Manitowoc Ice QF2300 Section, Troubleshooting, Analyzing Why SafeGuards May Stop the Ice Machine

Page 55
Troubleshooting

Section 5

Troubleshooting

 

 

Analyzing Why SafeGuards May Stop the Ice Machine

According to the refrigeration industry, a high percentage of compressor failure are the result of external causes. These can include flooding or starving expansion valves, dirty condensers, water loss to the ice machine, etc. SafeGuards protect the ice machine (primarily the compressor) from external failures by stopping ice machine operation before major component damage occurs.

Refrigeration and electrical component failures may also trip a safeguard. Eliminate all electrical components and external causes first. If it appears that the refrigeration system is causing the problem, use the charts, checklists, and other references to determine the cause.

NOTE: The following checklists are designed to assist the service technician in analysis. However, because there are many possible external problems, do not limit your diagnosis to only the items listed.

SAFEGUARD MODES

No Water

During the Freeze cycle if the water level probe opens or remains open for more than 90 continuous seconds, the ice machine will de-energize the compressor and gear motor, continuously flash the water level light and initiate a 60 minute Standby Mode.

During the Standby Mode the water level light will continually flash to indicate a Standby Mode.

After the 60 -minute Standby Mode, the ice machine will de-energize the water level light and initiate a start-up sequence.

WATER CONTACTS THE WATER LEVEL PROBE:

The ice machine continues to make ice.

WATER LEVEL PROBE OPENS OR REMAINS OPEN FOR MORE THAN 90 CONTINUOUS SECONDS:

The ice machine will start another 60-minute Standby Mode.

The ice machine repeats the above sequence until:

Water contacts the water level probe

or

The toggle switch is moved to the OFF position.

INDICATOR LIGHT

Before 48 hours have elapsed:

After a Standby Mode has been initiated the water level light will flash anytime the toggle switch is placed in the OFF position.

After 48 hours have elapsed:

The SafeGuard will be automatically erased from memory and the water level will not flash.

No Water Checklist

Possible Problem List

Corrective Action List

 

 

No water

Restore water supply.

 

 

Quick disconnect removed from water float valve

Restore water supply.

 

 

Water float valve screen blocked

Clean screen.

 

 

Water float valve solenoid coil defective

Replace coil (see Water float valve diagnostics).

 

 

Water float valve improperly adjusted

Adjust valve (see Water level check).

 

 

Dump valve leaking

Repair or replace dump valve.

 

 

Water level probes disconnected or removed

Connect and correctly position probes.

 

 

Part No. 80-1214-3

Revised 8/2003

5-3

 

 

