American Water Heater ITCE3-52/80/119, STCE3-52/80/119 manual Heating Element Amperage Test

Page 25
Heating Element Amperage Test

OPERATION & SERVICE

Heating Element Amperage Test

This test should be considered as a first diagnostic procedure for the common service complaints of no hot water or not enough hot water. The heating element amperage test shown on this page is the best procedure to quickly determine which (if any) heating elements are not working properly.

1Secure power to the water heater at the main breaker or disconnect switch.

2Ensure tank temperature is less than 100°F/38°C - dump water to lower tank temperature if necessary.

3Surface Mount Control Models - raise the temperature settings to ensure a call heat is active for all heating elements. Press the red reset button firmly on all thermostat/ECO controls then raise the temperature setting on all thermostat/ECO controls to 140°F or higher - see page 18.

4Restore power to the water heater.

5Electronic Control Models - adjust the temperature settings to ensure a call heat is active for all heating elements. Raise the Operating Set Point in the Temperatures Menu to 140°F or higher. Set all Heating Element Bank Differentials in the Temperatures Menu to 2°F - see pages 52 and 53.

6Using a clamp style AC amp meter: set the amp meter to an AC amperage range just above the expected amperage (100 AC amp range initially). Measure and record the amperage at all heating elements by clamping the jaws of the meter around ONLY one of the wires to each heating element. See the image below. Heating element amp readings should be approximately the same for all heating elements. The normal operating amps for all heating elements is provided in the Heating Element Amperage table on page 22 or it can be calculated using ohms law as explained on page 11.

Service Note: Check all power circuit wiring to the heating element(s) on any element drawing zero or low amps - see the wiring diagram on the water heater. On Electronic Control Models check the contactors on any heating element(s) drawing zero or low amps - see pages 29 - 33. Perform the Heating Element Voltage and Heating Element Resistance & Ground tests (see pages 24 - 26) on any heating elements drawing zero amps or any heating element drawing less than normal operating amps.

If the measured amp draw on any element is considerably less or more than the normal operating amps ensure the voltage and KW rating of those heating elements is the correct value for the water heater being serviced - see Heating Element Ratings and Heating Element Configurations on page 21.

Measuring amperage on an electric heating element. Make sure the jaws of the AC amp meter are clamped around ONLY ONE WIRE to the heating element being tested. Clamping around more than one wire often gives a false zero amp reading.

DO NOT TOUCH THE ENDS OF ANY

HEATING ELMENTS WHILE PERFORMING

THIS TEST

Be extremely careful as there will be high voltage present at the wiring terminals on all heating elements during this test.

