U-Line 2275DWRWOL, 2275DWRWS Forced Defrost, ICE Thickness Adjust, Temporary SHUTDOWN/OFFICE Mode

Page 47

Section 3 - Service and Repair

FORCED DEFROST

This will allow the unit to defrost quickly. For R and WC units, this is just an off cycle. For units with hot gas defrost the unit will enter a hot gas defrost per the specification. Hold the LIGHT key and press ON/OFF three times. The unit will beep once when entering this mode. To exit this mode either do the same key combination or turn the unit off via the display. Not available on CLR2160.

ICE THICKNESS ADJUST

This will allow addition or subtraction of up to five minutes from the ice-making cycle. To enter this mode hold the up arrow and press the down arrow three times. The unit will beep once and display the current ice thickness. To adjust up or down use the arrows. Press LIGHT key when completed. Please refer to the ice thickness section of the manual to view proper cube sizes and recommendations.

Only available on CLR2160 and CLRCO2175.

TEMPORARY SHUTDOWN/OFFICE MODE

In some cases it may be requested for the unit to be shut down for short periods during meetings for example. To do this hold the down arrow and press the up arrow three times. The unit will beep once and show OFF on the display. This mode can be canceled by removing power from the unit or turning it on via the display. The mode will automatically be changed back to ON after three hours.

Only available on CLR2160 and CLRCO2175.

RELAY STATUS

To see which relays are operating, hold the down arrow and hit ON/ OFF three times. The unit will scroll through all relays and whether they are on or off. See specific unit section for explanation.

MODEL NUMBER CHANGE

Only the main circuit board requires model number selection. The display board is universal and will automatically adapt to the unit it is plugged into. The model number can be changed with the board installed or uninstalled from the unit. To program uninstalled you will need a display board and a power supply. For the power supply hook a neutral wire up to pin 10 and a 120V wire to pin 8 of the circuit board.

1.Plug in unit.

2.The display may show a SP or --, either is OK.

3.Install a jumper on J3. The jumper can be obtained from U-Line P/ N 68080.

4.Hold down WARMER, COLDER and LIGHT buttons until display shows model number and main board beeps.

5.Use WARMER/COLDER to select new model number.

61-2175R 120V

75-2175R 220V

62-2175WC 120V

76-2175WC 220V

63-2175BEV 120V

77-2175BEV 220V

64-CO2175F 120V

78-CO2175 220V

65-2175RF 120V

79-2175RF 220V

66-CO2175DWR 120V

80-CO2175DWR 220V

67-CLR2160 120V

81-CLR2160 220V

68-CLRCO2175 120V

82-CLRCO2175 220V

70-2175DWR 120V

85-2275DWRWS 120V

71-2115R 120V

86-2275DWRWS 220V

72-2115WC 120V

87-2275ZWC 120V

73-2115R 220V

88-2275ZWC 220V

74-2115WC 220V

 

6.Press and release LIGHT key.

7.Wait for display to stop flashing.

8.Remove jumper from board.

9.Unplug unit and wait five seconds.

10.Plug unit back in.

Échelon Service Menu

Enter service menu by holding up arrow and pressing LIGHT three times. Select option 1 to 27 with the up and down arrows. To enter the option, press the LIGHT key. If changing a setting, you must press the LIGHT key again to retain the changed setting.

When entering service mode all other modes are cancelled and the unit will stop operating. When exiting service mode the unit will begin to operate normally, however the four-minute compressor off cycle still applies.

1.Light all LED segments.

This will illuminate all the LEDs on the board to ensure they work properly.

2.Thermistor 1 status—Temperature, E1, or E2.

This will show the pure thermistor reading with no offsets taken into account. When placed in ice water this thermistor should read 32°F in this menu option. Not available on CLR2160.

3.Error log

A list of the errors in the order they occurred will scroll once on the display. Repeat if desired. Once viewed perform option 12 to clear the errors from memory.

4.Defrost information

Displays the number of defrosts that have occurred in the past 24 hours.

5.Compressor runtime based on last cycle

This will show the number of minutes the compressor has run in the prior cycle (or current cycle if the compressor was running when service mode was entered).

