Hoshizaki SRH/3 Control Board with Harvest Pump Timer Operation, Harvest Pump Timer Startup

Page 18

"G" Control Board with Harvest Pump Timer Operation Flow Chart

 

 

 

 

 

 

1. 1-Minute

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cycle

 

 

 

 

 

 

2. Harvest Cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Freeze Cycle

 

 

 

4. Pump-Out Cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Steps

 

 

 

Fill Cycle

 

 

• WV time: 6 min. or the length of harvest minus 50

 

 

 

• Min. freeze time: 5 min.

 

 

• Factory set for every

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sec. (S4 dip switch 7), whichever is shorter. Do not

 

 

• Max. freeze time: freeze timer setting

10th cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

adjust S4 dip switch 7 out of the factory position.

 

 

 

(S4 dip switch 9 & 10)

 

 

(S4 dip switch 5 & 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Max. harvest time: 20 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Pump motor stops for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 sec., then reverses

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermistor

 

 

 

1 to 3-min. harvest timer in

 

 

 

 

 

 

 

5-min. timer

 

 

 

 

 

 

for 10/20 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(S4 dip switch 3 & 4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FS in control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in control

 

 

 

 

 

 

control (S4 dip switch 1 & 2)

 

 

 

 

 

 

in control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Harvest Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Startup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FS check

 

 

 

FS closed

 

 

 

 

 

PM energized

 

FS check

 

 

 

FS closed

 

 

 

FS opens or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WV de-energized

 

 

 

Comp continues

 

Comp continues

 

 

 

 

 

 

 

 

WV energized

 

 

Comp energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

freeze timer

 

 

 

 

 

 

 

 

 

 

Thermistor temperature

 

 

 

 

 

 

 

 

 

 

 

FMR continues

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FM continues

 

terminates

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FMR energized

reaches 48°F (9°C)

 

 

 

 

 

 

 

 

 

 

 

HGV energized

 

 

 

 

 

 

 

 

 

 

 

 

FS open

 

 

HGV energized

 

 

 

 

 

 

 

 

 

 

FMR continues

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3.9 kΩ or less).

 

 

 

 

 

 

 

 

 

 

 

 

 

PM de-energizes for 2 sec.,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WV energized

 

 

 

 

 

 

 

 

 

 

PM continues

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Harvest timer starts.

 

FS open

 

 

 

 

 

then reverses for 10/20 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLV energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HGV de-energized

 

 

 

FM de-energized

 

 

 

 

 

 

 

 

 

If FS is open, Comp stops and cycle returns to 1-Min. fill.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(FM continues on KM-1601SAH)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLV de-energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shutdown

 

 

 

1. Bin Full

 

 

 

 

 

 

 

 

 

 

 

 

2. Icemaker Off

 

 

3. Ice Level Lowered

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and Restart

 

 

 

 

 

Within 10 sec. after ice contacts BC bulb,

 

All components

 

 

 

 

 

 

No ice touching BC bulb.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

icemaker shuts down.

 

 

 

 

 

de-energized.

 

 

 

 

 

 

Icemaker starts at

 

 

 

 

 

 

BC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"1. 1-Minute Fill Cycle."

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To 1. 1-Minute Fill Cycle

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. "G" Control Board with Harvest Pump Timer Operation

Ice contacts BC bulb

Legend:

BC–bin control Comp–compressor FM–fan motor FMR–fan motor-remote FS–float switch HGV–hot gas valve LLV–liquid line valve PM–pump motor WV–inlet water valve

BC open

BC closed

All components

NOTE: Green "BC CLOSED" LED on continuously

de-energized

when the K4 jumper is in place.

 

Components Energized when the Control Switch is in the "WASH" Position

The "WASH" position on the control switch is used when cleaning and sanitizing the unit. When in the "WASH" position, power is supplied to the pump motor. With the cleaning valve closed, the cleaner and sanitizer flow over the outside of the evaporator plate assembly. With the cleaning valve open, the cleaner and sanitizer flow over both the outside and the inside of the evaporator plate assembly.

Note: Close the cleaning valve after cleaning and sanitizing are complete, otherwise the unit will not restart when the control switch is placed in the "ICE" position.

