American Water Heater 1010 319869-000 warranty Motors

Page 44

softened water is exceedingly corrosive because the process substitutes sodium ions for magnesium and calcium ions. The use of a water softener may decrease the life of the water heater tank. The anode rod should be inspected after 3 years of use and annually thereafter until the condition of the anode rod dictates its replacement.

NOTE: Artificially softened water requires the anode rod to be inspected annually.

The following are typical (but not all) signs of a depleted anode rod:

The majority of the rods diameter is less than 3/8”.

Significant sections of the support wire (approx. 1/3 or more of the anode rod’s length) are visible.

If the anode rod show signs of either or both it should be replaced.

NOTE: Whether re-installing or replacing the anode rod, check for any leaks and immediately correct if found.

1.Disconnect the electrical power to the water heater.

2.Close the shutoff valve on the cold-water line.

3.Follow the instructions in the “Draining The Tank” section in the Operating Manual to drain approximately 5 gallons (20 litres) of water from the tank.

4.Close the drain valve.

5.Disconnect the hot-water piping from the Hot Water Outlet Nipple/Anode.

6.Remove the Hot Water Outlet Nipple/Anode.

ANODE ROD REPLACEMENT

TEMPERATURE-PRESSURE RELIEF VALVE OPERATION

FIGURE 37

The temperature-pressure relief valve lever must be operated at least once a year to ensure that the water ways are clear. When checking the temperature-pressure relief valve operation, make sure that:

1.

No one is in front of or around the outlet of the

 

temperature-pressure relief valve discharge line.

2.

The water discharge will not cause any property

 

damage, as the water may be extremely hot.

Anode Rod Depletion

Exposed

Support

Wire

Pitted

Anode

Rod

Exposed Support Wire

FIGURE 36

If it is nessesary to replace the anode rod, refer to the detailed instructions that are supplied with the replacement anode.

See the “Parts Reference Illustration” for anode rod location.

Else:

Re-install the Hot Water Outlet Nipple/Anode.

Reconnect the hot-water piping to the Hot Water Outlet Nipple/ Anode.

Open the shutoff valve on the cold-water line.

Fill the tank following the instructions in the “Filling The Water Heater”.

Check for leaks and repair as required.

Reconnect the electrical power to the water heater.

Restart the water heater following the “Lighting Instructions”.

3. A discharge line is connected to this valve, directing

the flow of hot water from the valve to a proper

placement for disposal.

If water does not flow freely when the lever is in the open position, replacement of the valve is required. Turn off the cold water inlet heater and call a qualified service man.

If after manually operating the valve (see Figure 37), it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.

If the temperature-pressure relief valve on the appliance weeps or discharges periodically, this may be due to thermal expansion. You may have a check valve installed in the water line or a water meter with a check valve. Consult your local water supplier or a qualified service agency for further information. Do not plug the temperature-pressure relief valve.

MOTORS

Motors are permanently lubricated and do not need periodic lubrication. Keep fan and motor free of dust and dirt by cleaning annually.

44

www.americanwaterheater.com

Image 44
Contents Power Vent GAS Models AN Odorant is Added to the GAS Used By this Water HeaterTable of Contents Safe INSTALLATION, USE and Service Important DefinitionsGeneral Safety Can be triggered at any time Preparing for the Installation IntroductionPage Operation Replacement Parts and Deliming ProductsGET to Know Your Water Heater GAS Models Installation Considerations Rough in DimensionsDirectly BELOW. Keep Clear of ALL Obstructions Water Piping Mixing Valve Usage Suggested Piping Arrangement For TOP ConnectionsWater Potable Heating All models are considered Hotter Water can ScaldFacts to Consider about Location Handle Installation Earthquake Zones Page Appliances in Confined Spaces Combustion AIR and VentilationAppliances in Unconfined Spaces ALL AIR from Outdoors See Figures 12, 13 Chemical Vapor Corrosion Water PipingClosed Water Systems Thermal ExpansionTEMPERATURE-PRESSURE Relief Valve Hard WaterValve and Pipe Insulation if supplied GAS Piping High Altitude Installations GAS Line PurgingFLOODING/FREEZING Filling the Water HeaterVent Pipe Termination Planning the Vent SystemIf using 2 inch vent pipe If using 3 inch vent pipeInstallation of Vent System Vent Terminal INSTALLATION, SidewallCondensate Masonry Side WallsVent terminals supplied with heater must be used Sequence of InstallationsInstallation Sequence Installation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemSelection of Materials Vent Pipe PreparationInitial Preparation Step B Recommended BRUSH* Size for Primer Cement ApplicationsStep a Step G Connection to Vent Pipe Step EStep F Power Vent Calibration Electrical ConnectionsFilling the Water Heater Operating Instructions Display PanelPage MCU For Your Safety Read Before Lighting Lighting InstructionsHeat Cycle Definitions State Description Temperature Regulation Unique Hybrid Features Temperature ProbesPage Temperature Regulation Operational Conditions Constant Output Temperature ControlStart UP Conditions Maintenance Motors Cleaning the Inlet Water Filter Cleaning the Heat EngineSnow Accumulation Flushing the Heat Exchanger Lime BUILD- UPFault Indication and Error Codes Draining the TankCode Display Example Format Diagnostic DisplayRemarks Fault Lockout Code Description Cause Remedy Type Displayed Fault Lockout Code Description Cause Remedy Type Displayed Fault Lockout Code Description Cause Remedy Type Displayed Troubleshooting When the TAP is Opened There is no HOT Water orHOT Water Turns Cold Stays ColdService Leakage CheckpointsParts Identification Item # Description AB C DEF KIT # Replacement Parts DescriptionNIP/DIP/TBO/HT Service and Labor Responsibility Claim ProcedureConditions and Exceptions Limitation on Implied WarrantiesPage