6.Defrost length adjustment—up to 99 minutes

The length of the defrost can be adjusted up to 99 minutes long. The other defrost parameters still apply. Lengthening a defrost may cause higher than normal temperatures in the refrigerator section. Not available on CLR2160.

7.Light switch 1 status—0 or 1

This will tell if the light should turn off with the door switch or not. At the “0” reading the light should be off with the door closed and on with the door open. At the “1” reading the light stays on always.

8.Display toggle status—0 or 1

This will tell if the display should turn off with the door switch or not. At the “0” reading the display should be off with the door closed and on with the door open. At the “1” reading the display stays on always.

9.Restore factory defaults

This will restore the default set-point, defrost and offset values.

10.Adjust thermistor 1 offset—10 to +10F

3-32

Image 47 Contents
2010 Origins Models 1115R Potential Problems with HFC-134AIntroduction Échelon Models 2115RTable of Contents Wiring Diagrams Safety Alert Definitions Safety PrecautionsLine Corporation Limited Warranty Leaders In Quality Undercounter Refrigeration Product Liability PolicyProof of Purchase Warranty Claims ProcedureSerial Number Format How to Order Replacement Parts Parts ListingCustomer Call Guide CLR2160 Model Only Type 2 White Refrigeration System Diagnosis GuideType 1 Black Troubleshooting Troubleshooting Troubleshooting General Error CodesService OperationCLR2160 Ice not sized to customer satisfaction No iceToo much ice Too little iceCLRCO2175 CLRCO2175 Mode 1 Ice Making and Refrigeration ULIN0329A CLRCO2175 Mode 3 Refrigeration and No Ice Making CLRCO2175 Mode 4 Ice harvest No Refrigeration Possible CLRCO2175 Mode 5 Off Service and Repair CLRCO2175 Mode 7 Cleaning No Refrigeration Possible Error code is repeated, the thermistor is Ice maker not operating-no water flowing over mold Display is showing something other than SP 38, ER or CLRefrigerator not cooling but ice maker working 2115R/2175WC/2175BEV/2275DWRR/2175DWRR Thermistor Outage Dwrws & 2275ZWC Review the Following Notes for General InformationThermistor Outage Except Dwrws & 2275ZWC Refrigerator too warm Excessive Frost on evaporatorDisplay is showing something other than SP 38 or ER Line Frost Free Refrigeration System Service and Repair CO2175F/2175RF/CO2175DWRDefrost Reed SwitchThermistors Water fill cycle Storage modeFreeze cycle Harvest cycleCO2175F Harvest-1 Cycle First 30 Seconds CO2175F Water Fill Cycle CO2175F Freeze Cycle CO2175/2275DWR Harvest-2 Cycle After 30 Seconds CO2175/2275DWR Water Fill Cycle Not making ice This can be caused by poor incoming water quality Service and Repair 1175R/1115R 1175WC/1115WC 1175BEV/ADA24R It is most likely a refrigeration system issue Error CodeCabinet Light Operating ENVIRONMENTAL/ Climate Control RequirementsÉchelon Electronic Control ON/OFF2275ZWCOL Adjusting the SET-POINT 2275DWRWS onlyAdjusting the SET-POINT 2275ZWC/2275ZWCOL only Service Mode Viewing Actual Temperature 2275DWRWS onlyViewing Actual Temperature 2275ZWC/2275ZWCOL only Showroom ModeRelay Status ICE Thickness AdjustTemporary SHUTDOWN/OFFICE Mode Forced DefrostError Codes E2 Thermistor 1 is shorted. Not available on CLR2160 Model Thermistor Door Switch Échelon Service Quick Reference Card Échelon Electronic Control Quick Reference Guide Origins Electronic Control Viewing Actual TemperatureOrigins