 90 degree

8

Image 8
Contents With Installation Instructions for the Contractor USE & Care ManualSpecifications Liquefied Petroleum Models If LP GAS is Present or SuspectedN G E R Local Installation Regulations Temperature and Pressure Relief ValveLocation Expansion TankSpecial Instructions for Booster Installations Domestic Water ConnectionsElectrical Connection GAS ConnectionFor Longer Vent Lengths When Using 3 Vent Pipe Venting When Using 3 Vent PipePipe / Fittings When Using 3 Vent Pipe Special Venting Instructions Using 2 Vent Pipe Pipe / Fittings When Using 2 Vent PipeFor Longer Vent Lengths When Using 2 Vent Pipe Cleaner / CementFriction Loss Equivalence Tables Start UP Procedure Temperature SET Point Adjustment ProcedureControl Description Never Purge from the T&P ValveThermostat Differential Adjustment Procedure Status IndicatorsMaintenance Internal WiringFailure to Operate Fuel ConversionsCorrosive Atmospheres CondensateReplacement Parts not Shown Components of the AdvantagePlusGAS Valve Adjustment T E SIf There WAS no Ignition If Ignition WAS PoorStatus Indications Under Normal Conditions Status Indications Under Normal Operating Conditions Possible Cause Remedy No Incoming Line Voltage or 24 VoltIgnitor Lockout Possible Cause ECO Switch OpenIgnition Lockout Combustion AIR Blockage Temperature Probe FaultControl Health Page Integrated Water Heater Control Very Important SET-UP Instructions Venting Samples AdvantagePlus with Storage Tank Sequence of Operations Water is heating Verify flame presence through sight window Green LED on Main Trouble Shooting Guide Most Common Advantageplus Installation Concerns