Rheem HE119-199LP, HE45-160LP, HE45-130N, HE45-100LP, HE45-100N, HE45-130LP Green LED on Main

Page 28

Display Board LEDs

What they mean, controller functions, possible causes and suggested service remedies.

LED Flashing

Controlling Function

Possible Cause

Service Remedy

LINE

Monitors incoming AC line voltage.

Check Breaker

Turn breaker ON

 

ON when line voltage is present.

Wiring disconnected

Check wiring

Does not have 120 VAC

 

Plugs on module disconnected or

Reseat plugs on control

 

 

loose

module

24 VAC

Monitors incoming voltage from the

Transformer wiring problem

Repair wiring

 

transformer. ON when secondary 24

Transformer is defective

Replace transformer

Does not have 24 VAC

VAC is present.

 

Reseat plugs on control

 

 

 

module

ECO/VENT SWITCH

Monitors the ECO switch. ON when

Water temp probe unplugged or

Check connector. Repair wiring

Water in tank too hot

ECO switch is closed (normal

damaged

Check connector. Repair wiring

position).

Vent temp probe unplugged or

or

 

damaged

Normal when water gets too hot.

Monitors water temperature in the

Water in tank is too hot (ECO is

 

Venting has a problem

tank and exhaust vent temperature.

activated). Check water temp in

Cool tank. Determine cause for

over temperature.

or

 

tank on display board

Check venting for obstructions

To diagnose, must determine which

Vent switch overtemp switch is

Check orifices to insure they match

 

Water in tank too low

function is at fault.

open

fuel type.

Press reset button and recheck.

 

 

No or not enough water in tank.

Make sure tank is full of water.

 

 

 

 

PRESSURE SWITCH

Monitors the air pressure switch. ON

Combustion air blockage

Check intake and exhaust piping

Combustion air blockage

when the pressure switch is closed.

Blower not operating

and flue for obstructions

Means there is sufficient combustion

Check and repair blower wiring;

 

airflow.

 

replace blower motor

 

 

Air switch stuck open or closed

Replace air switch

WATER TEMPERATURE

Monitors water temperature inside

Temp probe wiring is unplugged

Check connector or repair wiring

Something is wrong with the

the tank (Thermostat). ON when the

Probe open internally

Replace probe

temperature probe

water temp drops below set point

Probe wiring shorted

Repair short

or

(temperature setting).

Probe shorted internally

Replace probe

no or low water in tank

 

 

 

GAS VALVE

Monitors the gas valve output. ON

Broken or corroded burner ground

Check wire and connection at

 

when power is applied to the gas

wire

burner

Ignition lock out

valve

Connectors on controlled panel

Check and reseat connections

 

 

unplugged

 

No flame rectification

Unit will make three (3) successive

Gas valve shut OFF

Turn gas valve ON

 

trials; then lock out.

Clogged gas valve

Replace gas valve

 

 

Faulty gas valve

Replace gas valve

 

 

Defective control

Replace control

 

 

Gas valve improperly adjusted

Adjust gas valve correctly

BLOWER

Monitors the blower motor output.

No power to blower

Check for power to blower

Power to blower

ON when power is applied to the

Blower is bad

Repair or replace wiring

 

blower.

 

Replace blower

IGNITOR

Monitors ignitor element output. ON

No power to ignitor

Check for power to ignitor

Power to ignitor

when power is applied to the ignitor

Ignitor is bad

Repair or replace wiring

 

 

 

Ignitor current draw is too low.

 

 

 

See ignitor lockout on page 17

 

 

 

Replace ignitor

CONTROL HEALTH

Monitors the controllers hardware

System problem on circuit board

Press red reset button. If error

System board OK

(circuit boards) and software. ON

 

occurs repeatedly, replace main

 

when controller is functioning OK

 

control board

GREEN LED ON MAIN

Monitors polarity and ground circuit.

Polarity is reversed

Correct polarity

CONTROL BOARD

ON when ground and polarity are

Poor or incomplete ground

Ensure adequate grounding to unit

Proper ground and polarity

OK.

 

and in electrical circuit

 

Attempts to fire for 4-6 seconds; then

 

 

 

 

 

 

28

Image 28
Contents With Installation Instructions for the Contractor USE & Care ManualSpecifications Liquefied Petroleum Models If LP GAS is Present or SuspectedN G E R Local Installation Regulations Temperature and Pressure Relief ValveLocation Expansion TankSpecial Instructions for Booster Installations Domestic Water ConnectionsElectrical Connection GAS ConnectionPipe / Fittings When Using 3 Vent Pipe Venting When Using 3 Vent PipeFor Longer Vent Lengths When Using 3 Vent Pipe Special Venting Instructions Using 2 Vent Pipe Pipe / Fittings When Using 2 Vent PipeFor Longer Vent Lengths When Using 2 Vent Pipe Cleaner / CementFriction Loss Equivalence Tables Start UP Procedure Temperature SET Point Adjustment ProcedureControl Description Never Purge from the T&P ValveThermostat Differential Adjustment Procedure Status IndicatorsMaintenance Internal WiringFailure to Operate Fuel ConversionsCorrosive Atmospheres CondensateReplacement Parts not Shown Components of the AdvantagePlusGAS Valve Adjustment T E SIf There WAS no Ignition If Ignition WAS PoorStatus Indications Under Normal Conditions Status Indications Under Normal Operating Conditions Ignitor Lockout No Incoming Line Voltage or 24 VoltPossible Cause Remedy Ignition Lockout ECO Switch OpenPossible Cause Control Health Temperature Probe FaultCombustion AIR Blockage Page Integrated Water Heater Control Very Important SET-UP Instructions Venting Samples AdvantagePlus with Storage Tank Sequence of Operations Water is heating Verify flame presence through sight window Green LED on Main Trouble Shooting Guide Most Common Advantageplus Installation Concerns