Image 55
Contents Flake / Chiplet Model Ice Machines Flake Models QF0400/QF0800 QF2200/QF2300Chiplet Models QC0700 Service ManualPERSONAL INJURY POTENTIAL Safety NoticesProcedural Notices Read These Before ProceedingManitowoc Cleaner and Sanitizer Table of ContentsSection Installation Instructions AccessoriesPreventative Maintenance Cleaning Procedure Table of Contents continuedSection Maintenance Exterior CleaningSafeGuard Indicator Lights Table of Contents continued SectionSection Troubleshooting Reset Procedure6-46 ICE/OFF/CLEAN Toggle SwitchCompressor Electrical Diagnostics Section Refrigeration SystemTable of Contents continued Revised 8/2003 MANITOWOC CLEANER AND SANITIZER Section General InformationHow to Read a Model Number AccessoriesModel/Serial Number Location General InformationSection Model/Serial Number LocationPARTS Owner Warranty Registration CardWarranty Coverage GENERALTHIS PAGE INTENTIONALLY LEFT BLANK QC700/QF800 AIR COOLED ICE MACHINE Section Installation InstructionsIce Machine Dimensions QF400 AIR COOLED ICE MACHINEInstallation Instructions Location of Remote Condensing Unit Location of Ice MachineIce Machine Head Section Clearance Requirements Ice Machine Heat of RejectionAir Baffle Leveling the Ice Storage BinCondenser Air Baffle QC700/QF800 Air-CooledIce Machines OnlyMINIMUM CIRCUIT AMPACITY Electrical ServiceVOLTAGE FUSE/CIRCUIT BREAKERRemote Condensing Unit Electrical RequirementsFor United Kingdom Only Ice Machine Head Section230/1/50 QF2200 ICE MACHINE HEAD SECTION 115/60/1QF2300 ICE MACHINE HEAD SECTION 115/60/1RFC2385 REMOTE CONDENSING UNIT 208-230/1/60 Remote Electrical Wiring ConnectionsRFC2085 REMOTE CONDENSING UNIT 208-230/1/60 POTABLE WATER INLET LINES Ice Machine Head Section Water Supply and DrainsCooling Tower Applications Water-CooledModels POTABLE WATER SUPPLY2-10 Typical Water Supply Drain InstallationWATER SUPPLY AND DRAIN LINE SIZING/CONNECTIONS USAGE WITH NON-MANITOWOC CONDENSING UNITS Refrigeration System Installation2-11 QF2200/RFC2085 AND QF2300/RFC2385 ONLYUnit Locations Are Within Guidelines Refrigeration Line Set Installation2-12 Step 1 Verify Ice Machine and Remote CondensingManitowoc S-TrapKit Service Loop2-13 C. SUCTION LINE OIL TRAPS2-14 Step 4 Connecting the line set2-15 Step 7 Leak Check The Refrigeration System Open Receiver Service Valve2-16 Torque Value’sSuction Shut Off Valve Insulation 2-172-18 QF400 Section Ice Machine OperationComponent Identification ICE MACHINE HEAD SECTION QC700/QF800RFC2385 Remote Condensing Unit Ice Machine OperationSection QF2300GENERAL Operational ChecksWATER LEVEL CHECK EXTERIOR CLEANING Interior Cleaning and SanitizingCleaning/Sanitizing Procedure Heavily Scaled Cleaning ProcedureStraighten Bent Condenser Fins CLEANING THE CONDENSERAir-CooledCondenser Self-Contained Air-CooledFilterMANITOWOC’S CLEANING TECHNOLOGY PREVENTATIVE MAINTENANCE CLEANING PROCEDURE QF400 CLEANING/SANITIZING PROCEDURE QC700/QF800/QF2300 CLEANING/SANITIZING PROCEDURE QF400 part number 3-10only 3-11 REMOVAL OF PARTS FOR CLEANING/SANITIZINGWater Reservoir Cover Removal 3-12Water Level Probe Removal QC700/QF800QF2300 Shown 3-13Float Valve Removal Water Reservoir Removal 3-14Ice Diverter Removal Ice Chute Removal 3-15Bin Door Removal 3-16Cabinet Removal 3-17 Dump Valve DisassemblyWater Dump Valve Pry Open the Water Regulating Valve Removal from Service/Winterization3-18 WATER COOLED CONDENSING UNITINITIAL START-UP1A. Flush Section Ice Machine Sequence of OperationQF400/QC700/QF800 PRIOR TO START-UPRemote Condensing Unit 3. Automatic Shut-Off Ice Machine Sequence of OperationQF2200 Remote Condensing Unit 2. FreezeQF2300 THIS PAGE INTENTIONALLY LEFT BLANK Checklist Section TroubleshootingSAFEGUARD INDICATOR LIGHTS TroubleshootingSafeguard Feature RESET PROCEDURENo Water Checklist TroubleshootingAnalyzing Why SafeGuards May Stop the Ice Machine SAFEGUARD