Multiquip DCA-15SPXU4 operation manual Refueling Procedure

Page 28

Refueling Procedure:

WARNING - RESPIRATORY HAZARDS

Diesel fuel and its vapors are dangerous to your health and the surrounding environment. Avoid skin contact and/or inhaling fumes.

1.Level Tanks – Make sure fuel cells are level with the ground. Failure to do so will cause fuel to spill from the tank before reaching full capacity (Figure 19).

CAUTION - REFUELINGTHE GENERATOR

ALWAYS place trailer on firm level ground before refueling to prevent spilling and maximize the amount of fuel that can be pumped into the tank.

Figure 19. Only Fill on Level Ground

 

DCA-15SPXU4 — SETUP

NOTE

If generator is equipped with an

 

environmental fuel tank, reference

 

Figures 21 and 22.

3.NEVER overfill fuel tank – It is important to read the fuel gauge when filling trailer fuel tank. DO NOT wait for fuel to rise in filler neck (Figure 21).

Figure 21. Full Fuel Tank

CAUTION - REFUELINGTHE GENERATOR

DO NOT OVER-FILLfuel system. Leave room for fuel expansion. Fuel expands when heated (Figure 22).

NOTE

ONLY! use #2 diesel fuel when

 

refueling.

Figure 22. Fuel Expansion

2.Remove fuel cap (internal fuel tank) and fill fuel tank as shown Figure 20.

Figure 20. Fueling the Generator

PAGE 28 — DCA-15SPXU4— OPERATION MANUAL — REV. #0 (03/31/11)

Image 28
Contents Model DCA-15SPXU4 Diesel engine exhaust and some Page Table of Contents Page DCA-15SPXU4 Specifications DCA-15SPXU4 Dimensions TOP, Side and Front DimensionsDCA-15SPXU4 Safety Message Alert Symbols Hazard SymbolsDCA-15SPXU4 Safety Message Alert Symbols General Safety DCA-15SPXU4 Rules for Safe OperationInjury People Carbon monoxide gasMaintenance Safety DCA-15SPXU4 Rules for Safe OperationBattery Safety Death Towing and Transporting Safety Guidelines section in this manualPage DCA-15SPXU4 Installation DCA-15SPXU4 Installation Outdoor InstallationIndoor Installation MountingGenerator Generator Control PanelOutput Terminal Panel Open Delta Excitation SystemDCA-15SPXU4 Major Components Major Components12 11 DCA-15SPXU4 Generator Control PanelDCA-15SPXU4 Generator Control Panel DCA-15SPXU4 Output Terminal Panel Familiarization Output Terminal Familiarization120VAC Gfci Receptacle DCA-15SPXU4 Output Terminal Panel FamiliarizationL5-30RTwist Lock 120VAC Receptacle Connecting Loads DCA-15SPXU4 Output Terminal Panel FamiliarizationSingle Phase Load DCA-15SPXU4 Load APPLICATION/MAXIMUM AmperageMotors and motor-driven Generator AmperageAmmeter gauge will only Show a reading when the Output DCA-15SPXU4 Gauge READING/TERMINAL Panel ConnectionsUNV Terminal Output Voltages 1Ø 120 Output Terminal Lug VoltagesCircuit Breakers Lubrication OilFuel Check Refilling the Fuel SystemRefueling Procedure RefuelingCleaning the Radiator Air Cleaner Fan Belt TensionCoolant Antifreeze/Summer Coolant/Water Operation FreezingWeatherBattery Battery Cable InstallationWiring AlternatorDCA-15SPXU4 Generator START-UP Procedure Before StartingEngines exhaust contains harmful emissions Direct exhaust away from nearby personnelDCA-15SPXU4 Generator START-UP Procedure On position FigureNormal Shutdown Procedure Emergency Shutdown ProcedureGeneral Inspection Air Cleaner Air Cleaner with Dust Indicator If EquippedService Daily Fuel AdditionCleaning the Fuel Strainer Air RemovalCheck Oil Level Replacing Oil FilterBattery Charger JacketWater Heater Power Connections To ensure adequate startingDCA-15SPXU4 -TRAILER Maintenance Brake AdjustmentBrakes Check the wheel and drum for free rotationTireWear/Inflation Tires/Wheels/Lug NutsSuspension Lug Nut Torque Requirements Start all wheel lug nuts by handDCA-15SPXU4 Generatorwiring Diagram Generator Wiring DiagramDCA-15SPXU4 Enginewiring Diagram Engine Wiring DiagramDCA-15SPXU4 -TROUBLESHOOTING Engine DCA-15SPXU4 -TROUBLESHOOTING Engine DCA-15SPXU4 -TROUBLESHOOTING Generator Generator TroubleshootingDCA-10SPX4 -TROUBLESHOOTING PRE-HEAT Lamp Codes Failure Diagnosis Lamp CodeHERE’S HOW to GET Help