10-6. TROUBLESHOOTING FLOW
POWER lamp flashes 3-time.
Indoor fan does not operate.
A Check of indoor fan motor
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
Turn OFF the power supply.
Is there any foreign matter that interferes the rotation of the line flow fan?
Yes
Remove the foreign matter and adjust the line flow fan.
No
Pay careful attention to the high voltage on the fan motor connector CN211.
Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch.
Measure the supply voltage as follows within 12 seconds after EMERGENCY OPERATION switch is pressed.
If more than 12 seconds passes by, turn OFF the power supply and turn ON it again, then measure the voltage. w
1.Measure the voltage between CN211 1(+) and
wIf more than 12 seconds passes after EMERGENCY OPERATION switch is pressed, the voltage mentioned above 2 goes 0 VDC although the indoor electric control P.C. board is normal.
Is there 325 VDC between |
|
|
| |
CN211 1 (+) and 3 |
|
|
| |
the voltage between CN211 5(+) | Yes |
| ||
and |
|
| Replace the indoor fan motor. | |
| ||||
VDC within 12 seconds after |
|
|
| |
|
|
| ||
EMERGENCY OPERATION switch |
|
|
| |
is pressed? |
|
|
| |
| No |
|
|
|
|
|
|
| |
|
|
|
|
|
Indoor electronic control P.C. board
CN211
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats
Measure the voltage between CN211 6(+) and
| No | |
Is it unchanged holding | (Changed) | |
Replace the indoor electronic control P.C. board. | ||
0 or 15 VDC? | ||
|
Yes (Unchanged)
Replace the indoor fan motor.
28