American Water Heater COMMERCIAL ELECTRIC WATER HEATERS manual CCB Enable/Disable Circuits Test

Page 47
CCB Enable/Disable Circuit(s) Test

ELECTRONIC CONTROLS

CCB Enable/Disable Circuit(s) Test

The electronic control system includes two enable/disable circuits (see page 54) for use with field installed supervisory controls such as building EMS (Energy Management System). These two circuits are located at the CCB’s four pin J7 Socket. Both of these Enable/Disable circuits must be closed to enable heating operation. If either circuit is open for any reason heating operation will be disabled even though the tank temperature may be well below the Operating Set Point - see Heating Cycle Disabled on page 66.

There is a plug with two jumper wires installed from the factory in the CCB J7 socket to enable heating operation when external controls are not in use. If the plug is not present or if one of the two jumper wires fails to close either enable/disable circuit heating operation will be disabled. A simple continuity check is performed on the J7 Plug end to ensure heating should not be disabled as follows:

1If either enable/disable circuit is in use (external wiring connected to J7 plug) by an external supervisory control - ensure that control’s dry contacts are closed to enable heating operation. Check the supervisory control’s settings/programming to ensure it is not disabling heating operation during occupied/normal demand periods.

2If the J7 plug is missing or jumper wires are not installed in the J7 plug - call the toll free Technical Support phone number listed on the back cover of this manual for further assistance

3If there are no external supervisory controls wired to the J7 plug: Secure power to the water heater. Unplug the J7 plug from the CCB circuit board - see page 42 for location.

4Using an ohm meter; set the Ohm meter to it’s lowest resistance range (< 200) or to an audible beep continuity test setting if so equipped.

5Touch the ohm meter probes between pins 1 & 2 first and then between pins 3 & 4 of the J7 plug end as shown in the images below. There should be continuity present in both tests.

If the ohm meter shows no continuity (open circuit) between pins 1 & 2 or between pins 3 & 4 of the J7 plug end ensure the two jumper wires are properly installed in the plug end and are not broken. Ensure the J7 plug/socket connection is mating properly and providing good contact. Repair/replace damaged plug connectors/wiring as necessary.

If the ohm meter shows continuity (closed circuit) between pins 1 & 2 and between pins 3 & 4 of the J7 plug end and heating operation will not activate with a cold tank of water call the toll free Technical Support phone number listed on the back cover of this manual for further assistance.

Service Note: If a supervisory control(s) is used to enable/disable heating operation, install field wiring between the J7 socket on the CCB and a set of “dry contacts” on the external control per all applicable building codes. This is a switching circuit only: DO NOT apply any external voltage or connect any load (IE: relay coil) to either circuit.

