321 Studios FLF110D60E, FLF110D48E, FH110D48E, FLR140D60E, FLF085D36E FH Series Wiring Diagram, Unit

Page 37

FH SERIES

WIRING DIAGRAM

 

 

 

 

 

UNIT

 

 

 

 

 

NOTES

 

 

 

PURPLE

 

 

 

 

 

PRIMARY

AREA

 

 

 

 

 

 

 

BACKUP

1

IF PRIMARY LIMIT WIRES

 

 

 

 

 

 

 

 

LIMIT

USE WIRE WITH INSUL.

 

 

 

PURPLE

 

 

 

 

 

 

 

 

 

ARE TO BE REPLACED,

 

 

BURNER ASS'Y

 

 

 

 

LIMIT

CONTROL

EXCHANGER

 

TEMP. RATING OF 200°C.

 

 

 

 

 

 

 

 

 

 

ONLY ONE HEATING

 

 

VALVE

OIL VALVE

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

 

 

 

 

2

HEATING SPEED

 

T T

L2

 

 

 

 

 

 

 

 

 

3

COOLING SPEED

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTION POINT.

 

BURNER

BURNER

 

 

 

 

 

 

 

HEAT

 

AND COOLING SPEED

 

 

 

 

 

 

BLACK

BLACK

4

CAN BE CONNECTED.

 

MOTOR

MOTOR

 

WHITE

BLACK

BLACK

BLACK

ALL OTHER TAPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECT TO "SPARE"

 

IGNITOR

IGNITOR

 

 

 

 

 

 

 

 

 

TERMINALS.

 

 

 

 

 

 

 

 

 

 

DASHED LINES

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

REPRESENT FIELD WIRING.

 

CAD CELL

CAD CELL

 

 

 

 

 

 

 

 

 

! DANGER

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*ELECTRICAL SHOCK HAZARD

 

 

 

 

 

 

 

 

 

 

 

 

*DISCONNECT POWER BEFORE

 

 

 

 

 

 

 

 

 

 

 

 

SERVICING.

 

 

 

 

 

 

 

 

BLACK

 

 

 

HOT

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

NEUTRAL

 

PLUG

 

 

 

 

 

 

GREEN

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

#1

3 4

5 6 7 8 9

 

 

PLUG #2

 

 

 

 

WARNING

 

1 2

1

2

 

 

 

 

 

!

 

PURPLE

PURPLE BLACK

 

 

 

 

 

 

 

 

 

IF ANY OF THE ORIGINAL WIRE AS

 

BLACK

 

 

 

 

BLACK BLACK

 

 

 

SUPPLIED WITH THIS APPLIANCE

 

 

GREEN

 

 

 

DOOR

 

MUST BE REPLACED, IT MUST BE

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

REPLACED WITH WIRING MATERIAL

 

 

 

 

 

 

 

 

 

SWITCH

 

HAVING A TEMP. RATING OF AT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEAST 105°C EXCEPT PRIMARY

5

 

 

 

 

 

 

 

 

 

 

 

LIMIT WIRES. SEE NOTE "1".

 

 

 

 

 

 

 

 

GREEN

 

 

 

C Y

Rc Y G

W

Rh

 

 

 

 

 

 

 

 

 

 

 

 

 

R

W G

Y

C

 

SEC2

T SEC1

BLUE

 

 

 

COND.

 

 

 

 

180

 

 

 

 

 

 

 

 

 

THERMOSTAT

150

 

 

 

 

 

 

 

 

PANEL

UNIT

 

 

 

 

210

BLOWER CONTROL

 

24V

 

 

OR EQUIVELANT

240

 

 

 

 

CONN.

 

 

 

T

 

 

 

 

24V.

 

T87F/Q539A1220

HUM HEAT

COOL EAC

3

SPR1

SPR2

SPR3

 

 

TRANSFORMER

 

CONTROL

OPTIONAL AIR COND. SETTINGS

 

L2 COM

L1

 

 

 

 

NOM.

COOLING BLOWER

CFM @

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120V

COM

 

 

UNIT

A/C

 

 

 

 

 

 

 

 

 

 

SPEED (COLOR)

.50 WC

 

 

 

 

 

 

4

 

 

 

TONS

 

 

 

 

 

 

 

 

 

 

 

2

LOW (RED)

730

 

 

 

 

 

 

 

 

BLACK

 

 

 

FH085D36E

2 1/2

MED (BLUE)

900

2

 

 

 

 

WHITE WHITE

 

 

 

 

3

HIGH (BLACK)

1160

 

 

 

 

 

 

 

 

 

3

MED-LOW (ORANGE)

1280

 

 

 

 

 

 

 

 

 

 

 

 

 

2 1/2

LOW (RED)

1020

 

 

 

 

 

 

 

 

SEE CHART FOR

 

 

 

FH110D48E

3 1/2

MED-HIGH (BLUE)

