Mitsubishi Electronics MSZ-FD35VAS, MSZ-FD25VA Check of indoor P.C. board and indoor fan motor

Page 30

The unit does not operate with the remote controller.

Also, POWER lamp does not light up by pressing EMERGENCY OPERATION switch.

C Check of indoor P.C. board and indoor fan motor

Turn OFF the power supply.

Remove indoor fan motor connector CN211, vane motor connector CN151 and the i-see Sensor motor connector CN110 from the indoor electronic control P.C. board and turn ON the power supply.

Does the unit operate with the remote controller?

Yes

Does POWER lamp light up by pressing EMERGENCY

 

OPERATION switch?

 

No

 

Measure the resistance of the i-see Sensor motor coil.

Refer to 10-5.

Measure the resistance between CN211 3 and 4 of the indoor fan motor connector.

Measure the resistance of the horizontal vane motor coil and the vertical vane motor coil. Refer to 10-5.

Replace the varistor(NR11) and fuse(F11).

Yes

Short/open circuit:

Replace the i-see Sensor motor

and the indoor electronic control P.C. board.

Short/open circuit:

Replace the indoor fan motor.

Short/open circuit:

Replace the horizontal vane motor, the vertical vane motor and the indoor electronic control P.C. board.

Turn OFF the power supply.

Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.

 

 

Are the varistor(NR11) burnt No

 

 

 

 

 

 

 

 

and the fuse(F11) blown?

 

 

 

 

 

 

 

 

 

Be sure to check both the fuse

 

 

 

 

 

 

 

 

and the varistor in any case.

 

 

 

 

 

 

 

 

Is the fuse(F11) blown only?

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Measure the resistance between

 

 

 

 

w1. The fan motor connector's1 lead wire is red, whereas 3 is black.

 

 

1(+) and 3(-) of the indoor fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

motor connector.

 

 

 

 

w2. Connect "+" of the tester to fan motor connector's1 lead

 

 

w1,w2

 

 

 

 

 

 

 

 

 

 

wire, and "-" to 3 lead wire, otherwise the resistance cannot be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

measured properly.

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

Is the resistance 1 M"

 

 

 

 

 

Replace the fuse (F11) and the indoor fan motor.

 

 

 

 

 

 

 

 

 

or more?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the fuse (F11).

Measure the resistance of cement resistor(R111) on the indoor electronic control P.C. board.

Is the resistance approx. 4 "?

Yes

No

Replace the indoor electronic control P.C. board and the indoor fan motor.

Replace the indoor electronic control P.C. board.

30

Image 30
Contents MSZ-FD25VA E1 MSZ-FD25VAS E1 MSZ-FD35VA E1 MSZ-FD35VAS E1 Page Technical Changes Part Names and Functions See control operationSpecification Specifications and rating conditions of main electric partsIndoor model Noise Criteria Curves MSZ-FD25VA MSZ-FD25VASOutlines and Dimensions Wiring DiagramUnit mm Refrigerant System Diagram Unit mmP.C. Board Modification for Individual Operation Service FunctionsTimer Short Mode J1 J2Remote Controller Auto Restart FunctionOperation Microprocessor Control OPERATE/STOPDRY Operation Auto Change Over ··· Auto Mode OperationCool Operation Heat OperationAuto Vane Operation Outdoor Unit MXZ seriesHorizontal vane Vertical vane COOL/DRY HeatArea Setting See Control OperationSee Sensor Daytime Plasma Operation Operation and operating rangeClean Operation Timer OperationProgram Timer Minute Time Delay Operation Emergency Operation switch E.O.SWEMERGENCY/TEST Operation Troubleshooting Failure Mode Recall Function OFFFlow chart of Plasma operation failure mode recall function Plasma operation checkIndoor unit failure mode table Plasma operation failure mode tableInstruction of Troubleshooting StartTroubleshooting Check Table An abnormality other than above mentioned is detectedPlasma Trouble Criterion of Main Parts Troubleshooting Flow Power lamp flashes 3-time Indoor fan does not operateYes Check of indoor P.C. board and indoor fan motor How to check miswiring and serial signal error Check of installation of the horizontal vane Electromagnetic noise enters into TV sets or radios Test Point Diagram and Voltage Indoor electronic control P.C. boardSW P.C. Board CN1 Disassembly Instructions Removing the panel PhotoPower monitor receiver Removing the nozzle assembly Photo Removing the electrical box PhotoRemoving the vertical vane motor unit Photo Removing the horizontal vane motor Photo Removing the indoor fan motor and the line flow fan PhotoSpecifications subject to change without notice