PHASE CONVERSIONS - SURFACE MOUNT CONTROL MODELS

OPERATION & SERVICE

PHASE CONVERSIONS - SURFACE MOUNT CONTROL MODELS

Internal wiring connections between the Power Distribution Block and the heating elements are different on Surface Mount Control (see Figure 1 page 8) and Electronic Control (see Figure 2 page 9) model water heaters. Because of these differences there are two methods for field converting these models to work with single and three phase power supplies.

Service Note: 208 volt 54 KW models are 3 phase only and CAN NOT be converted to single phase. All other models can be phase converted.

SECURE MAIN POWER SUPPLY TO THE WATER HEATER AT THE MAIN BREAKER OR DISCONNECT SWITCH FIRST.

Service Warning: Never touch any wiring inside the water heater until the main power supply to the water heater has been turned off. Verify with a volt meter that all wiring has no voltage present before touching any wiring inside the water heater’s control panel.

Surface Mount Control Models

Three Phase to Single Phase

1Disconnect blue wires from terminal L-2.

2Connect all blue wires to terminal L-1 (with black wires).

3Disconnect all red wires from terminal l-3.

4Connect all red wires to terminal L-2 (with yellow wires).

5Incoming power will be connected to terminals L-1 and L-2.

Service Note: 208 volt 54 KW models are three phase only - these models CAN NOT be converted to single phase. Keep in mind when converting other models from three phase power to single phase power the current/amperage will increase significantly - ensure breakers, fuses and wiring are properly sized to allow for the increased amperage before placing the water heater back in service. Contact a Qualified/Licensed electrician to make necessary changes.

Power Distribution Block

(see Figure 1 on page 8)

L1 L2 L3

Surface Mount Control Models

Single Phase to Three Phase

1Disconnect blue wires from terminal L-1

2Disconnect red wires from terminal L-2.

3Connect all blue wires to terminal L-2 (with yellow wires).

4Connect red wires to terminal L-3.

5Incoming power will be connected to terminals L-1, L-2 and L-3.

Service Note: Keep in mind when converting from single phase power to three phase power the current/amperage will decrease significantly - ensure breakers and fuses are not oversized before placing the water heater back in service. Contact a Qualified/ Licensed electrician to make necessary changes.

Power Distribution Block

(see Figure 1 on page 8)

