Bradford-White Corp EF Section XI Troubleshooting Guide, Combustion System Inspection

Page 45

COMBUSTION SYSTEM INSPECTION

Inspect the operation of the combustion system monthly. Use the following procedure to inspect the combustion system.

1.Turn off the main power switch of the water heater.

2.Adjust the thermostat to the Min. setting.

3.Remove the top of the combustion surround by unlatching it.

4.While observing the ignition module, turn on the main power switch.

5.Adjust thermostat to the Max. setting.

6.Watch the LED’s light as the controller goes through the S-OP as previously described.

7.Upon ignition, observe the main burner flame.

8.Readjust thermostat to previous setting.

9.Replace combustion surround top and latch it securely in place.

WARNING

Do not run out of propane gas. Damage to the water heater may occur.

 

 

 

SECTION XI: TROUBLESHOOTING GUIDE

 

 

 

 

 

 

 

Main power

Make sure that water heater is plugged in.

 

 

light is not lit.

When the switch is on, is there 120VAC between L1 and N on the terminal block? If not, then check for loose wire

 

 

 

connections on the "Power Switch Wire Harness." If connections are ok, then replace the switch.

 

 

 

If there is voltage between L1 and N then the light on the switch is burnt out. Replace switch

 

 

Ignition module

Check for 120 VAC at the ignition module on "120 VAC IN." If there is voltage, then check the secondary (24 volt

 

 

"Power" LED is

 

terminals) voltage across the transformer as previously described. If no voltage from the secondary plug from the

 

 

not lit

 

transformer, replace the transformer or wire harness. If the control has 120 and 24 volt input, replace the control.

 

 

 

 

 

 

 

Blower does not

Unplug the wire harness to the blower and check the pins for 120 volts. If no voltage, and the ignition control has 120

 

 

energize

 

volts, the control may be defective, call tech support. If 120 volts is present to the blower, make sure the pins are making

 

 

 

 

good contact. Replace blower if connections are good and 120 volts is present to blower.

 

 

Ignitor does not

Make sure pressure switch contacts are closed (24 volts from pressure switch harness to ground). Is there voltage to the

 

 

glow

 

"Hot Surface Ignitor"? Check for 120VAC to the ignitor from the ignition module when the ignition LED is lit. If no

 

 

 

voltage to the ignitor, replace ignition control.

 

 

 

Check the resistance value across the "Hot Surface Ignitor?" If over 120 ohms, then replace hot surface ignitor.

 

 

Main valve does

Put your hand on the gas valve. When the "Valve" LED lights on the ignition module, can you feel it energize? If not,

 

 

not turn on

 

 

 

then check the voltages at the ignition module across pins 2 (blue) and 5 (brown) on the plug "CONTROL". If there is 24

 

 

 

 

 

 

 

 

VAC across these pins, then check to see if the "Rectifier Harness” (or gas valve harness on 100 gallon 399,999 BTU/hr

 

 

 

(117.2 kw) model) is secure. If it is secure, then replace the "Gas Valve".

 

 

 

If you can feel the gas valve energize, check to make sure the main gas supply is not in the off position.

 

 

 

 

 

 

 

Burner Flame

Is there minimum gas supplied to water heater as stated on the rating plate? If not, then increase the supply pressure to the

 

 

keeps going out

water heater (4.5 min. - 14 max.).

 

 

 

Measure the microAmps through the flame sensor using a multimeter. Is there at least 4 microAmps? If not, then replace

 

 

 

 

the "Flame Sensor" or flame sensor wire.

 

 

Thermostat does

Make sure that the temperature of the tank is cool.

 

 

not call for heat

If the thermostat does not call for heat, then check the PRIMARY voltage across the "Transformer". If there is voltage

 

 

 

across the PRIMARY, then check the voltage across the SECONDARY leads of the "Transformer".

 

 

 

Install a jumper wire from N.O. terminal to the COM terminal on the "Thermostat PC Board." If the thermostat calls for

 

 

 

 

heat after installing a jumper wire then check the "Thermostat Sensor Probe" leads for proper resistance with an OHM

 

 

 

meter (See appendix A).

 

 

 

If sensor reading is not correct, replace "Thermostat Sensor Probe."

 

 

 

If the sensor readings are correct, then check "Potentiometer" for the proper resistance. If the readings are correct, then

 

 

 

 

replace the "Thermostat PC Board"; If readings are not correct replace the "Potentiometer."

 

Manufactured under one or more of the following U.S. Patents: RE.34,534; B1 5,341,770; 4,416,222; 4,628,184; 4,669,448; 4,672,919; 4,808,356; 4,829,983; 4,861,968; 4,904,428; 5,000,893; 5,023,031; 5,052,346; 5,081,696; 5,092,519; 5,115,767; 5,199,385; 5,277,171; 5,372,185; 5,485,879; 5,574,822; 5,596,952; 5,660,165; 5,682,666; 5,761,379; 5,943,984; 5,954,492; 5,988,117; 6,142,216; 6,684,821; 7,063,132; 7,007,748;

Other U.S. and Foreign patent applications pending. Current Canadian Patents: 1,272,914; 1,280,043; 1,289,832; 2,045,862; 2,092,105; 2,107,012; 2,108,186; 2,112,515

45

Image 45
Contents What to do if YOU Smell GAS With Troubleshooting GuideTable of Contents Page Do not Operate the Appliance Until the Leakage is Corrected If YOU Smell GASDimensions Inches Section II SpecificationsSection III General Information FeaturesTemperature and Pressure Relief Valve Condensate Elbow With Trap Dishwashing Machine RequirementsSection IV Installation Instructions Minimum Clearance To Combustible Material UnpackingRemove Crate Recommended Minimum Clearances For Service AccessAIR Requirements LocationMechanical Exhausting of Room AIR Unconfined SpaceChemical Vapor Corrosion Typical Installation IllustrationTypical Two Water Heater Connection Section V Water Connections Instructions for ConnectionsScalding Alternate Space Heating Water Connections Approximate TIME/TEMPERATURE Relationships in ScaldsSection VI Venting Approved Venting Materials Venting Direct Vent InstallationCanadian US Installations2 Installations1 Clearance above Direct Vent Terminal Clearances Page Typical Horizontal Direct Vent System Typical Vertical Direct Vent System Installation Determining required vent length Power Vent InstallationPage Typical Horizontal Power Vent System Typical Vertical Power Vent System Installation Power Vent Maximum Vent Length Multiple INTAKE/EXHAUST Terminal Separation Distances Dimensional Layout of Concentric Vent Kit Concentric Vent Terminal Installation ProcedureRain Cap to Small Vent Pipe Ass’y Concentric Vent Side Wall Attachment Vent Pipe Preparation ModelsSection VII GAS Connections Initial PreparationSelection of Materials GAS Pressure Regulation GAS Meter Size Natural Gases onlySection Viii Electrical Connections Wiring Diagram and SchematicGeneral Instructions Section IX Operating InstructionsTo Fill the Water Heater Sequence of OperationLighting Instructions Temperature AdjustmentSight Glass Location Burner Flame CheckMaintenance Schedule Section X MaintenanceGeneral Flushing Water Heater Draining Water Heater Filling Water Heater Sediment and Lime Scale Removal To inspect or replace an anode Anode Inspection and ReplacementVent and AIR Intake System Drain Valve and Tank Access PanelCombustion System Inspection Section XI Troubleshooting GuideEF Series Water Heater Section XII Parts ListCombustion Surround Assy Ignition Control Assy