Broan HEPA 1000, HEPA 4000, HEPA 3000 Hepa 2000, HF2.0, Hepa 3000, HF 3.0 and Hepa 4000 Units only

Page 23

4.INSTALL THE UNIT (CONT’D)

4.6INSTALLING INSULATED FLEXIBLE DUCTS

(HEPA 2000, HF2.0, HEPA 3000, HF 3.0 AND HEPA 4000 UNITS ONLY)

CAUTION

Make sure the vapor barrier on the insulated ducts does not tear during installation.

Use the following procedure for connecting the insulated flexible ducts to the Tandem® transition* (EXHAUST AIR TO OUTSIDE and FRESH AIR FROM OUTSIDE). NOTE: If the joist are perpendicular to the ducts, or if the connection to the exterior

hood is in a limited area, your installation will need two exterior hoods instead of one. In this case, do not use the Tandem® transition. Identify each insulated duct. For fresh air from outside duct, use the blue sticker dots (one dot at each end). For exhaust air to outside duct, use the red sticker dots (one dot at each end). Then, go to point 4.6.2 and refer to the optional single hood enclosed instructions.

*Patent pending.

4.6.1CONNECTION TO TANDEM® TRANSITION

1.For each duct, pull back the insulation to expose the interior flexible duct.

2.Connect the interior flexible duct to the smaller part of the Tandem® transition (5’’ oval) using a 24’’ tie wrap.

NOTE: If you are using a 6’’ diameter insulated duct, use the bigger part of the Tandem® transition (6’’ oval).

3.Pull the insulation over the joint. Pull the vapor barrier over the insulation.

4.Apply duct tape gently to the joint in order to make an airtight seal. See figures below.

1

EXHAUST AIR TO OUTSIDE

 

DUCT ON TOP

VJ0025

 

3

 

2

VJ0022

4

VJ0023

VJ0024

Identify each insulated duct. For fresh air from outside duct, use the blue sticker dots (one dot at each end). For exhaust air to outside duct, use the red sticker dots (one dot at each end). Be careful to identify the exhaust air to outside duct (red dot) at the upper section of the transition.

- 23 -

Image 23
Contents Installation Instructions About this Manual About These Units Table of Contents Table DES Matières Before Starting Typical InstallationsTypical Installations CONT’D Hepa 1000 and HF 1.0 Unit Installations CONT’D RETURN-RETURN Installation Connection to a Forced AIR System Hepa 4000 Restricted Area VH0051 Hepa 2000, HF 2.0, Hepa 3000, HF 3.0 and Hepa Hepa 2000, HF 2.0, Hepa 3000, HF 3.0 and Hepa 4000 Unit VH0043 Front View TOP View DimensionsDimensions CONT’D Install the Unit Install the Unit CONT’D HOW to Hang the Unit CONT’D Stale air exhaust ductwork Stale air ductwork Filtered air ductwork Return side connection cont’d Hepa 2000, HF2.0, Hepa 3000, HF 3.0 and Hepa 4000 Units only Pull back the insulation to expose the flexible duct 457 mm Xmas tree pin Connecting the Drain Hepa 3000 and HF 3.0 Units only NORMAL/REMOTE ControlsControls C12 / CM and C34 / CMR Controls CONT’DControls C12 / CM and C34 / CMR CONT’D VD0088 Is on Normal or Boost Using C34 / CMR Control Maintenance For Hepa 2000 and HF 2.0 only Maintenance CONT’DMaster Reset C12 / CM and C34 / CMR Controls Parts Ordering Chart Problems Solutions Troubleshooting