Electrical System | Section 6 |
|
|
2.Disconnect bin level probe from control board and check continuity (ohms) from the female connector to the bin level probe.
| CHECK FOR CONTINUITY |
| CONNECTOR TO GROUND. |
|
|
Continuity | Cause |
|
|
No | Replace bin level probe. |
|
|
Yes | Go to step 3. |
|
|
3.Remove bin level probe from ice chute and clean with Manitowoc Ice Machine Cleaner and Sanitizer. Rinse well with fresh water, reinstall and monitor the Bin light.
Control Board | Cause | |
Bin Level Light | ||
| ||
|
| |
Off | Bin level probe | |
needed cleaning. | ||
| ||
|
| |
Flashes | Go to step 4. | |
|
|
4.Disconnect bin level probe wire from the control board and place a jumper from the bin level terminal to ground.
Control Board | Cause | |
Bin Level Light | ||
| ||
|
| |
On | Replace bin level probe. | |
|
| |
| Reconfirm control board is not | |
Flashes | in an | |
steps 1 – 4, then replace | ||
| ||
| control board. | |
|
|
Bin Level Probe Closed or Shorted
The ice machine will not start and the Bin Level light is energized continuously.
1.Verify ice is not in contact with bin level probe.
2.Disconnect bin level probe wire from the control board.
| DISCONNECT BIN LEVEL PROBE | |
| FROM CONTROL BOARD. | |
|
| |
Control Board | Cause | |
Bin Level Light | ||
| ||
|
| |
Off | Clean bin level probe. | |
|
| |
On | Replace control board. | |
|
|
| Revised 8/2003 | Part No. |
|
|