Bradford-White Corp EF operation manual

Page 26

NOTICE

This unit can be vented using only PVC (Class 160, ASTM D-2241 Schedule 40, ASTM D-1785; or Cellular Core Schedule 40 DWV, ASTM F-891), Schedule 40 CPVC (ASTM F-411), or ABS (ASTM D-2661) pipe. The fittings, other than the TERMINATIONS should be equivalent to PVC- DWV fittings meeting ASTM F-2665. (Use CPVC fittings, ASTM F-438 for CPVC pipe and ABS fittings, ASTM D-266/3311 for ABS pipe.) If CPVC or ABS pipe and fittings are used, then the proper cement must be used for all joints, including joining the pipe to the Termination (PVC material). PVC materials should use ASTM –D2564 grade cement; CPVC materials should use ASTM F-493 grade cement; and ABS materials should use ASTM D-2235 grade cement.

For water heaters in locations with high ambient temperatures (above 100°F (37.8°C)) and/or insufficient dilution air, it is recommended that CPVC or ABS pipe and fittings (MUST USE SUPPLIED VENT TERMINAL) be used.

Horizontal Installation:

In a horizontal application, it is important that condensate not be allowed to buildup in the exhaust vent pipe. To prevent this from happening, the pipe should be installed with a slight upward slope of ¼ inch (.6 cm) per foot (.3 m). The vent system must be supported every 5 feet (1.5 m) of vertical run and every 3 feet (.9 m) of horizontal run of vent pipe length.

CAUTION

Failure to properly support the vent piping with hangers and clamps may result in damage to the water heater or venting system.

Stress levels in the pipe and fittings can be significantly increased by improper installation. If rigid pipe clamps are used to hold the pipe in place, or if the pipe cannot move freely through a wall penetration, the pipe may be directly stressed, or high thermal stresses may be formed when the pipe heats up and expands. Install accordingly to minimize such stresses.

Follow the following procedure to vent through the wall:

1.Cut one 3 ½ inch (8.9 cm) diameter hole (for 3 inch (7.6 cm) diameter pipe) or 4 ½ inch (11.5 cm) diameter hole (for 4 inch (10.2 cm) diameter pipe).

2.Use the proper PVC cement or sealant to secure the exhaust vent terminal provided with the water heater to the plastic pipes. The distance between the back edge of the exhaust vent terminal and the exterior wall (see Figure 16) must 6 inches (15.2 cm). Use the proper cement and assembly procedures to secure the vent connector joints between the terminal and the blower outlet. Provide support brackets for every 3 feet (.9 m) of horizontal vent.

26

Image 26
Contents With Troubleshooting Guide What to do if YOU Smell GASTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSection II Specifications Dimensions InchesFeatures Section III General InformationTemperature and Pressure Relief Valve Dishwashing Machine Requirements Condensate Elbow With TrapSection IV Installation Instructions Unpacking Minimum Clearance To Combustible MaterialRecommended Minimum Clearances For Service Access Remove CrateMechanical Exhausting of Room AIR LocationAIR Requirements Unconfined SpaceTypical Installation Illustration Chemical Vapor CorrosionTypical Two Water Heater Connection Scalding Section V Water ConnectionsInstructions for Connections Approximate TIME/TEMPERATURE Relationships in Scalds Alternate Space Heating Water ConnectionsSection VI Venting Approved Venting Materials Direct Vent Installation VentingCanadian US Installations2 Installations1 Clearance above Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Power Vent Installation Determining required vent lengthPage Typical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Concentric Vent Terminal Installation Procedure Dimensional Layout of Concentric Vent KitRain Cap to Small Vent Pipe Ass’y Concentric Vent Side Wall Attachment Models Vent Pipe PreparationSelection of Materials Section VII GAS ConnectionsInitial Preparation GAS Meter Size Natural Gases only GAS Pressure RegulationWiring Diagram and Schematic Section Viii Electrical ConnectionsTo Fill the Water Heater Section IX Operating InstructionsGeneral Instructions Sequence of OperationTemperature Adjustment Lighting InstructionsBurner Flame Check Sight Glass LocationGeneral Section X MaintenanceMaintenance Schedule Flushing Water HeaterSediment and Lime Scale Removal Draining Water HeaterFilling Water Heater Anode Inspection and Replacement To inspect or replace an anodeDrain Valve and Tank Access Panel Vent and AIR Intake SystemSection XI Troubleshooting Guide Combustion System InspectionSection XII Parts List EF Series Water HeaterCombustion Surround Assy Ignition Control Assy