Mitsubishi Electronics MSZ-FD25VAS, MSZ-FD35VAS service manual Indoor unit failure mode table

Page 23

4. Indoor unit failure mode table

POWER lamp

Abnormal point

Condition

Correspondence

(Failure mode)

 

 

 

 

 

 

 

Not lighted

Normal

 

 

 

 

1-time flash

Room temperature

The room temperature thermistor short

Refer to the characteristics of the room

or open circuit is detected every 8 seconds

every 0.5-second

thermistor

temperature thermistor (10-7.).

during operation.

 

 

 

 

 

 

 

2-time flash

 

The indoor coil thermistor short or open

Refer to the characteristics of the main

Indoor coil thermistor

circuit is detected every 8 seconds during

indoor coil thermistor, the sub indoor coil

2.5-second OFF

 

operation.

thermistor (10-7.).

 

 

 

 

 

 

3-time flash

Serial signal

The serial signal from outdoor unit is

Refer to 10-6.D"How to check miswiring

2.5-second OFF

not received for 6 minutes.

and serial signal error".

 

 

 

 

 

11-time flash

 

The rotational frequency feedback signal is

Refer to 10-6.A"Check of indoor fan

Indoor fan motor

not sent out for 12-seconds after indoor fan

2.5-second OFF

motor".

 

motor is operated.

 

 

 

 

 

 

 

12-time flash

 

It cannot properly read data in the

Replace the indoor electronic control

Indoor control system

nonvolatile memory of the indoor electronic

2.5-second OFF

P.C. board.

 

control P.C. board.

 

 

 

 

 

 

 

NOTE : Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-4.).

5. PLASMA operation failure mode table

POWER lamp

Abnormal point

Condition

Correspondence

(Failure mode)

 

 

 

 

 

 

 

 

 

PLASMA power supply cannot be turned

Replace the indoor electronic control

1-time flash

PLASMA power supply

OFF even if the PLASMA operation is turned

P.C.board.

 

control

OFF with the remote controller.

 

 

 

 

 

 

 

The voltage between CN1 3(+) and 2(GND)

 

2-time flash

Spark discharge

on the PLASMA POWER P.C.board falls

 

below 1.6 V(spark discharge judgment

 

 

 

voltage).

 

 

 

 

 

 

Abnormal electric

The voltage between CN1 3(+) and 2(GND)

Refer to 10-6.F"Check of PLASMA

3-time flash

on the PLASMA POWER P.C.board falls by

operation".

discharge error 1

0.9 V below the normal voltage value (3 V).

 

 

 

 

 

 

 

The voltage between CN1 3(+) and 2(GND)

 

4-time flash

Abnormal electric

on the PLASMA POWER P.C.board falls

 

discharge error 2

significantly. (0.4 V / 0.5 ms)

 

 

 

 

 

 

 

 

 

The voltage between CN1 3(+) and 2(GND)

 

5-time flash

PLASMA DEODORIZING

on the PLASMA POWER P.C board rises

 

 

 

above the normal voltage value (3 V).

 

 

 

 

 

NOTE1 : Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (10-4.).

NOTE2 : As soon as an abnormality is detected, PLASMA operation goes OFF, therefore measuring instrument which records the voltage wave is required in order to perform the above mentioned voltage measurement.

NOTE3 : When POWER lamp flashes 1-time or 2-time, Please perform PLASMA operation check (Refer to 10-2.3).

23

Image 23
Contents MSZ-FD25VA E1 MSZ-FD25VAS E1 MSZ-FD35VA E1 MSZ-FD35VAS E1 Page Technical Changes See control operation Part Names and FunctionsIndoor model SpecificationSpecifications and rating conditions of main electric parts MSZ-FD25VA MSZ-FD25VAS Noise Criteria CurvesUnit mm Outlines and DimensionsWiring Diagram Unit mm Refrigerant System DiagramJ1 J2 Service FunctionsTimer Short Mode P.C. Board Modification for Individual OperationOperation Remote ControllerAuto Restart Function OPERATE/STOP Microprocessor ControlHeat Operation Auto Change Over ··· Auto Mode OperationCool Operation DRY OperationHorizontal vane Auto Vane OperationOutdoor Unit MXZ series COOL/DRY Heat Vertical vaneSee Sensor Area SettingSee Control Operation Daytime Operation and operating range Plasma OperationProgram Timer Clean OperationTimer Operation EMERGENCY/TEST Operation Minute Time Delay OperationEmergency Operation switch E.O.SW Troubleshooting OFF Failure Mode Recall FunctionPlasma operation check Flow chart of Plasma operation failure mode recall functionPlasma operation failure mode table Indoor unit failure mode tableStart Instruction of TroubleshootingAn abnormality other than above mentioned is detected Troubleshooting Check TablePlasma Trouble Criterion of Main Parts Power lamp flashes 3-time Indoor fan does not operate Troubleshooting FlowYes Check of indoor P.C. board and indoor fan motor How to check miswiring and serial signal error Check of installation of the horizontal vane Electromagnetic noise enters into TV sets or radios SW P.C. Board Test Point Diagram and VoltageIndoor electronic control P.C. board CN1 Removing the panel Photo Disassembly InstructionsPower monitor receiver Removing the vertical vane motor unit Photo Removing the nozzle assembly PhotoRemoving the electrical box Photo Removing the indoor fan motor and the line flow fan Photo Removing the horizontal vane motor PhotoSpecifications subject to change without notice