Electrical connection
All electrical work should be by a licensed electrician, in strict accordance with national and local safety regulations and standards.
^Note to installer:
Please leave these instructions with the consumer.
^Power supply:
Please check the data plate for verification of:
240 VAC, 60 Hz, 15A, L1, L2, Ground.
Caution:
Disconnect the main power supply before servicing. To reduce the risk of electric shock, make sure that the appliance is properly grounded after installation.
WARNING : THIS APPLIANCE MUST BE GROUNDED
For USA only
The appliance is provided with 3 terminal leads, 1 black wire (L1), 1 red wire (L 2) and 1 green wire (GND) which have to be connected to a dedicated junction box. Connect the black wire to L1, the red wire to L2 and the green wire to GND.
ALSO SEE THE WIRING DIAGRAM PROVIDED WITH THE APPLIANCE.
For CDN only
The appliance is provided with 3 terminal leads, 1 black wire (L1), 1 red wire (L 2) and 1 green wire (GND) which have to be connected to a dedicated junction box. Connect the black wire to L1, the red wire to L2 and the green wire to GND.
All hot wires (black and red) have to be fused individually before connecting them to the main power supply leads.
Use 15 Amp fuses or circuit breakers for appliances rated 240 VAC.
ALSO SEE THE WIRING DIAGRAM PROVIDED WITH THE APPLIANCE.