DCA-70SSIU (60 Hz) — LOAD APPLICATION

Single Phase Load

Always be sure to check the nameplate on the generator and equipment to insure the wattage, amperage, frequency, and voltage requirements are satisfactorily supplied by the generator for operating the equipment.

Generally, the wattage listed on the nameplate of the equipment is its rated output. Equipment may require 130— 150% more wattage than the rating on the nameplate, as the wattage is influenced by the efficiency, power factor and starting system of the equipment.

If wattage is not given on the equipment's name plate,

NOTE approximate wattage may be determined by multiplying nameplate voltage by the nameplate amperage.

WATTS = VOLTAGE x AMPERAGE

The power factor of this generator is 0.8. See Table 4 below when connecting loads.

Table 5. Power Factor By Load

 

 

Type Of Load

 

 

 

 

 

Power Factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-phase induction motors

 

 

0.4 - 0.75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electric heaters, incandescent

 

 

1.0

 

 

 

 

lamps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluorescent lamps, mercury lamps

 

 

0.4 - 0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic devices, communication

 

 

1.0

 

 

 

 

equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Common power tools

 

 

 

 

 

 

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 6. Cable Selection (60 Hz, Single Phase Operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current in

Load In Watts

 

 

 

Maximum Allowable Cable Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amperes

At 100

At 200

 

#10 Wire

 

#12 Wire

#14 Wire

 

#16 Wire

 

 

 

Volts

Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

300

600

 

1000 ft.

 

600

ft.

375 ft.

 

250 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

600

1200

 

500

ft.

 

300

ft.

200 ft.

 

125 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

900

1800

 

350

ft.

 

200

ft.

125 ft.

 

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

1200

2400

 

250

ft.

 

150

ft.

100 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

1800

3600

 

150

ft.

 

100

ft.

65 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

2400

4800

 

125

ft.

 

75 ft.

50 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION: Equipment damage can result from low voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Three Phase Load

When calculating the power requirements for 3-phase power use the following equation:

If 3Ø load (kVA) is not given on the equipment nameplate,

NOTEapproximate 3Ø load output maybedeterminedbymultiplying voltage by amperage by 1.732.

Motors and motor-driven

NOTEequipment draw much greater current for starting than during operation.

An inadequate size connecting cable which cannot carry the required load can cause a voltage drop which can burn out the appliance or tool and overheat the cable. See Table 5.

When connecting a resistance load such as an incandescent lamp or electric heater, a capacity of up to the generating set’s rated output (kW) can be used.

When connecting a fluorescent or mercury lamp, a capacity of up to the generating set’s rated output (kW) multiplied by 0.6 can be used.

When connecting an electric drill or other power tools, pay close attention to the required starting current capacity.

When connecting ordinary power tools, a capacity of up to the generating set’s rated output (kW) multiplied by 0.8 can be used.