L1 L2 L3

Servicing should only be performed by a Qualified Service Agent

15

Image 17
Contents COMMERCIAL ELECTRIC WATER HEATERS Service HandbookMODELS STCE3-52/80/119 & ITCE3-52/80/119 Technical Support and PartsPage COMMERCIAL ELECTRIC WATER HEATER TABLE OF CONTENTSSERVICE MANUAL SERVICE WARNING QUALIFICATIONS - QUALIFIED SERVICE AGENTIMPORTANT SERVICE REMINDER INTRODUCTIONTOOLS REQUIRED INSTRUCTION MANUALTHERMAL EXPANSION INSTALLATION CONSIDERATIONSCLOSED WATER SYSTEMS Grounding Power SupplyELECTRICAL REQUIREMENTS SERVICE PRECAUTIONS PRE SERVICE CHECKSWIRING CONNECTIONS WATER HEATER CONSTRUCTION HEATING ELEMENT CONFIGURATIONSSURFACE MOUNT CONTROL MODELS ELECTRONIC CONTROL MODELSWATER HEATER CONSTRUCTION SURFACE MOUNT CONTROL MODELSWATER HEATER CONSTRUCTION PRINCIPLES OF ELECTRICITY OPERATION & SERVICEVoltage AmperageCalculating Amps/Ohms/Volts/Watts Ohms Law applied to “SINGLE PHASE” 1Ø powerOhms Law L1 L2 L3 SINGLE AND THREE PHASE POWERChecking Single Phase 1Ø Power 1 L1 and L2 terminals of the water heater’s Power Distribution Block Checking Three Phase 3Ø Power2 L2 and L3 terminals of the water heater’s Power Distribution Block 3 L1 and L3 terminals of the water heater’s Power Distribution BlockSurface Mount Control Models Single Phase to Three Phase PHASE CONVERSIONS - SURFACE MOUNT CONTROL MODELSSurface Mount Control Models Three Phase to Single Phase Electronic Control Models Single Phase to Three Phase PHASE CONVERSIONS - ELECTRONIC CONTROL MODELSElectronic Control Models Three Phase to Single Phase Volt Meter Method FUSESOhm Meter Method SURFACE MOUNT THERMOSTATS Thermostat & ECO Test Wire conductor inside tube HEATING ELEMENTSHeating Element Construction NUMBER OF FACTORY INSTALLED Heating Element ConfigurationsHeating Element Ratings TOTALELEMENT Heating Element AmperageAPPROXIMATE CURRENT - AMPS 208 VACHeating Element Amperage Test Heating Element Voltage Test Measuring Resistance Heating Element Resistance & Ground TestsReplacing Heating Elements Heating Element Ground TestElement Sensor Construction ELEMENT SENSORSElement Sensor Three Current Sensors Element Sensor FunctionsElement Sensor Operation Contactor Construction - How They Work CONTACTORSPower Connection Terminals Contactor ConfigurationsElement Numbers/Connections Wire Colors to Elements ContactorsPhysically Operate Mechanical Contactor InspectionContactor Coil Voltage - At Contactor Contactor Coil Voltage - At CCB X1 120 VAC 120 VAC Control Circuit Transformer WiringTRANSFORMERS H1 H2 H3 H4 H5 N/A Primary Winding Secondary WindingSecondary Winding Voltage Test 120 VAC Control Circuit Transformer TestPrimary Winding Voltage Test 24 VAC Transformer Test Temperature Sensor ECO High Temperature Limit SwitchIMMERSION TEMPERATURE PROBE Temperature Sensor Resistance Data Temperature Sensor Resistance TestChecking Temperature Sensor Resistance WATER TEMPERATUREECO Continuity Test Temperature Sensor DC Voltage TestChecking ECO Switch Continuity DC Voltage To Temperature Sensor120 VAC To ECO ECO Voltage Test120 VAC From ECO Ground ConnectionUIM User Interface Module CCB Central Control Board ELECTRONIC CONTROLSCCB - CENTRAL CONTROL BOARD J2 Socket - 120 VAC Power Supply CCB Socket & Wiring Terminal IdentificationJ3 Wiring Terminals - Alarm Output Relay see page J4 Wiring Terminals - Contactor CoilsJ16 Socket - Not Used J17 Wiring Terminals - Not Used J7 Socket - Enable / Disable Circuits 1 & 2 see pages 45J8 Socket - Not Used J9 Socket - Not Used J10 Socket - Not Used J13 Socket - Heating Element Sensors BankCCB Enable/Disable Circuits Test Checking for Ground Checking Power and Ground To The CCBChecking for 120 VAC UIM - USER INTERFACE MODULE Service Notes - Button Pad Ribbon CableUIM Circuit Board Back UIM Circuit Board FrontELECTRONIC CONTROL SYSTEM CONTROL SYSTEM FEATURESCONTROL SYSTEM NAVIGATION UIM - User Interface ModuleTHE DESKTOP SCREEN ICON Table 1 Status IconsTable 3 - Control System Menus Table 2 - Operating StatesSTATE MENUS†TEMPERATURES MENU Differential SettingsOperating Set Point Tank TemperatureTemperature Settings Alarm Condition Enable / Disable 1Alarm Relay Output HEATER STATUS MENUSetpoint Adjustment ECONOMY MODE SETUP MENUDesktop Screen During Economy Mode Economy Mode Setup Menu Current TimeEconomy Mode Settings Setpoint Adjustment Value Economy Mode Settings Time Clock Settings Normal Operation Between Economy Mode Settings Daily Operating Mode SettingsEconomy Mode All Day Temp Alarm SP Used for external ALARM OUTPUT SETUP MENUAlarm SP Alarm Output SettingsDisplay Settings DISPLAY SETTINGS MENUTemperature Units Backlight DelayElapsed Time HEATER INFORMATION MENUTotal Heating Time Bank # CyclesFAULT HISTORY MENU CURRENT FAULT / ALERT MENUFAULT OCCURRENCE MENU Main Menu - Current Fault Selected Fault History MenuFactory Default User Settings RESTORE FACTORY DEFAULTS MENURestore Factory Defaults COMMON SERVICE PROBLEMS TROUBLESHOOTINGNo Hot Water Not Enough Hot WaterResetting Control System Fault ConditionsCONTROL SYSTEM UNRESPONSIVE Alert ConditionsUIM is Inoperable Heating Cycle DisabledControl System Unresponsive cont “No Current Detected” FAULT AND ALERT MESSAGES“Temp Probe Short” Fault & Alert Messages“Temp Probe Open” “Energy Cut Out ECO” Page Page Page Page Technical Support and Parts