Mitsubishi Electronics MSZ-FD25VAS, MSZ-FD35VAS service manual Troubleshooting Check Table

Page 25

10-4. TROUBLESHOOTING CHECK TABLE

Before taking measures, make sure that the symptom reappears for accurate troubleshooting.

When the indoor unit has started operation and the following detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.

L AREA R

POWER CLEAN PLASMA

Lighted

 

 

Blinking

 

 

Not lighted

No.

Abnormal

Operation indicator lamp

 

point

 

 

 

POWER lamp flashes.

Symptom

Condition

Correspondence

 

Miswiring

0.5-second ON

 

 

1

or serial

 

 

signal

 

 

 

0.5-second OFF

 

Indoor coil

POWER lamp flashes.

2

thermistor

2-time flash

Room

 

 

 

 

temperature

 

 

thermistor

2.5-second OFF

 

 

POWER lamp flashes.

 

 

3-time flash

3

Indoor fan

 

motor

 

 

 

 

 

2.5-second OFF

 

Indoor

POWER lamp flashes.

 

4-time flash

4

control

 

 

system

 

 

 

2.5-second OFF

 

 

POWER lamp flashes.

5

Outdoor

5-time flash

power

 

system

2.5-second OFF

POWER lamp flashes. 6-time flash

Outdoor

6 thermistors

2.5-second OFF

 

Outdoor

POWER lamp flashes.

 

7-time flash

 

control

7

 

system

 

 

 

2.5-second OFF

POWER lamp flashes.

14-time flash

Other

8 abnormality

2.5-second OFF

Outdoor

9 control POWER lamp lights up. system

Indoor unit and outdoor unit do not operate.

Outdoor unit does not operate.

The serial signal from the outdoor unit is not received for 6 minutes.

The indoor coil or the room temperature thermistor is short or open circuit.

The rotational frequency feedback signal is not emitted during the indoor fan operation.

It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.

It consecutively occurs 3 times that the compressor stops for overcurrent protection or start-up failure protection within 1 minute after start-up.

The outdoor thermistors short or open circuit during the compressor operation.

It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.

An abnormality other than above mentioned is detected.

It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.

Refer to 10-6.D"How to check miswiring and serial signal error".

Refer to 10-7.the characteristics of indoor coil thermistor, and the room temperature thermistor.

Refer to 10-6.A"Check of indoor fan motor".

Replace the indoor electronic control P.C. board.

Refer to "How to check of inverter/compressor".

Refer to outdoor unit service manual.

Check the stop valve.

Refer to "Check of outdoor thermistor".

Refer to outdoor unit service manual.

Replace the inverter P.C. board or the outdoor electronic control P.C. board. Refer to outdoor unit service manual.

Check the stop valve.

Confirm the abnormality in detail using the failure mode recall function for outdoor unit.

Check the blinking pattern of the LED on the inverter P.C. board or the outdoor electronic

control P.C. board.

25

Image 25
Contents MSZ-FD25VA E1 MSZ-FD25VAS E1 MSZ-FD35VA E1 MSZ-FD35VAS E1 Page Technical Changes See control operation Part Names and FunctionsSpecifications and rating conditions of main electric parts SpecificationIndoor model MSZ-FD25VA MSZ-FD25VAS Noise Criteria CurvesWiring Diagram Outlines and DimensionsUnit mm Unit mm Refrigerant System DiagramTimer Short Mode Service FunctionsP.C. Board Modification for Individual Operation J1 J2Auto Restart Function Remote ControllerOperation OPERATE/STOP Microprocessor ControlCool Operation Auto Change Over ··· Auto Mode OperationDRY Operation Heat OperationOutdoor Unit MXZ series Auto Vane OperationHorizontal vane COOL/DRY Heat Vertical vaneSee Control Operation Area SettingSee Sensor Daytime Operation and operating range Plasma OperationTimer Operation Clean OperationProgram Timer Emergency Operation switch E.O.SW Minute Time Delay OperationEMERGENCY/TEST Operation Troubleshooting OFF Failure Mode Recall FunctionPlasma operation check Flow chart of Plasma operation failure mode recall functionPlasma operation failure mode table Indoor unit failure mode tableStart Instruction of TroubleshootingAn abnormality other than above mentioned is detected Troubleshooting Check TablePlasma Trouble Criterion of Main Parts Power lamp flashes 3-time Indoor fan does not operate Troubleshooting FlowYes Check of indoor P.C. board and indoor fan motor How to check miswiring and serial signal error Check of installation of the horizontal vane Electromagnetic noise enters into TV sets or radios Indoor electronic control P.C. board Test Point Diagram and VoltageSW P.C. Board CN1 Removing the panel Photo Disassembly InstructionsPower monitor receiver Removing the electrical box Photo Removing the nozzle assembly PhotoRemoving the vertical vane motor unit Photo Removing the indoor fan motor and the line flow fan Photo Removing the horizontal vane motor PhotoSpecifications subject to change without notice