Multiquip operation manual DCA-15SPXU4 -TROUBLESHOOTING Generator, Generator Troubleshooting

Page 44

DCA-15SPXU4 —TROUBLESHOOTING (GENERATOR)

Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a breakdown, use Table 17 shown below for diagnosis of the generator. If the problem cannot be remedied, consult our company's business office or service plant.

TABLE 17. GENERATOR TROUBLESHOOTING

SYMPTOM

POSSIBLE PROBLEM

SOLUTION

 

 

 

No Voltage Output

AC Voltmeter defective?

Check output voltage using a voltmeter.

 

 

 

 

Is wiring connection loose?

Check wiring and repair.

 

 

 

 

Is AVR defective?

Replace if necessary.

 

 

 

 

Defective Rotating Rectifier?

Check and replace.

 

 

 

 

Defective Exciter Field?

Check for 17.3 ohms across J & K on CN1

 

 

 

Low Voltage Output

Is engine speed correct?

Turn engine throttle lever to "High".

 

 

 

 

Is wiring connections loose?

Check wiring and repair.

 

 

 

 

Defective AVR?

Replace if necessary.

 

 

 

High Voltage Output

Is wiring connections loose?

Check wiring and repair.

 

 

 

 

Defective AVR?

Replace if necessary.

 

 

 

Circuit Breaker Tripped

Short Circuit in load?

Check load and repair.

 

 

 

 

Over current?

Confirm load requirements and reduce.

 

 

 

 

Defective circuit breaker?

Check and replace.

 

 

 

 

Over current Relay actuated?

Confirm load requirement and replace.

 

 

 

PAGE 44 — DCA-15SPXU4— OPERATION MANUAL — REV. #0 (03/31/11)

Image 44
Contents Model DCA-15SPXU4 Diesel engine exhaust and some Page Table of Contents Page DCA-15SPXU4 Specifications DCA-15SPXU4 Dimensions TOP, Side and Front DimensionsDCA-15SPXU4 Safety Message Alert Symbols Hazard SymbolsDCA-15SPXU4 Safety Message Alert Symbols General Safety DCA-15SPXU4 Rules for Safe OperationInjury People Carbon monoxide gasMaintenance Safety DCA-15SPXU4 Rules for Safe OperationBattery Safety Death Towing and Transporting Safety Guidelines section in this manualPage DCA-15SPXU4 Installation DCA-15SPXU4 Installation Outdoor InstallationIndoor Installation MountingGenerator Generator Control PanelOutput Terminal Panel Open Delta Excitation SystemDCA-15SPXU4 Major Components Major Components12 11 DCA-15SPXU4 Generator Control PanelDCA-15SPXU4 Generator Control Panel DCA-15SPXU4 Output Terminal Panel Familiarization Output Terminal FamiliarizationL5-30RTwist Lock 120VAC Receptacle DCA-15SPXU4 Output Terminal Panel Familiarization120VAC Gfci Receptacle Connecting Loads DCA-15SPXU4 Output Terminal Panel FamiliarizationSingle Phase Load DCA-15SPXU4 Load APPLICATION/MAXIMUM AmperageMotors and motor-driven Generator AmperageAmmeter gauge will only Show a reading when the Output DCA-15SPXU4 Gauge READING/TERMINAL Panel ConnectionsUNV Terminal Output Voltages 1Ø 120 Output Terminal Lug VoltagesCircuit Breakers Lubrication OilFuel Check Refilling the Fuel SystemRefueling Procedure RefuelingCleaning the Radiator Air Cleaner Fan Belt TensionCoolant Antifreeze/Summer Coolant/Water Operation FreezingWeatherBattery Battery Cable InstallationWiring AlternatorDCA-15SPXU4 Generator START-UP Procedure Before StartingEngines exhaust contains harmful emissions Direct exhaust away from nearby personnelDCA-15SPXU4 Generator START-UP Procedure On position FigureNormal Shutdown Procedure Emergency Shutdown ProcedureGeneral Inspection Air Cleaner Air Cleaner with Dust Indicator If EquippedService Daily Fuel AdditionCleaning the Fuel Strainer Air RemovalCheck Oil Level Replacing Oil FilterBattery Charger JacketWater Heater Power Connections To ensure adequate startingDCA-15SPXU4 -TRAILER Maintenance Brake AdjustmentBrakes Check the wheel and drum for free rotationSuspension Tires/Wheels/Lug NutsTireWear/Inflation Lug Nut Torque Requirements Start all wheel lug nuts by handDCA-15SPXU4 Generatorwiring Diagram Generator Wiring DiagramDCA-15SPXU4 Enginewiring Diagram Engine Wiring DiagramDCA-15SPXU4 -TROUBLESHOOTING Engine DCA-15SPXU4 -TROUBLESHOOTING Engine DCA-15SPXU4 -TROUBLESHOOTING Generator Generator TroubleshootingDCA-10SPX4 -TROUBLESHOOTING PRE-HEAT Lamp Codes Failure Diagnosis Lamp CodeHERE’S HOW to GET Help