American Water Heater 1010 319869-000 warranty ALL AIR from Outdoors See Figures 12, 13

Page 17

FIGURE 11

B.ALL AIR FROM OUTDOORS: (See Figures 12, 13 and 14)

The confined space should be provided with two permanent openings, one commencing within 12 in. (30cm) of the top and one commencing within 12 in. (30cm) from the bottom of the enclosure. The openings should communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

1.When directly communicating with the outdoors, each opening should have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure (see Figure 12).

FIGURE 13

4.When ducts are used, they should be of the same cross-sectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts should not be less than 3 in. (7.6cm) (see Figure 14).

FIGURE 12

2.When communicating with the outdoors through vertical ducts, each opening should have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure (see Figure 13).

3.When communicating with the outdoors through horizontal ducts, each opening should have a minimum free area of 1 square inch per 2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment in the enclosure (see Figure 14).

FIGURE 14

5.Alternatively a single permanent opening may be used when communicating directly with the outdoors, or with spaces that freely communicate with the outdoors. The opening should have a minimum free area of 1 square inch per 3,000 BTU per hour (8.3 cm2/kW) of total input rating of all equipment in enclosure (see Figure 15).

FIGURE 15

www.americanwaterheater.com

17

Image 17
Contents AN Odorant is Added to the GAS Used By this Water Heater Power Vent GAS ModelsTable of Contents Important Definitions Safe INSTALLATION, USE and ServiceGeneral Safety Can be triggered at any time Introduction Preparing for the InstallationPage Operation Replacement Parts and Deliming ProductsGET to Know Your Water Heater GAS Models Rough in Dimensions Installation ConsiderationsDirectly BELOW. Keep Clear of ALL Obstructions Suggested Piping Arrangement For TOP Connections Water Piping Mixing Valve UsageWater Potable Heating All models are considered Hotter Water can ScaldFacts to Consider about Location Handle Installation Earthquake Zones Page Appliances in Confined Spaces Combustion AIR and VentilationAppliances in Unconfined Spaces ALL AIR from Outdoors See Figures 12, 13 Water Piping Chemical Vapor CorrosionClosed Water Systems Thermal ExpansionHard Water TEMPERATURE-PRESSURE Relief ValveValve and Pipe Insulation if supplied GAS Piping GAS Line Purging High Altitude InstallationsFLOODING/FREEZING Filling the Water HeaterPlanning the Vent System Vent Pipe TerminationIf using 3 inch vent pipe If using 2 inch vent pipeVent Terminal INSTALLATION, Sidewall Installation of Vent SystemCondensate Masonry Side WallsVent terminals supplied with heater must be used Sequence of InstallationsInstallation Sequence Installation of Vertical Vent System Installation of Vent SYSTEM, SidewallSelection of Materials Vent Pipe PreparationInitial Preparation Step B Recommended BRUSH* Size for Primer Cement ApplicationsStep a Step G Connection to Vent Pipe Step EStep F Power Vent Calibration Electrical ConnectionsFilling the Water Heater Display Panel Operating InstructionsPage MCU Lighting Instructions For Your Safety Read Before LightingHeat Cycle Definitions State Description Temperature Regulation Temperature Probes Unique Hybrid FeaturesPage Temperature Regulation Operational Conditions Constant Output Temperature ControlStart UP Conditions Maintenance Motors Cleaning the Heat Engine Cleaning the Inlet Water FilterSnow Accumulation Flushing the Heat Exchanger Lime BUILD- UPDraining the Tank Fault Indication and Error CodesCode Display Example Format Diagnostic DisplayRemarks Fault Lockout Code Description Cause Remedy Type Displayed Fault Lockout Code Description Cause Remedy Type Displayed Fault Lockout Code Description Cause Remedy Type Displayed Troubleshooting There is no HOT Water or When the TAP is OpenedHOT Water Turns Cold Stays ColdLeakage Checkpoints ServiceParts Identification Item # Description AB C DEF KIT # Replacement Parts DescriptionNIP/DIP/TBO/HT Claim Procedure Service and Labor ResponsibilityConditions and Exceptions Limitation on Implied WarrantiesPage