Image 18
Contents Superior Degree Reliability Hoshizaki AMERICA, INC Contents Page 100 Important Safety Information Additional Warning for Remote Models Air-Cooled Models SAH/3 Model Shown KM-1301SAH3Water-Cooled Models SWH/3/-M Model Shown KM-1301SWH3Remote Models SRH/3 Model Shown KM-1301SRH3KMH Construction Water-Cooled Models SWH/3Model Shown KMH-2000SWH3 Model Shown KMH-2000SRH3 Diagram Water TankWater Supply KM-2500SRH3 Water Sequence of Operation Flow Chart Shutdown Bin Full Icemaker Off Ice Level Lowered RestartTo 1 -Minute Fill Cycle Control Board with Harvest Pump Timer Operation Harvest Pump Timer StartupService Diagnosis G Control Board without Harvest Pump Timer Diagnosis Page Page OFF Shutdown E and G Control Board Control Board with Harvest Pump Timer Diagnosis Page Page Page Every cycle After 2nd freeze cycle Shutdown G Control Board Control Board Check Control Correct LED Board Lighting SequenceBin Control Check Float Switch Check and Cleaning Float Switch CheckFloat Switch Cleaning Thermistor Check Diagnostic Tables No Ice ProductionNo Ice Production Possible Cause Freeze-Up Freeze-Up Possible Cause Harvest CycleFreeze Cycle Low Ice ProductionFreeze-Up Possible Cause Low Ice Production Possible Cause Long Harvest CycleLow Ice Production Possible Cause Long Freeze Cycle III. Controls and Adjustments Control Board Layout Control BoardControl Board K2 Connector Bin Control Switch Open LED yellowPart Number Alarm Buzzer S5 Dip Switch K5 black ConnectorSequence Step LED Lights and Audible Alarm SafetiesNo. of Beeps Type of Alarm Every 3 sec Energized Time LEDs are On Components Min Max AvgControl Board Settings and Adjustments Default Dip Switch SettingsS4 Dip Switch G Control Boards S5 Dip SwitchHarvest Timer S4 dip switch 1 Pump-Out Timer S4 dip switch 3 S4 Dip Switch Setting Time sec Inlet WaterValve S4 Dip Switch Setting Pump-Out Frequency Control S4 dip switch 5Control Board 1st Pump-Out S4 Dip Switch Setting Frequency Control BoardControl Board S4 Dip Switch Setting Pump Motor Time sec Factory Use S4 dip switchFreeze Timer S4 dip switch 9 S4 Dip Switch Setting Time MinControl Switch Float Switch Selector S5 dip switch 1 G Control BoardRefill Counter S5 dip switch 2 through 5 G Control Board IV. Refrigeration Circuit and Component Service Information Refrigeration Circuit Service InformationRefrigerant Recovery Brazing Evacuation and Recharge R-404APage Component Service Information ComponentWater Regulating Valve Adjustment water-cooled models Maintenance Maintenance ScheduleFrequency Area Task VI. Preparing the Icemaker for Periods of Non-Use Remove the water from the icemaker water supply lineDrain the water tank Page VII. Disposal Specification and Performance Data VIII. Technical InformationKM-1301SAH KM-1301SAH3 KM-1301SWH Electric & Water Consumption237 KM-1301SWH31770 240KM-1301SRH with URC-14F 192 KM-1301SRH3 with URC-14F463 214KM-1400SWH-M 1720 KM-1400SWH3-M1700 2302450 KM-1601SAH1462 228KM-1601SAH3 14562610 KM-1601SWH 241257 KM-1601SWH3 12.8 a 5 Min. Freeze AT 104F/WT 80F 785 375213 352 KM-1601SRH with URC-22F Auxiliary Codes S-2 and Later755 207504 202247 781 KM-1601SRH3 with URC-22F Auxiliary Codes S-2 and Later KM-1900SAH 2480KM-1900SAH3 18591850 KM-1900SWH1876 16502137 KM-1900SWH31814 239KM-1900SRH with URC-21F 2500 KM-1900SRH with URC-22F1857 3282680 KM-1900SRH3 with URC-21F1965 332KM-1900SRH3 with URC-22F KM-2100SWH3 20961794 382 KM-2100SRH3 with URC-22F3210 270KM-2500SWH3 24082174 KM-2500SRH3 with URC-23F 37802410 KMH-2000SWH1821 1464KMH-2000SWH3 2570 KMH-2000SRH with URC-22F1944 307KMH-2000SRH3 with URC-22F Wiring Diagrams KM-1601SWH, KM-1601SRH, KM-1900SH, KMH-2000SHKM-2500SH3, KMH-2000SH3 Diagrams with Harvest Pump Timer Relays G Control Board Auxiliary CodeKM-1301SH3 Auxiliary Code T-0, U-0 KM-1301SH Auxiliary Code U-1 and Later and KM-1601SAH KM-1301SH3 Auxiliary Code U-1 and Later and KM-1601SAH3 KM-1400SWH-M KM-1400SWH3-M