
TABLE 4
FURNACE DATA
Furnace Installed Standard | Field Installed Options |
|
|
| 2 |
|
| 2 |
|
| 2 |
| 1 |
| Heating | 1 |
| Heating | 1 |
| Heating |
| Nozzle | Input | Capacity | Nozzle | Input | Capacity | Nozzle | Input | Capacity |
Model Number | Size | BTUH | BTUH | Size | BTUH | BTUH | Size | BTUH | BTUH |
FLF085D36E | .75 | 105,000 | 85,000 | .65 | 91,000 | 74,000 | .55 | 77,000 | 63,000 |
|
|
|
|
|
|
|
|
|
|
FLR085D36E | .75 | 105,000 | 85,000 | .65 | 91,000 | 74,000 | .55 | 77,000 | 63,000 |
FLF110D48E | 1.00 | 140,000 | 113,000 | .85 | 119,000 | 96,000 | NA | NA | NA |
|
|
|
|
|
|
|
|
|
|
FLR110D48E | 1.00 | 140,000 | 113,000 | .85 | 119,000 | 96,000 | NA | NA | NA |
FLF110D60E | 1.00 | 140,000 | 113,000 | .85 | 119,000 | 96,000 | NA | NA | NA |
|
|
|
|
|
|
|
|
|
|
FLR110D60E | 1.00 | 140,000 | 113,000 | .85 | 119,000 | 96,000 | NA | NA | NA |
FLR140D60E | 1.25 | 175,000 | 142,000 | 1.10 | 154,000 | 125,000 | NA | NA | NA |
|
|
|
|
|
|
|
|
|
|
FC085D36E | .75 | 105,000 | 85,000 | .65 | 91,000 | 74,000 | .55 | 77,000 | 63,000 |
FH085D36E | .75 | 105,000 | 85,000 | .65 | 91,000 | 74,000 | .55 | 77,000 | 63,000 |
|
|
|
|
|
|
|
|
|
|
FH110D48E | 1.00 | 140,000 | 113,000 | .85 | 119,000 | 96,000 | NA | NA | NA |
FH110D60E | 1.00 | 140,000 | 113,000 | .85 | 119,000 | 96,000 | NA | NA | NA |
|
|
|
|
|
|
|
|
|
|
j70 degree hollow cone spray pattern, 100 PSIG pump pressure
kAnnual fuel utilization efficiency and heating capacity based upon U.S. Government standard test using D.O.E. isolated combustion rating procedure.
BURNER SETUP AND ADJUSTMENT PROCEDURES
All oil burner installations should be performed by a qualified installer in accordance with regulations of the National Fire Protection Standard for
The proper installation and adjustment of any oil burner requires technical knowledge and the use of combustion test instruments. The following procedure must be followed to correctly adjust the burner to match the specific characteristics of the installation.
IMPORTANT
Always use combustion test instruments when making burner adjustments and draft gauge when setting the barometric damper. It is virtually impossible to make accurate and reliable adjustments using the “eyeball” method.
Check all oil lines and connections for leaks.
Connect pressure gauge by removing bleed fitting and screwing in pressure gauge. See Figure 9.
1.PREPARATION STEPS
A.Calibrate and Check Operation of Measuring Equipment Follow manufacturer’s recommended procedures for calibration and equipment check out.
B.Prepare Heating Unit for Testing Drill two 1/4 inch holes in the flue between the heating plant and the barometric draft regulator. If space permits, the holes should be located in a straight section of the flue, at least two flue diameters from the elbow in the flue pipe and at least one diameter from the draft regulator. The purpose of the two holes in the flue pipe is to speed up testing and reduce instrument handling.
C.Clean and Seal Heating Plant Make sure the burner blast tube, fan housing, and blower wheel are clear of dirt and lint. Seal any air leaks into the combustion chamber.
D.Nozzle Inspection Annual replacement of nozzle is recommended. The nozzle size should match the design load . DO NOT OVERSIZE. (Determination of oversizing can be determined prior to your adjustment. If the firing rate should be reduced refer to Table 4.) Short cycles and low percent :on: time result in higher overall pollutant emissions and lower thermal efficiency. An
Manual
Page 14