DCA-220SSJ — GENERATOR OUTPUTS
Generator OutputVoltages
A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by apply- ing jumpers (6) to the voltage
Voltage Change-Over Board
The voltage
Generator Amperage
Tables 8 and 9 describe the generator’s current output capa- bility for both
Table 8. Generator Ampere Ratings
⎯1∅
kW | 120V | 240V |
|
|
|
16 | 134 | 67 |
|
|
|
36 | 300 | 150 |
|
|
|
56 | 467 | 233 |
|
|
|
76 | 634 | 317 |
|
|
|
96 | 800 | 400 |
|
|
|
116 | 966 | 483 |
|
|
|
136 | 1,136 | 568 |
|
|
|
156 | 1,300 | 650 |
|
|
|
176 (Max) | 1,466 | 733 |
|
|
|
Figure 16. Voltage Change-Over Board
CAUTION - CHANGINGVOLTAGES
NEVER attempt to place jumper plates on the voltage
Table 7. Voltages Available
Three Phase | 208V | 220V | 240V | 416V | 440V | 480V | |
(Selectable) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
Single Phase | 120V | 127V | 139V | 240V | 254V | 277V | |
(Selectable) | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
Table 9. Generator Ampere Ratings ⎯ 3∅
KVA | 240V | 480V |
|
|
|
25 | 60 | 30 |
|
|
|
45 | 108 | 54 |
|
|
|
60 | 144 | 72 |
|
|
|
70 | 168 | 84 |
|
|
|
82 | 197 | 99 |
|
|
|
100 | 241 | 120 |
|
|
|
125 | 301 | 150 |
|
|
|
150 | 361 | 180 |
|
|
|
180 | 433 | 216 |
|
|
|
220 | 529 | 265 |
|
|
|
PAGE 44 —