Broan HEPA 2000, HEPA 4000, HEPA 3000, HEPA 1000 Controls C12 / CM and C34 / CMR CONT’D

Page 30

5.CONTROLS (CONT’D)

5.4INSTALLATION OF THE OPTIONAL WALL CONTROLS

(CONTROLS C12 / CM AND C34 / CMR) (CONTD)

5.Pass the other end of the cable through the wall. Reinstall the cover plate.Using wall anchors (not included) and provided screws, mount the wall control on the wall. See illustrations below.

2

3

1

4

 

 

5

VC0051

 

2

3

 

1

 

 

4

VC0052

 

1) Wall anchors

4) Control

1) Outlet box

3) Control

2) Control cable

5) Screws

2) Control cable

4) Screws

3)Control backplate

6.Route the cable to the unit.

CAUTION

Keep control low voltage wiring at least 1 foot (305 mm) away from motors, lightning ballast, light dimming circuit and power distribution panel. Do not route control wiring along with house power wiring. Avoid poor wiring connections. Failure to follow these practices can introduce electrical interference, which can cause erratic control operations.

7.Remove the front 8’’ oval port (A) and the front panel (B) of the unit by unscrewing their retaining screws.

A

VO0018

B

VO0019

- 30 -

Image 30
Contents Installation Instructions About this Manual About These Units Table of Contents Table DES Matières Typical Installations Before StartingTypical Installations CONT’D Hepa 1000 and HF 1.0 Unit Installations CONT’D RETURN-RETURN Installation Connection to a Forced AIR System Hepa 4000 Restricted Area VH0051 Hepa 2000, HF 2.0, Hepa 3000, HF 3.0 and Hepa Hepa 2000, HF 2.0, Hepa 3000, HF 3.0 and Hepa 4000 Unit VH0043 Dimensions Front View TOP ViewDimensions CONT’D Install the Unit Install the Unit CONT’D HOW to Hang the Unit CONT’D Stale air exhaust ductwork Stale air ductwork Filtered air ductwork Return side connection cont’d Hepa 2000, HF2.0, Hepa 3000, HF 3.0 and Hepa 4000 Units only Pull back the insulation to expose the flexible duct 457 mm Xmas tree pin Connecting the Drain Hepa 3000 and HF 3.0 Units only Controls NORMAL/REMOTEControls CONT’D Controls C12 / CM and C34 / CMRControls C12 / CM and C34 / CMR CONT’D VD0088 Is on Normal or Boost Using C34 / CMR Control Maintenance Maintenance CONT’D For Hepa 2000 and HF 2.0 onlyMaster Reset C12 / CM and C34 / CMR Controls Parts Ordering Chart Troubleshooting Problems Solutions