DANGER - ELECTRICAL SYSTEM HAZARDS

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

DCA-70SSIU (60 Hz) — OPERATION AND PARTS MANUAL — REV. #1 (01/06/09) — PAGE 27

Image 27
Contents Model DCA-70SSIU Parts List NO. M2870300504Page Wilmington Ave Carson, CA Heres HOW to GET HelpTable of Contents Direct TOLL-FREE access to our Parts Department DCA-70SSIU 60 Hz Specifications Dimensions DCA-70SSIU 60 Hz Dimensions TOP, Side and FrontHazard Symbols DCA-70SSIU 60 Hz Safety Message Alert SymbolsThis generator, other property, or DCA-70SSIU 60 Hz Safety Message Alert SymbolsGeneral Safety DCA-70SSIU 60 Hz Rules for Safe OperationBurns Electrical Safety DCA-70SSIU 60 Hz Rules for Safe OperationGenerator Grounding Battery Safety Maintenance SafetyEmergencies Towing &Transporting SafetyDCA-70SSIU 60 Hz Generator Decals Generator Decals Cont inued DCA-70SSIU 60 Hz Generator DecalsTypical Generator Grounding Application DCA-70SSIU 60 Hz InstallationWhen connecting the generator DCA-70SSIU 60 Hz InstallationOutdoor Installation Indoor InstallationOutput Terminal Panel GeneratorEngine Operating Panel Generator Control PanelMajor Components DCA-70SSIU 60 Hz Major ComponentsPage DCA-70SSIU 60 Hz Generator Control Panel DCA-70SSIU 60 Hz Engine Operating Panel Major faults will shutdown the generator DCA-70SSIU 60 Hz Engine Operating PanelAuto On/Off Engine Controller Mpec Output Terminal Familiarization DCA-70SSIU 60 Hz Output Terminal Panel Familiarization120VAC Gfci Receptacles DCA-70SSIU 60 Hz Output Terminal Panel FamiliarizationBlower Fan Connecting LoadsMotors and motor-driven Single Phase LoadThree Phase Load DCA-70SSIU 60 Hz Load ApplicationGfci Receptacle Load Capability Voltage Selector SwitchGenerator Amperage Generator OutputVoltagesHow to Read the OutputTerminal Gauges DCA-70SSIU 60 Hz Gauge ReadingReading Amperage 3Ø 240/139 Output Terminal Lug Voltages Three-Phase PositionDCA-70SSIU 60 Hz Output Terminal Panel Connections Uvwo Terminal Output VoltagesDCA-70SSIU 60 Hz Output Terminal Panel Connections 3Ø 480/277 Output Terminal Lug Voltages1Ø 240V/120V Output Terminal Lug Voltages Fuel Check DCA-70SSIU 60 Hz PRE-SETUPCircuit Breakers Lubrication OilRefueling Refueling ProcedureVol % Freezing Point Cleaning the RadiatorAir Cleaner Fan Belt Tension Operation FreezingWeatherAlternator BatteryBattery Cable Installation WiringDirect exhaust away from nearby personnel DCA-70SSIU 60 Hz Generator START-UP Procedure ManualBefore Starting Engines exhaust contains harmful emissionsNo Load Engine Running LED onStarting Auto Mode Shutdown ProcedureEmergency Shutdown Procedure DCA-70SSIU 60 Hz Maintenance Replacing Oil Filter Cleaning the Fuel StrainerAir Removal Check Oil LevelTo ensure adequate starting DCA-70SSIU 60 Hz MaintenanceCoupler Type of hitch used on the trailer for towing Trailer MaintenanceCheck the wheel and drum for free rotation DCA-70SSIU 60 Hz -TRAILER MaintenanceBrake Adjustment BrakesTires/Wheels/Lug Nuts TireWear/InflationSuspension DCA-70SSIU 60 Hz -TRAILER Maintenance Lug Nut Torque RequirementsStart all wheel lug nuts by hand DCA-70SSIU 60 Hz -TRAILERWIRING Diagram DCA-70SSIU 60 Hz Operation and Parts Manual REV. #1 01/06/09 Generator Wiring Diagram DCA-70SSIU 60 Hz Generatorwiring DiagramEngine Wiring Diagram DCA-70SSIU 60 Hz Enginewiring DiagramGenerator Troubleshooting DCA-70SSIU 60 Hz -TROUBLESHOOTING GeneratorEngine Controller Troubleshooting Mpec DCA-70SSIU 60 Hz -TROUBLESHOOTING Engine ControllerIf more than one of the same Items Found In the Items Number ColumnDCA-70SSIU 60 Hz Suggested Spare Parts Part number on this Suggested Spare Parts listDCA-70SSIU 60 HZ Generator Assy DCA-70SSIU 60 Hz Generator Assy DCA-70SSIU 60 Hz Control BOX Assy 0601870432 M22130014020330000180 0330000240DCA-70SSIU 60 Hz Control BOX ASSY. 0601807641 060220254635A 0040506000 M2223000603DCA-70SSIU 60 Hz Engine and Radiator Assy M1303200103 B59232000341132402321 1132400791DCA-70SSIU 60 Hz Engine and Radiator ASSY. 0269200500 06055113950603306395 0602021070Output Terminal Assy DCA-70SSIU 60 Hz Outputterminal Assy0040020000 M3230700003M3278500004 0801830904DCA-70SSIU 60 Hz Actuator Assy 0343502090 06021500950030006000 M2354200104DCA-70SSIU 60 Hz Battery Assy 0602220920 0602220187M9310500014 M9103000304DCA-70SSIU 60 Hz Muffler Assy 3943690210 B53301003030016910025 M2333001203DCA-70SSIU 60 Hz Fueltank Assy 0605516090 M23630001020605505070 0605501074Enclosure Assy DCA-70SSIU 60 Hz Enclosure AssyM2493107203 M2413001902M1413400004 M2423001602DCA-70SSIU 60 Hz Enclosure ASSY. 35A 0042308000 M245320160234A M2493408704 0019108055DCA-70SSIU 60 Hz Rubber Seals Assy 0228901120 02289016600228900915 0228900745DCA-70SSIU 60 Hz Name Plate and Decals Assy M2550001803 M1550000204M1550002203 M1550001304Freightpolicy EffectiveOctober 1, 2002 Terms and Conditions of Sale PartsDCA-70SSIU 60 Hz Operation and Parts Manual REV. #1 01/06/09 Your Local Dealer is