1495

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

HEATING AND COOLING

 

 

 

4

HIGH (BLACK)

1640

 

PLUG #3

 

 

 

 

 

 

 

3

LOW (RED)

1300

 

 

 

 

 

 

WIRE COLORS

 

 

 

FH110D60E

3 1/2

MED-LOW (ORANGE)

1460

 

 

 

 

 

 

 

 

 

 

 

 

4

MID-HIGH (BLUE)

1660

 

 

 

 

1 2 3 4 5

 

 

 

 

 

 

BLOWER

 

 

 

 

 

 

5

HIGH (BLACK)

1970

 

 

BLACK BLUE ORANGE

RED WHITE

AREA

 

 

 

FACTORY SETTINGS

 

 

LOW

CAPACITOR

 

INPUT

HEATING BLOWER COOLING BLOWER

TEMP.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

RATE

RISE

VOLTAGE

 

 

 

 

 

 

 

 

SPEED (COLOR)

 

SPEED (COLOR)

 

 

 

 

 

 

 

 

 

GPH

 

RANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.55

 

LOW (RED)

 

 

70°-100°

HIGH

 

 

 

 

 

 

 

RETURN

FH085D36E

0.65

 

LOW (RED)

 

 

70°-100°

 

BROWN

BROWN

 

 

 

 

FH110D60E

0.75

 

MED (BLUE)

 

 

 

60°-90°

VOLTAGE

 

 

 

 

0.85

 

LOW (RED)

 

HIGH (BLACK)

70°-100°

 

 

 

 

 

 

 

FH110D48E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

MED-LOW (ORANGE)

 

 

60°-90°

 

 

 

 

 

 

 

 

 

 

0.85

 

LOW (RED)

 

 

 

60°-90°

FIELD

 

 

 

 

 

 

 

 

 

1

MED-LOW (ORANGE)

 

 

60°-90°

 

 

 

 

 

 

 

 

BLOWER CAPACITOR RATING

 

 

 

 

WIRING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

MOTOR

CAPACITOR

 

4047-118 B

 

 

 

 

 

 

 

 

 

FH110D48E

1/2

7.5/370

 

 

 

 

 

BLOWER ASSEMBLY

FH085D36E

1/3

5/370

 

 

 

 

 

 

 

 

FH110D60E

3/4

15/370

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual 2100-422 Page 35

Image 37
Contents OIL Furnace Installation Instructions Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsLocating the Furnace Equipment SelectionMinimum Clearances Specification Sheet Supply Specification Sheet FC085 Model Dimensions Specification SheetInstalling a Cooling Unit Installing the FurnaceInstruments Required for Proper Setup of the Furnace InstallationFactory Wiring WiringField Wiring Electrical DataTypical Unit Setup FLF Unit Shown I m n e y OIL Line Piping Typical Single Inside Tank InstallationBeckett AFG OIL Burner Beckett Solid State Igniter Beckett Cleancut OIL PumpBeckett R7184B Primary Control Beckett R7184B Primary Operational Guide Electronic Blower Control Cleaner ConnectionFurnace Data Burner Setup and Adjustment ProceduresPreparation Steps Combustion Diagnosis Combustion Adjustment StepsFinal Checks Short Form Adjustment ProcedureCheck Draft Smoke TestTypical Smoke CO2 Chart with Adjustment Range High Air Settings Low Bacharach Smoke NumberPressure Gauge Connection to Bleed Port Recommended START-UP Settings No Fuel OIL Efficiency Chart NET Stack TEMP. Degrees FCorrelation of Percent of CO2, O2 Reserve AIR Removing GUN Assembly GUN Assembly AdjustmentElectrode Adjustments Combustion AIR RequirementsCombination AIR Boot Assembly Combustion AIR Boot AssemblySquare Feet Required to Qualify AS Unconfined Space Appliances Located in Confined SpacesALL AIR from Inside Building ALL Ventilation AIR from Outdoors Minimum Ventilation OpeningsAppliances Located in Confined Spaces ALL AIR from Outdoors MIS-1338 Venting Options Louvers and GrillesThermostat Vertical Venting200 Typical Installation of FR25 Filter KIT Typical Installation of FR26 FR27 Filter RacksFilter Sizes for OIL Furnaces LO-BOY Models Filter Locations Filter Installation LO-BOY ModelsLubrication Service HintsInspect AIR Filter Final Inspection and TestRemoval of Burner only Combination Combustion CHAMBER/BURNER Mounting SystemTo Remove the Entire Combustion Chamber Mounting System To Remove Burner onlyRemoval of Entire Combustion Chamber Mounting System Common Causes of Trouble Cleaning of the Heat ExchangerCare of Finish Chart FH110D48E Data Chart FH085D36E DataChart FH110D60E Data Chart FLF/FLR085D36E DataChart FC085D36E Data Chart FLR140D60E DataUnit FH Series Wiring DiagramCond Cond Unit