Servicing should only be performed by a Qualified Service Agent

23

Image 25
Contents COMMERCIAL ELECTRIC WATER HEATERS Service HandbookMODELS STCE3-52/80/119 & ITCE3-52/80/119 Technical Support and PartsPage SERVICE MANUAL TABLE OF CONTENTSCOMMERCIAL ELECTRIC WATER HEATER SERVICE WARNING QUALIFICATIONS - QUALIFIED SERVICE AGENTIMPORTANT SERVICE REMINDER INTRODUCTIONTOOLS REQUIRED INSTRUCTION MANUALCLOSED WATER SYSTEMS INSTALLATION CONSIDERATIONSTHERMAL EXPANSION ELECTRICAL REQUIREMENTS Power SupplyGrounding WIRING CONNECTIONS PRE SERVICE CHECKSSERVICE PRECAUTIONS WATER HEATER CONSTRUCTION HEATING ELEMENT CONFIGURATIONSSURFACE MOUNT CONTROL MODELS ELECTRONIC CONTROL MODELSWATER HEATER CONSTRUCTION SURFACE MOUNT CONTROL MODELSWATER HEATER CONSTRUCTION PRINCIPLES OF ELECTRICITY OPERATION & SERVICEVoltage AmperageOhms Law Ohms Law applied to “SINGLE PHASE” 1Ø powerCalculating Amps/Ohms/Volts/Watts L1 L2 L3 SINGLE AND THREE PHASE POWERChecking Single Phase 1Ø Power 1 L1 and L2 terminals of the water heater’s Power Distribution Block Checking Three Phase 3Ø Power2 L2 and L3 terminals of the water heater’s Power Distribution Block 3 L1 and L3 terminals of the water heater’s Power Distribution BlockSurface Mount Control Models Three Phase to Single Phase PHASE CONVERSIONS - SURFACE MOUNT CONTROL MODELSSurface Mount Control Models Single Phase to Three Phase Electronic Control Models Three Phase to Single Phase PHASE CONVERSIONS - ELECTRONIC CONTROL MODELSElectronic Control Models Single Phase to Three Phase Ohm Meter Method FUSESVolt Meter Method SURFACE MOUNT THERMOSTATS Thermostat & ECO Test Heating Element Construction HEATING ELEMENTSWire conductor inside tube NUMBER OF FACTORY INSTALLED Heating Element ConfigurationsHeating Element Ratings TOTALELEMENT Heating Element AmperageAPPROXIMATE CURRENT - AMPS 208 VACHeating Element Amperage Test Heating Element Voltage Test Measuring Resistance Heating Element Resistance & Ground TestsReplacing Heating Elements Heating Element Ground TestElement Sensor Construction ELEMENT SENSORSElement Sensor Three Current Sensors Element Sensor FunctionsElement Sensor Operation Contactor Construction - How They Work CONTACTORSPower Connection Terminals Contactor ConfigurationsElement Numbers/Connections Wire Colors to Elements ContactorsPhysically Operate Mechanical Contactor InspectionContactor Coil Voltage - At Contactor Contactor Coil Voltage - At CCB X1 120 VAC 120 VAC Control Circuit Transformer WiringTRANSFORMERS H1 H2 H3 H4 H5 N/A Primary Winding Secondary WindingPrimary Winding Voltage Test 120 VAC Control Circuit Transformer TestSecondary Winding Voltage Test 24 VAC Transformer Test IMMERSION TEMPERATURE PROBE ECO High Temperature Limit SwitchTemperature Sensor Temperature Sensor Resistance Data Temperature Sensor Resistance TestChecking Temperature Sensor Resistance WATER TEMPERATUREECO Continuity Test Temperature Sensor DC Voltage TestChecking ECO Switch Continuity DC Voltage To Temperature Sensor120 VAC To ECO ECO Voltage Test120 VAC From ECO Ground ConnectionUIM User Interface Module CCB Central Control Board ELECTRONIC CONTROLSCCB - CENTRAL CONTROL BOARD J2 Socket - 120 VAC Power Supply CCB Socket & Wiring Terminal IdentificationJ3 Wiring Terminals - Alarm Output Relay see page J4 Wiring Terminals - Contactor CoilsJ16 Socket - Not Used J17 Wiring Terminals - Not Used J7 Socket - Enable / Disable Circuits 1 & 2 see pages 45J8 Socket - Not Used J9 Socket - Not Used J10 Socket - Not Used J13 Socket - Heating Element Sensors BankCCB Enable/Disable Circuits Test Checking for 120 VAC Checking Power and Ground To The CCBChecking for Ground UIM - USER INTERFACE MODULE Service Notes - Button Pad Ribbon CableUIM Circuit Board Back UIM Circuit Board FrontELECTRONIC CONTROL SYSTEM CONTROL SYSTEM FEATURESCONTROL SYSTEM NAVIGATION UIM - User Interface ModuleTHE DESKTOP SCREEN ICON Table 1 Status IconsTable 3 - Control System Menus Table 2 - Operating StatesSTATE MENUS†TEMPERATURES MENU Differential SettingsOperating Set Point Tank TemperatureTemperature Settings Alarm Condition Enable / Disable 1Alarm Relay Output HEATER STATUS MENUSetpoint Adjustment ECONOMY MODE SETUP MENUDesktop Screen During Economy Mode Economy Mode Setup Menu Current TimeEconomy Mode Settings Setpoint Adjustment Value Economy Mode Settings Time Clock Settings Economy Mode All Day Economy Mode Settings Daily Operating Mode SettingsNormal Operation Between Temp Alarm SP Used for external ALARM OUTPUT SETUP MENUAlarm SP Alarm Output SettingsDisplay Settings DISPLAY SETTINGS MENUTemperature Units Backlight DelayElapsed Time HEATER INFORMATION MENUTotal Heating Time Bank # CyclesFAULT HISTORY MENU CURRENT FAULT / ALERT MENUFAULT OCCURRENCE MENU Main Menu - Current Fault Selected Fault History MenuRestore Factory Defaults RESTORE FACTORY DEFAULTS MENUFactory Default User Settings COMMON SERVICE PROBLEMS TROUBLESHOOTINGNo Hot Water Not Enough Hot WaterResetting Control System Fault ConditionsCONTROL SYSTEM UNRESPONSIVE Alert ConditionsControl System Unresponsive cont Heating Cycle DisabledUIM is Inoperable “No Current Detected” FAULT AND ALERT MESSAGES“Temp Probe Open” Fault & Alert Messages“Temp Probe Short” “Energy Cut Out ECO” Page Page Page Page Technical Support and Parts