Model Selection Origins Service MenuOrigins Electronic Control Quick Reference Guide Refrigeration System Diagnosis Guide Defrost Information ALL ModelsCOMPRESSOR/COIL Specifications SpecificationsCLRCO2175 2115R/2175WC/2115WC/2175BEV 2175WRR/2175DWRWS Refrigerator Coil OHMS-2175DWRWS/2275ZWCCO2175F/2175RF/CO2175DWR ICE Maker Limit Switch1175R/1115R 1175WC/1115WC 1175BEV/ADA24R Échelon Full Overlay Adjustments and RepairNotch must face center of door Adjusting Door AlignmentChecking Door Alignment Door Alignment Origins ModelsDrawer Removal Adjusting Drawer AlignmentChecking Drawer Alignment FRONT-TO-BACK Adjustment Minor AdjustmentSevere Adjustment SIDE-TO-SIDE AdjustmentTOP-TO-BOTTOM and LEFT-TO-RIGHT Adjustment RE-INSTALLATION of Drawer Interval AS Required Ice Cube Thickness AdjustmentReplacing Evaporator FAN Motor CO2175F/2175RF Accessing Evaporator or Drain CO2175F/2175RFReplacing Evaporator FAN Motor CO2175DWR To access evaporator or drainReplacing ICE Maker Replacing Mold and Heater CO2175F/CO2175DWR Gravity Drain FACTORY-INSTALLED Drain PumpDrain Connection Remove 12 screws and back panel CLR Drain KIT Available for Purchase LOCALLY-INSTALLED Drain PumpTools Required Materials RequiredULINS0168A Loose. For the disposal or Waterhookup Water Supply ConnectionANTI-TIP KIT CLR2160 1 Description CLR2160 2 41993 CLRCO2175 1 Screw, handle included with handle assembly CLRCO2175 2 Compression nut included with water line CLRCO2175 3 Armaflex, 1-5/8 ID included with 2276-CLRCO-S CLRCO2175 4 BF4CO5-S 2175R 1 Screw, handle included with handle assembly 2175R 2 Not 2950-01 Wire connector, 12-pin 2115R 1 Screw, handle included with handle assembly 2115R 2 41993 2175WC/2175WCOL/2175WCOL2 1 2175WC/2175WCOL/2175WCOL2 1 2175WC/2175WCOL /2175WCOL22 Black Stainless Steel 2115WC/2115WCOL/2115WCOL2 1OF2 2115WC/2115WCOL/2115WCOL2 1 2115WC/2115WCOL/2115WCOL2 2 41993 2175BEV/2175BEVOL/2175BEVOL2 1 Overlay Door Stainless Steel 2175BEV/2175BEVOL/2175BEVOL2 2 Black Stainless Steel 2175DWRR/2275DWRR 1 2175DWR-TOP-BLK 2175DWRR/2275DWRR 2 Not 14159-05 Commerical handle SS accesory only 2275DWRWS/2275DWRWOL 1 Not 80-50002-00 Overlay Bracket Assembly 2275DWRWS/2275DWRWOL 2 Item Part No. Description CO2175F 1 Description CO2175F 2 0f CO2175F 2 CO2175F 3 Not 35014 Tape, drain pan heater CO2175F 4 Mold and Heater Assembly 2175RF 1 Black White Stainless Steel 2175RF 2 Solenoid only included with 73002-FFS 2175RF 3 Evaporator Assembly includes heat exchanger CO2175DWR/CO2275DWR 1 Process tube included with 73002-FFS CO2175DWR/CO2275DWR 2 Drawer Front Assembly, top CO2175DWR/CO2275DWR 3 Evaporator Assembly includes heat exchanger CO2275DWR 4 Mold and Heater Assembly 2275ZWC/2275ZWCOL 1 Overlay Stainless Steel 2275ZWC/2275ZWCOL 2 Process tube included with compressor 2275ZWC/2275ZWCOL 3 26100 Display housing 41992 1175R 1 Towel Bar Handle Assembly SS accessory only 1175R 2 Thermistor, quick connect white 1115R 1 Black Stainless Steel 1115R 2 31213 Spacer 1175WC 1 26147 Door Spacer, for Field Reversable Doors 1175WC 2 26058 1115WC 1 Pivot screw, bottom included with hinge assembly 1115WC 2 26059 1175BEV 1 26147 Door Spacer, for Field Reversable Doors 1175BEV 2 26058 ADA24R 1 0F Description ADA24R 1 0FADA24R 2 0F Description Black Stainless Steel This page intentionally left blank CLRCO2175 2115R, 2115WC, 2175R, 2175WC, 2175BEV 2175RF CO2175F ADA24R This page intentionally left blank About U-LINE Product Information