321 Studios FLR110D60E, FLF110D48E, FH110D48E warranty High Air Settings Low Bacharach Smoke Number

Page 19

FIGURE 8

TYPICAL SMOKE – CO2 CHART WITH ADJUSTMENT RANGE

High

Air Settings

Low

8

Bacharach Smoke Number

CO2 Curve

6from plotted points

Plotted point

 

Normal

 

adjustment

4

range

 

Tolerance

 

 

 

 

to "knee"

 

 

 

 

"Best" air

 

Plotted point

 

2

setting

 

 

 

Plotted point

 

 

 

 

 

 

"Knee"

 

0

 

 

 

 

6

8

10

12

14

 

 

Percent CO2

in Flue Gas

 

Bacharach Smoke Number

Technician's plotting area

8

6

4

2

0

6

8

10

12

14

 

 

Percent CO2

in Flue Gas

MIS-1827

Manual 2100-422 Page 17

Image 19
Contents OIL Furnace Installation Instructions Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsLocating the Furnace Equipment SelectionMinimum Clearances Specification Sheet Supply Specification Sheet FC085 Model Dimensions Specification SheetInstallation Installing the FurnaceInstalling a Cooling Unit Instruments Required for Proper Setup of the FurnaceElectrical Data WiringFactory Wiring Field WiringTypical Unit Setup FLF Unit Shown I m n e y OIL Line Piping Typical Single Inside Tank InstallationBeckett AFG OIL Burner Beckett Solid State Igniter Beckett Cleancut OIL PumpBeckett R7184B Primary Control Beckett R7184B Primary Operational Guide Electronic Blower Control Cleaner ConnectionFurnace Data Burner Setup and Adjustment ProceduresPreparation Steps Combustion Diagnosis Combustion Adjustment StepsSmoke Test Short Form Adjustment ProcedureFinal Checks Check DraftTypical Smoke CO2 Chart with Adjustment Range High Air Settings Low Bacharach Smoke NumberPressure Gauge Connection to Bleed Port Recommended START-UP Settings No Fuel OIL Efficiency Chart NET Stack TEMP. Degrees FCorrelation of Percent of CO2, O2 Reserve AIR Combustion AIR Requirements GUN Assembly AdjustmentRemoving GUN Assembly Electrode AdjustmentsCombination AIR Boot Assembly Combustion AIR Boot AssemblySquare Feet Required to Qualify AS Unconfined Space Appliances Located in Confined SpacesALL AIR from Inside Building ALL Ventilation AIR from Outdoors Minimum Ventilation OpeningsAppliances Located in Confined Spaces ALL AIR from Outdoors MIS-1338 Vertical Venting Louvers and GrillesVenting Options Thermostat200 Typical Installation of FR25 Filter KIT Typical Installation of FR26 FR27 Filter RacksFilter Sizes for OIL Furnaces LO-BOY Models Filter Locations Filter Installation LO-BOY ModelsFinal Inspection and Test Service HintsLubrication Inspect AIR FilterRemoval of Burner only Combination Combustion CHAMBER/BURNER Mounting SystemTo Remove the Entire Combustion Chamber Mounting System To Remove Burner onlyRemoval of Entire Combustion Chamber Mounting System Common Causes of Trouble Cleaning of the Heat ExchangerCare of Finish Chart FLF/FLR085D36E Data Chart FH085D36E DataChart FH110D48E Data Chart FH110D60E DataChart FC085D36E Data Chart FLR140D60E DataUnit FH Series Wiring DiagramCond Cond Unit