h)Freeze Termination Diagnosis: After 5 min. in freeze, disconnect CB K5 FS connector. 15 sec. later appliance should switch out of the freeze cycle (15 second delay after FS opens before terminating the freeze cycle). If appliance remains in freeze longer than 15 sec. after FS removed, replace CB. If appliance switches with FS removed but would previously not switch out of freeze with FS connected (long freeze - 3 beep alarm), see "II.E. Float Switch Check and Cleaning."
Note: Normal freeze cycle will last 20 to 40 min. depending on model and conditions. Cycle times and pressures should follow performance data provided in this manual. See "VIII.A. Specification and Performance Data."
i)Short Freeze Cycle Diagnosis: Confirm water tank fills and overflows during 1 min. fill and harvest cycles. If not, check water supply filters,
7)
"E" & "G" Control Board Settings | 1st | ||||
|
|
|
|
| |
S4 Dip Switch Setting | "E" Control Board | "G" Control Board | |||
No. 5 | No. 6 | Frequency | |||
|
| ||||
|
|
|
|
| |
OFF | OFF | Every cycle | After 1st freeze cycle | After 2nd freeze cycle | |
|
|
|
|
| |
ON | OFF | Every 2 cycles |
| After 3rd freeze cycle | |
|
|
|
|
| |
OFF | ON | Every 5 cycles |
| After 6th freeze cycle | |
ON | ON | Every 10 cycles |
| After 11th freeze cycle | |
|
|
|
|
|
Comp and FMR continue, HGV energizes. If S4 dip switch 3 & 4 are set to 3 off and
4 on, LED 4 turns on and WV energizes. FM and LLV de‑energize. PM stops for 2 sec., then reverses for 10/20 sec. depending on pump‑out timer (S4 dip switch 3 & 4) setting. When the pump‑out timer terminates, pump‑out is complete. The
Confirm FM and LLV
23