Page 22

SPACING OF ELECTRODES

The electrodes should be spaced 5/32” apart. They should extend 1/16” beyond the end and 5/16” above the center of the nozzle tip as shown in Figure 10.

GUN ASSEMBLY ADJUSTMENT

The gun assembly can be adjusted in the slot inside of fan housing by loosening screw holding slot cover in position. Nozzle tip should ordinarily be located 1-1/8” behind the front face of the cone.

REMOVING GUN ASSEMBLY

Disconnect the oil line at the fan housing and remove lock nuts on copper tube fitting. Loosen igniter hold down clamps, then swing igniter up and backward. Gun assembly can now be removed through this opening.

COMBUSTION AIR REQUIREMENTS

This furnace must be installed in a location where a sufficient supply of combustion air is available for the complete combustion of the fuel oil. Keep in mind that a certain amount of excess air is required as well to ensure complete combustion of the fuel oil.

When structures are constructed too tightly to supply sufficient combustion air, air from outside the structure is required to be brought in directly to the furnace. This furnace has been conveniently designed to accept a combustion air boot which is attached directly to the outdoors by means of a 4” pipe. This pipe can be rigid or flexible, but it is recommended that a metallic material be used. Refer to Figure 11. The air boot used for this design is a Field Controls model number CAS-2B-90E that can be purchased through your local distributor. Follow all installation procedures as specified in the instructions packaged with the air boot kit.

FIGURE 10

ELECTRODE ADJUSTMENTS

1-1/8

5/32 GAP

5/16

1/16NOZZLE

MIS-160

Manual 2100-422

Page 20

Image 22
Contents OIL Furnace Installation Instructions Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersLocating the Furnace Equipment SelectionMinimum Clearances Specification Sheet Supply Specification Sheet Specification Sheet FC085 Model DimensionsInstruments Required for Proper Setup of the Furnace Installing the FurnaceInstalling a Cooling Unit InstallationField Wiring WiringFactory Wiring Electrical DataTypical Unit Setup FLF Unit Shown I m n e y OIL Line Piping Typical Single Inside Tank InstallationBeckett AFG OIL Burner Beckett Solid State Igniter Beckett Cleancut OIL PumpBeckett R7184B Primary Control Beckett R7184B Primary Operational Guide Cleaner Connection Electronic Blower ControlFurnace Data Burner Setup and Adjustment ProceduresPreparation Steps Combustion Adjustment Steps Combustion DiagnosisCheck Draft Short Form Adjustment ProcedureFinal Checks Smoke TestHigh Air Settings Low Bacharach Smoke Number Typical Smoke CO2 Chart with Adjustment RangePressure Gauge Connection to Bleed Port Recommended START-UP Settings No Fuel OIL Efficiency Chart NET Stack TEMP. Degrees FCorrelation of Percent of CO2, O2 Reserve AIR Electrode Adjustments GUN Assembly AdjustmentRemoving GUN Assembly Combustion AIR RequirementsCombustion AIR Boot Assembly Combination AIR Boot AssemblySquare Feet Required to Qualify AS Unconfined Space Appliances Located in Confined SpacesALL AIR from Inside Building ALL Ventilation AIR from Outdoors Minimum Ventilation OpeningsAppliances Located in Confined Spaces ALL AIR from Outdoors MIS-1338 Thermostat Louvers and GrillesVenting Options Vertical Venting200 Typical Installation of FR25 Filter KIT Typical Installation of FR26 FR27 Filter RacksFilter Sizes for OIL Furnaces Filter Installation LO-BOY Models LO-BOY Models Filter LocationsInspect AIR Filter Service HintsLubrication Final Inspection and TestCombination Combustion CHAMBER/BURNER Mounting System Removal of Burner onlyTo Remove the Entire Combustion Chamber Mounting System To Remove Burner onlyRemoval of Entire Combustion Chamber Mounting System Common Causes of Trouble Cleaning of the Heat ExchangerCare of Finish Chart FH110D60E Data Chart FH085D36E DataChart FH110D48E Data Chart FLF/FLR085D36E DataChart FLR140D60E Data Chart FC085D36E DataFH Series Wiring Diagram UnitCond Cond Unit