MODES No WaterGear Motor Speed Gear Motor Speed ChecklistTemperature is Too High or Low QF400/QC700/QF800 Temperature Sensor Checklist QF400/QC700/QF800Temperature is Too High or Low QF2200 Only Temperature Sensor Checklist QF2200Gear Box Removal QF2200/QF2300 Evaporator Removal 5-10 Energized Parts Charts Section Electrical SystemElectrical System QF2300 Wiring Diagram Sequence of OperationL1 1B. WATER FILL Freeze Cycle Automatic Shut-Off 3B. DRAIN EVAPORATOR Electrical System 6-10 Wiring Diagram Sequence of L1 Operation6-11 6-12 6-13 6-14 6-15 6-16 RFC2085 Initial Start-Up Remote Condensing Unit 6-17Initial Start-Up 6-18RFC2085 Initial Start-Up 6-196-20 RFC2085 Freeze Cycle 6-21QF2200 Automatic Shut-Off 6-22RFC2085 Automatic Shut-Off 6-236-24 8 Minute Lockout 6-256-26 Wiring Diagram Sequence of OperationRFC2385 6-276-28 6-29 6-30 6-31 6-32 6-33 QF2300 Automatic Shut-Off 6-346-35 WIRING DIAGRAM LEGEND Wiring Diagrams6-36 ICE MACHINE HEAD SECTION QF400 6-37115V/60Hz/1Ph - 230V/50Hz/1Ph QC700/QF800 115V/60Hz/1Ph - 230V/50Hz/1Ph 6-38COMPRESSOR SECTION QC700/QF800 6-39115/60/1 - 230/50/1 ICE MACHINE HEAD SECTION QF2200 6-40RFC2085 230V/60HZ/1PH - 230/50/1 6-41RFC2085 208-230V/60HZ/3PH 6-426-43 Diagram Shown During Freeze CycleICE MACHINE HEAD SECTION RFC2385 230V/60HZ/1PH - 230/50/1 6-44RFC2385 208-230V/60HZ/3PH 6-456-46 Control BoardCheck Procedure Component Specifications and DiagnosticsICE/OFF/CLEAN TOGGLE SWITCH Function Specifications6-48 MOTOR SPEED SENSOR Function 6-49Failure Modes WATER LEVEL PROBES Function 6-506-51 TEMPERATURE SENSOR Function 6-52TEMPERATURE/RESISTANCE CHART CONTROL BOARD RELAYS Function 6-53MAIN FUSE Function WATER FLOAT VALVE Function 6-54WATER LEVEL CHECK HIGH PRESSURE CONTROL HPCO Function 6-55Function FAN CYCLE CONTROL Function 6-56Check Motor Windings to Ground COMPRESSOR ELECTRICAL DIAGNOSTICS6-57 Check Resistance Ohm ValuesDiagnosing Start Components 6-58Relay Operation Check QF400/QC700/QF800/QF2200/QF2300 Diagnosing An Ice Machine That Will Not RunDiagnosing A Condensing Unit That Will Not Run 6-596-60 Tubing Schematic Section Refrigeration SystemSV3082 QF2200/RFC2085 Refrigeration SystemCondensing Unit QF2300/RFC2385 Refrigeration System Diagnostics ICE PRODUCTION/QUALITY CHECK Quality Check BEFORE BEGINNING SERVICEIce Production Check WATER SYSTEM CHECKLIST INSTALLATION/VISUAL INSPECTION CHECKLISTSAFEGUARDS Discharge Pressure High Checklist ProcedureDischarge Pressure Low Checklist Suction Pressure Low Checklist Suction Pressure High ChecklistANALYZING SUCTION PRESSURE WATER REGULATING VALVE WATER-COOLEDMODELS ONLY EQUALIZATION VALVE QF2300 GeneralNormal Operation AnalysisAir-CooledCondensing Units 7-10HEADMASTER CONTROL VALVE Function FREEZE CYCLE OPERATION Air-CooledIce MachinesOperating Pressures 7-11QF400 SELF-CONTAINEDAIR COOLED 24 Hour Ice ProductionQC700 SELF-CONTAINEDAIR COOLED 7-12QC700 SELF-CONTAINEDWATER COOLED QF800 SELF-CONTAINEDAIR COOLED 7-13QF800 SELF-CONTAINEDWATER COOLED QF2200/RFC2085 REMOTE AIR COOLED 7-14QF2300/RFC2385 REMOTE AIR COOLED Recovery/Evacuation Connections Refrigerant Recovery/Evacuation and RechargingREFRIGERANT RECOVERY/EVACUATION Normal Self-ContainedModel Procedures7-16 Recovery/Evacuation QF2200/QF2300Connections 7-17 Self-ContainedModel Charging ProceduresCharging Connections 7-18 Remote Charging Procedures QF2200/QF23007-19 SYSTEM CONTAMINATION CLEAN-UP GeneralDetermining Severity Of Contamination Severe System Contamination Cleanup Procedure Mild System Contamination Cleanup Procedure7-20 7-21 7-22 Using Pinch-OffToolSV1406 Remote Models SUCTION CLEAN-UPFILTER/DRIER QF400/QC700/QF8007-23 FILTER-DRIERS Liquid Line Filter DrierRecycle REFRIGERANT DEFINITIONS RecoverNew Product Specifications 7-24Revised 8/2003 Attend A Manitowoc Factory Service School 1.New Refrigerant 3.Recovered or Recycled Refrigerant7-25 REFRIGERANT RE-USEPOLICY7-26