Servicing should only be performed by a Qualified Service Agent

45

Image 47
Contents Technical Support and Parts Service HandbookCOMMERCIAL ELECTRIC WATER HEATERS MODELS STCE3-52/80/119 & ITCE3-52/80/119Page COMMERCIAL ELECTRIC WATER HEATER TABLE OF CONTENTSSERVICE MANUAL INTRODUCTION QUALIFICATIONS - QUALIFIED SERVICE AGENTSERVICE WARNING IMPORTANT SERVICE REMINDERTOOLS REQUIRED INSTRUCTION MANUALTHERMAL EXPANSION INSTALLATION CONSIDERATIONSCLOSED WATER SYSTEMS Grounding Power SupplyELECTRICAL REQUIREMENTS SERVICE PRECAUTIONS PRE SERVICE CHECKSWIRING CONNECTIONS ELECTRONIC CONTROL MODELS HEATING ELEMENT CONFIGURATIONSWATER HEATER CONSTRUCTION SURFACE MOUNT CONTROL MODELSWATER HEATER CONSTRUCTION SURFACE MOUNT CONTROL MODELSWATER HEATER CONSTRUCTION Amperage OPERATION & SERVICEPRINCIPLES OF ELECTRICITY VoltageCalculating Amps/Ohms/Volts/Watts Ohms Law applied to “SINGLE PHASE” 1Ø powerOhms Law L1 L2 L3 SINGLE AND THREE PHASE POWERChecking Single Phase 1Ø Power 3 L1 and L3 terminals of the water heater’s Power Distribution Block Checking Three Phase 3Ø Power1 L1 and L2 terminals of the water heater’s Power Distribution Block 2 L2 and L3 terminals of the water heater’s Power Distribution BlockSurface Mount Control Models Single Phase to Three Phase PHASE CONVERSIONS - SURFACE MOUNT CONTROL MODELSSurface Mount Control Models Three Phase to Single Phase Electronic Control Models Single Phase to Three Phase PHASE CONVERSIONS - ELECTRONIC CONTROL MODELSElectronic Control Models Three Phase to Single Phase Volt Meter Method FUSESOhm Meter Method SURFACE MOUNT THERMOSTATS Thermostat & ECO Test Wire conductor inside tube HEATING ELEMENTSHeating Element Construction TOTAL Heating Element ConfigurationsNUMBER OF FACTORY INSTALLED Heating Element Ratings208 VAC Heating Element AmperageELEMENT APPROXIMATE CURRENT - AMPSHeating Element Amperage Test Heating Element Voltage Test Measuring Resistance Heating Element Resistance & Ground TestsReplacing Heating Elements Heating Element Ground TestThree Current Sensors Element Sensor Functions ELEMENT SENSORSElement Sensor Construction Element SensorElement Sensor Operation Contactor Construction - How They Work CONTACTORSContactors Contactor ConfigurationsPower Connection Terminals Element Numbers/Connections Wire Colors to ElementsPhysically Operate Mechanical Contactor InspectionContactor Coil Voltage - At Contactor Contactor Coil Voltage - At CCB H1 H2 H3 H4 H5 N/A Primary Winding Secondary Winding 120 VAC Control Circuit Transformer WiringX1 120 VAC TRANSFORMERSSecondary Winding Voltage Test 120 VAC Control Circuit Transformer TestPrimary Winding Voltage Test 24 VAC Transformer Test Temperature Sensor ECO High Temperature Limit SwitchIMMERSION TEMPERATURE PROBE WATER TEMPERATURE Temperature Sensor Resistance TestTemperature Sensor Resistance Data Checking Temperature Sensor ResistanceDC Voltage To Temperature Sensor Temperature Sensor DC Voltage TestECO Continuity Test Checking ECO Switch ContinuityGround Connection ECO Voltage Test120 VAC To ECO 120 VAC From ECOUIM User Interface Module CCB Central Control Board ELECTRONIC CONTROLSCCB - CENTRAL CONTROL BOARD J4 Wiring Terminals - Contactor Coils CCB Socket & Wiring Terminal IdentificationJ2 Socket - 120 VAC Power Supply J3 Wiring Terminals - Alarm Output Relay see pageJ13 Socket - Heating Element Sensors Bank J7 Socket - Enable / Disable Circuits 1 & 2 see pages 45J16 Socket - Not Used J17 Wiring Terminals - Not Used J8 Socket - Not Used J9 Socket - Not Used J10 Socket - Not UsedCCB Enable/Disable Circuits Test Checking for Ground Checking Power and Ground To The CCBChecking for 120 VAC UIM Circuit Board Front Service Notes - Button Pad Ribbon CableUIM - USER INTERFACE MODULE UIM Circuit Board BackUIM - User Interface Module CONTROL SYSTEM FEATURESELECTRONIC CONTROL SYSTEM CONTROL SYSTEM NAVIGATIONTHE DESKTOP SCREEN ICON Table 1 Status IconsMENUS† Table 2 - Operating StatesTable 3 - Control System Menus STATETank Temperature Differential SettingsTEMPERATURES MENU Operating Set PointTemperature Settings HEATER STATUS MENU Enable / Disable 1Alarm Condition Alarm Relay OutputCurrent Time ECONOMY MODE SETUP MENUSetpoint Adjustment Desktop Screen During Economy Mode Economy Mode Setup MenuEconomy Mode Settings Setpoint Adjustment Value Economy Mode Settings Time Clock Settings Normal Operation Between Economy Mode Settings Daily Operating Mode SettingsEconomy Mode All Day Alarm Output Settings ALARM OUTPUT SETUP MENUTemp Alarm SP Used for external Alarm SPBacklight Delay DISPLAY SETTINGS MENUDisplay Settings Temperature UnitsBank # Cycles HEATER INFORMATION MENUElapsed Time Total Heating TimeMain Menu - Current Fault Selected Fault History Menu CURRENT FAULT / ALERT MENUFAULT HISTORY MENU FAULT OCCURRENCE MENUFactory Default User Settings RESTORE FACTORY DEFAULTS MENURestore Factory Defaults Not Enough Hot Water TROUBLESHOOTINGCOMMON SERVICE PROBLEMS No Hot WaterAlert Conditions Fault ConditionsResetting Control System CONTROL SYSTEM UNRESPONSIVEUIM is Inoperable Heating Cycle DisabledControl System Unresponsive cont “No Current Detected” FAULT AND ALERT MESSAGES“Temp Probe Short” Fault & Alert Messages“Temp Probe Open” “Energy Cut Out ECO” Page Page Page Page Technical Support and Parts