DANGER
Adequate means must be provided to limit the movement of this appliance without depending on or transmitting stress to the electrical conduit. A restraint kit is provided with the fryer. If the restraint kit is missing contact your local Frymaster Factory Authorized Service Center (FASC) for part number
DANGER
Prior to movement, testing, maintenance and any repair on your Frymaster fryer, disconnect all electrical power from the fryer.
ELECTRICAL POWER SPECIFICATIONS
Three (3) Phase Requirements
|
|
|
| WIRE | MINIMUM SIZE | AMPS PER LEG | ||||
| kW | VOLTAGE | PHASE | SERVICE | AWG | mm2 | L1 |
| L2 | L3 |
14 | 208 | 3 | 3 | 6 | 16 | 39 |
| 39 | 39 | |
14 | 240 | 3 | 3 | 6 | 16 | 34 |
| 34 | 34 | |
14 | 480 | 3 | 3 | 8 | 10 | 17 |
| 17 | 17 | |
14 | 220/380 | 3 | 4 | 6 | 16 | 21 |
| 21 | 21 | |
14 | 240/415 | 3 | 4 | 6 | 16 | 20 |
| 20 | 21 | |
14 | 230/400 | 3 | 4 | 6 | 16 | 21 |
| 21 | 21 | |
| ALL | 208 | 3 | 3 | 6 | 16 | 39 |
| 39 | 39 |
| 240 | 3 | 3 | 6 | 16 | 34 |
| 34 | 34 | |
| EPRI 14kW |
| ||||||||
| 220/380 | 3 | 4 | 6 | 16 | 21 |
| 21 | 21 | |
| (SOLID STATE) |
| ||||||||
| 240/415 | 3 | 4 | 6 | 16 | 20 |
| 20 | 20 | |
|
|
| ||||||||
17 | 208 | 3 | 3 | 6 | 16 | 48 |
| 48 | 48 | |
17 | 240 | 3 | 3 | 6 | 16 | 41 |
| 41 | 41 | |
17 | 480 | 3 | 3 | 6 | 16 | 21 |
| 21 | 21 | |
17 | 220/380 | 3 | 4 | 6 | 16 | 26 |
| 26 | 26 | |
17 | 240/415 | 3 | 4 | 6 | 16 | 24 |
| 24 | 24 | |
17 | 230/400 | 3 | 4 | 6 | 16 | 25 |
| 25 | 25 | |
| ALL | 208 | 3 | 3 | 6 | 16 | 48 |
| 48 | 48 |
| 240 | 3 | 3 | 6 | 16 | 41 |
| 41 | 41 | |
| EPRI 17kW |
| ||||||||
| 220/380 | 3 | 4 | 6 | 16 | 26 |
| 26 | 26 | |
| (SOLID STATE) |
| ||||||||
| 240/415 | 3 | 4 | 6 | 16 | 24 |
| 24 | 24 | |
|
|
| ||||||||
22 | 208 | 3 | 3 | 4 | 25 | 61 |
| 61 | 61 | |
22 | 240 | 3 | 3 | 4 | 25 | 53 |
| 53 | 53 | |
22 | 480 | 3 | 3 | 6 | 16 | 27 |
| 27 | 27 | |
22 | 220/380 | 3 | 4 | 6 | 16 | 34 |
| 34 | 34 | |
22 | 240/415 | 3 | 4 | 6 | 16 | 31 |
| 31 | 31 | |
22 | 230/400 | 3 | 4 | 6 | 16 | 32 |
| 32 | 32 | |
|
|
|
|
|
|
|
|
| ||
|
|
| Single Phase Requirements |
|
|
|
|
| ||
|
|
|
| WIRE | MINIMUM SIZE |
| AMPS |
| ||
| kW | VOLTAGE | PHASE | SERVICE | AWG | mm2 |
|
| ||
|
|
|
|
| ||||||
| 14 | 208 | 1 | 2 | 3 | 34 |
| 68 |
| |
| 14 | 240 | 1 | 2 | 4 | 25 |
| 59 |
| |
| 14 | 480 | 1 | 2 | 8 | 10 |
| 30 |
|
ii