Bradford-White Corp EF Location, AIR Requirements, Mechanical Exhausting of Room AIR

Page 12

DANGER

Temperature setting should not exceed safe temperature at fixtures. See Approximate Time/Temperature Scald Chart in “Section V: Water Connections”. If higher preheat temperatures are necessary to obtain adequate booster output, add an anti-scald valve for hot water supplied to fixtures.

LOCATION

KEEP APPLIANCE AREA CLEAR AND FREE OF COMBUSTIBLE MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS.

This water heater must be located in an area where the general public does not have access to set temperatures.

AIR REQUIREMENTS

1.Do not obstruct the flow of combustion and ventilating air.

2.For safe operation, adequate air is needed for combustion and ventilation. Sooting may result in serious damage to the water heater and risk of fire or explosion. It can also create a risk of asphyxiation. Such a condition often will result in a yellow, luminous burner flame, causing carboning or sooting of the combustion chamber, burner and flue tubes.

MECHANICAL EXHAUSTING OF ROOM AIR

1.Where an exhaust fan is installed in the same room with this water heater and combustion air is drawn from inside the room, sufficient openings for air must be provided in the walls. UNDERSIZED OPENINGS WILL CAUSE AIR TO BE DRAWN INTO THE ROOM THROUGH THE WATER HEATER’S VENTING SYSTEM, CAUSING POOR COMBUSTION THAT MAY BE HAZARDOUS TO LIFE. SOOTING MAY RESULT IN SERIOUS DAMAGE TO THE WATER HEATER AND RISK OF FIRE OR EXPLOSION, WHICH CAN ALSO CREATE A RISK OF ASPHYXIATION. Refer to local codes and /or National Fuel Gas Code for proper air opening sizing.

UNCONFINED SPACE

1.In buildings of conventional frame, brick or stone construction, unconfined spaces may provide adequate air for combustion and ventilation.

2.If the unconfined space is within a building of tight construction (buildings using the following construction: weather stripping, heavy insulation, caulking, vapor barrier, etc.), air for combustion and ventilation must be obtained from outdoors. This may be accomplished by piping air directly to the water heater from outside or providing opening or ducts in the wall. The installation instructions for confined spaces in tightly constructed buildings must be followed to ensure adequate air supply.

CONFINED SPACE

1.When drawing combustion air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings.

The top opening is to be located within 12 inches (30.5 cm) of the enclosure top and the bottom opening within 12 inches (30.5 cm) of the enclosure bottom.

Each opening shall have a free area of at least 1 inch² (6.5 cm²) per 1000 Btu/h (.3 kw) of the total input of all appliances in the enclosure, but not less than 100 inches² (645.2 cm²).

2.If the confined space is within a building of tight construction, air for combustion and ventilation must be obtained from outdoors. This may be accomplished by piping air directly to the water heater from outside or providing opening or ducts in the wall. When directly communicating with the outdoors through vertical ducts, two permanent openings, located in the above manner, shall be provided.

Each opening shall have a free area of not less than 1 inch² (6.5 cm²) per 4000 Btu/h (1.2 kw) of the total input of all appliances in the enclosure.

If horizontal ducts are used, each opening shall have a free area of not less than 1 inch² (6.5 cm²) per 2000 Btu/h (.6 kw) of the total input of all appliances in the enclosure.

12

Image 12
Contents With Troubleshooting Guide What to do if YOU Smell GASTable of Contents Page If YOU Smell GAS Do not Operate the Appliance Until the Leakage is CorrectedSection II Specifications Dimensions InchesFeatures Section III General InformationTemperature and Pressure Relief Valve Dishwashing Machine Requirements Condensate Elbow With Trap Section IV Installation Instructions Unpacking Minimum Clearance To Combustible MaterialRecommended Minimum Clearances For Service Access Remove CrateLocation AIR RequirementsMechanical Exhausting of Room AIR Unconfined SpaceTypical Installation Illustration Chemical Vapor CorrosionTypical Two Water Heater Connection Section V Water Connections Instructions for ConnectionsScalding Approximate TIME/TEMPERATURE Relationships in Scalds Alternate Space Heating Water ConnectionsSection VI Venting Approved Venting Materials Direct Vent Installation VentingCanadian US Installations2 Installations1 Clearance above Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Power Vent Installation Determining required vent lengthPage Typical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Concentric Vent Terminal Installation Procedure Dimensional Layout of Concentric Vent KitRain Cap to Small Vent Pipe Ass’y Concentric Vent Side Wall Attachment Models Vent Pipe PreparationSection VII GAS Connections Initial PreparationSelection of Materials GAS Meter Size Natural Gases only GAS Pressure RegulationWiring Diagram and Schematic Section Viii Electrical ConnectionsSection IX Operating Instructions General InstructionsTo Fill the Water Heater Sequence of OperationTemperature Adjustment Lighting InstructionsBurner Flame Check Sight Glass LocationSection X Maintenance Maintenance ScheduleGeneral Flushing Water HeaterDraining Water Heater Filling Water HeaterSediment and Lime Scale Removal Anode Inspection and Replacement To inspect or replace an anodeDrain Valve and Tank Access Panel Vent and AIR Intake SystemSection XI Troubleshooting Guide Combustion System InspectionSection XII Parts List EF Series Water HeaterCombustion Surround Assy Ignition Control Assy