Mitsubishi Electronics MSZ-FD25VAS, MSZ-FD35VAS Cool Operation, DRY Operation, Heat Operation

Page 12

9-1. COOL ( ) OPERATION

(1)Press OPERATE/STOP(ON/OFF) button.

POWER lamp of the indoor unit turns on with a beep tone.

(2)Select COOL mode with OPERATION SELECT button.

(3)Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 16 ~ 31 °C.

1. Coil frost prevention

The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil from frosting.

When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.

The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor heat exchanger rises.

2.Low outside temperature operation

When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.

9-2. DRY ( ) OPERATION

(1)Press OPERATE/STOP(ON/OFF) button.

POWER lamp of the indoor unit turns on with a beep tone.

(2)Select DRY mode with OPERATION SELECT button.

(3)The set temperature is determined from the initial room temperature.

1.Coil frost prevention

Coil frost prevention is as same as COOL mode. (9-1.1.)

2.Low outside temperature operation

Low outside temperature operation is as same as COOL mode. (9-1.2.)

9-3. HEAT ( ) OPERATION

(1)Press OPERATE/STOP(ON/OFF) button.

POWER lamp of the indoor unit turns on with a beep tone.

(2)Select HEAT mode with OPERATION SELECT button.

(3)Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 16 ~ 31 °C.

1.Cold air prevention control

When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem- perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.

2.High pressure protection

The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con- densing pressure from increasing excessively.

When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.

The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor heat exchanger falls.

3.Defrosting

Defrosting starts when the temperature of outdoor heat exchanger becomes too low.

The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts. This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.

9-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION

Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.

Mode selection

(1)Initial mode

When unit starts the operation with AUTO operation from off;

If the room temperature is higher than the set temperature, operation starts in COOL mode.

If the room temperature is equal to or lower than the set temperature, operation starts in HEAT mode.

(2)Mode change

COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 2 °C below the set temperature.

HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 2 °C above the set temperature.

NOTE 1

If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is operating

in

(AUTO), cannot change over to the other operating mode (COOL HEAT) and becomes a state of standby.

Refer to NOTE 2 “FOR MULTI SYSTEM AIR CONDITIONER”.

12

Image 12
Contents MSZ-FD25VA E1 MSZ-FD25VAS E1 MSZ-FD35VA E1 MSZ-FD35VAS E1 Page Technical Changes Part Names and Functions See control operationSpecification Specifications and rating conditions of main electric partsIndoor model Noise Criteria Curves MSZ-FD25VA MSZ-FD25VASOutlines and Dimensions Wiring DiagramUnit mm Refrigerant System Diagram Unit mmService Functions Timer Short ModeP.C. Board Modification for Individual Operation J1 J2Remote Controller Auto Restart FunctionOperation Microprocessor Control OPERATE/STOPAuto Change Over ··· Auto Mode Operation Cool OperationDRY Operation Heat OperationAuto Vane Operation Outdoor Unit MXZ seriesHorizontal vane Vertical vane COOL/DRY HeatArea Setting See Control OperationSee Sensor Daytime Plasma Operation Operation and operating rangeClean Operation Timer OperationProgram Timer Minute Time Delay Operation Emergency Operation switch E.O.SWEMERGENCY/TEST Operation Troubleshooting Failure Mode Recall Function OFFFlow chart of Plasma operation failure mode recall function Plasma operation checkIndoor unit failure mode table Plasma operation failure mode tableInstruction of Troubleshooting StartTroubleshooting Check Table An abnormality other than above mentioned is detectedPlasma Trouble Criterion of Main Parts Troubleshooting Flow Power lamp flashes 3-time Indoor fan does not operateYes Check of indoor P.C. board and indoor fan motor How to check miswiring and serial signal error Check of installation of the horizontal vane Electromagnetic noise enters into TV sets or radios Test Point Diagram and Voltage Indoor electronic control P.C. boardSW P.C. Board CN1 Disassembly Instructions Removing the panel PhotoPower monitor receiver Removing the nozzle assembly Photo Removing the electrical box PhotoRemoving the vertical vane motor unit Photo Removing the horizontal vane motor Photo Removing the indoor fan motor and the line flow fan PhotoSpecifications subject to change without notice