Bradford-White Corp D-38T-155 service manual Upper Sensor, Lower Sensor

Page 26

Conditions: Upper or Lower Sensor Reading Faulty, High Water Temperature, or suspect thermostat is not accurate.

SERVICE PROCEDURE D24-I

Thermostat Circuit Testing

Sensor Resistance Testing

Upper Sensor

1.Determine resistance value of upper sensor. Test across grey wires.

2.Draw quart of water off T&P valve. Using a thermometer, determine water temperature.

3.Use table below to verify correct resistance per water temperature measured.

Lower Sensor:

Upper thermister location

(applicable models)

10

1. Determine resistance value of lower sensor. Test across center wire (common) to each outside wire. Resistance of both thermisters in the lower sensor should be close to each other. If the resistance values for both thermisters are not close to each other, replace the lower sensor. The dual thermisters are used to provide high limit protection in case the thermostat circuit fails to shut off the water heater.

2. Draw quart of water off Drain Valve.

Using a thermometer, determine water temperature.

3.Use table below to verify correct resistance per water temperature measured.

Checking resistance of

upper sensor

Lower thermister

access located inside

control box.

11

Are readings N

Replace

 

correct?

 

thermister

Checking resistance of

Y

 

 

 

 

lower sensor (center and

Check harness

 

Replace

outside pins)

N

 

continuity.

 

 

harness

CAUTION

Continuity okay?

 

 

 

Y

 

 

Be Careful When Making Resistance

 

 

Measurements Not to Damage or

 

 

 

Replace

 

 

Deform Connectors or Connector Pins.

 

 

 

control board

 

Sensor Resistance at Various Temperatures

 

 

Example: If water temperature is 84°F, then the resistance through the sensor would be 8449 (see shaded area).

NOTE: Sensor resistance increases as the temperature falls.

In Degrees F

°F

0

1

2

3

4

5

6

7

8

9

40

26109

25400

24712

24045

23399

22771

22163

21573

21000

20445

50

19906

19383

18876

18383

17905

17440

16990

16553

16128

15715

60

15314

14925

14548

14180

13823

13477

13140

12812

12494

12185

70

11884

11592

11308

11032

10763

10502

10248

1000

9760

9526

80

9299

9078

8862

8653

8449

8250

8057

7869

7685

7507

90

7333

7165

7000

6839

6683

6531

6383

6238

6098

5961

100

5827

5697

5570

5446

5326

5208

5094

4982

4873

4767

110

4663

4562

4464

4368

4274

4183

4094

4006

3922

3839

120

3758

3679

3602

3527

3453

3382

3312

3244

3177

3112

130

3048

2986

2925

2866

2808

2752

2697

2643

2590

2538

140

2488

2439

2391

2344

2298

2253

2209

2166

2124

2083

150

2043

2004

1966

1928

1891

1856

1820

1786

1753

1720

160

1688

1656

1625

1595

1566

1537

1509

1481

1454

1427

170

1402

1376

1351

1327

1303

1280

1257

1235

1213

1191

180

1170

1150

1129

1110

1090

1071

1053

1035

1017

999

190

982

965

949

933

917

901

886

871

857

842

200

828

814

801

788

775

762

749

737

725

713

Page 26

26

Image 26
Contents Service Manual To be performed only by qualified service providersTable of Contents Features of Honeywell Integrated Controls System Tools Required for Service Specifications Sequence of Operation Lockout ConditionVoltage at primary pins 1&3 white TroubleshootingPins to black and white wires DefectiveFrom previous Displaying temperature SensorsExample of error code shown on control display Operate?Using Control Display for Servicing Water Heater Sensor is used Setpoint Display/Change Software Version Display only Select SET ExitingSELECTServiceSETMode Display of Water TemperatureTo Display and Change Temperature Setpoint To Display Flame Sense Current of the Pilot Flame SensorSetpoint Flashes Selectset Idle Status Operational Error Codes and Error History Display Error Code HistoryTo view previous error codes ExitingSELECTServiceSET Mode Error Code Definitions Error Code Shown Water Heater Display Press for 3 seconds to reset control in service modeDo not reset the display from the hard lockout Service Procedure D24-IThermostat Circuit Testing State without correcting the causeService Procedure D24-I Upper thermister location Applicable models Upper SensorLower Sensor 131 Service Procedure D24-IIPilot Operation Testing Pilot Inspection Meter Probe Micro-amp readings MeterProbe Micro Amp =114 Service Procedure D24-IIIMain Burner Operation Testing See Pilot Inspection section Build-up causing restrictionHeater. Refer to Installation Instructions InspectionMain Burner Removal Service Procedure D24-IVMain Burner & Pilot Removal and Inspection Main Burner InspectionFlame Rod Pilot Burner RemovalPilot Burner Inspection Ferrule NutTo remove lower sensor Control Board ReplacementControl board replacement Service Procedure D24-V Flue Baffle Removal, InspectionService Procedure D24-VI Approximate Anode Rod Locations Generic Parts List 15A 16/16A 17/17A13A 14A 16A 17A6A 11A 10A 18A 15A 19A 12A 20A 19B 20B 17B18B 16B 12B10B 13B 14B 15BECO BTU/HCO2 GFIPage Page Parts@bradfordwhite.com Techserv@bradfordwhite.com