Guardian Technologies 02010-2, 04164-3 SUMMER/WINTER Heat Riser System, Stopping the Generator

Page 11

Section 2 – Operation

NOTE:

If starting from the generator control panel, turn OFF loads by setting the generator’s main circuit breaker to the OFF (or OPEN) position. If starting from a remote panel, turn OFF loads using the means provided in the vehicle (such as a main circuit breaker). Electrical load circuits will be turned ON after the generator has started, stabi- lized and warmed up.

2.If the engine has not been started in more than two weeks, press the Fuel Pump Primer switch and hold it for about 10 to 15 seconds to prime the fuel system. However, if the engine is warm, skip Step 2.

3.Hold the engine Start/Stop switch in the START position to crank the engine. Release the switch when the engine starts.

If the engine does not start after it has been cranking for 15 seconds, release the Start/Stop switch and try again. Holding the switch for longer than 15 seconds can damage the starter motor.

4.Let the engine run at no-load for a few minutes to stabilize and warm up.

5.Turn ON electrical loads using the means pro- vided (such as a main circuit breaker or transfer switch).

Recreational Vehicle Generator

2.8SUMMER/WINTER HEAT

RISER SYSTEM

Under certain weather conditions, it is possible for ice to form in the venturi area of the carburetor. This condition can be very dangerous because it can pre- vent the governor system from functioning properly, which results in a “runaway” engine.

The most common weather conditions leading to this problem are temperatures in the range of 25° F to 35° F (-4° C to 1.7° C), along with high humidity. This ice formation also can be attributed to the load being applied during these weather conditions. Generators running with no-load or light loads applied usually have the most problems.

The Summer/Winter Lever (Figure 2.3) should be in the WINTER position for ambient temperatures below 40° F (4.4° C) and in the SUMMER position for ambient temperatures above 40° F (4.4° C).

Figure 2.3 – Heat Riser System

2.6STOPPING THE GENERATOR

1.Turn OFF all electrical loads using the means provided (such as a main circuit breaker or transfer switch).

2.Let generator run at no-load for a few minutes, to stabilize internal engine generator temperatures.

3.Place the Start/Stop switch in its STOP position.

2.7APPLYING LOADS TO GENERATOR

When applying electrical loads to the generator, observe these guidelines:

Before applying electrical loads, let the generator stabilize and warm up for a minute or two.

DO NOT overload the generator.

‹2.7.1 LETTING THE ENGINE STABILIZE

The generator supplies correct rated voltage only at the proper governed speed. Some electrical appli- ances may be extremely sensitive to voltage. Incorrect voltages can damage such appliances.

If electrical loads are applied at reduced operating speeds, such loads imposed on the engine when suf- ficient power is not available may shorten engine life. Never turn ON electrical loads until after the generator engine has started and stabilized at no-load.

When the heat riser is in the SUMMER (down) posi- tion (Figure 2.2), air is drawn into the air cleaner from the upper intake tube.

When the heat riser is in the WINTER (up) position, air is drawn from the lower intake tube, which is positioned to draw the heated air near the exhaust manifold.

To prevent carburetor icing, the owner/operator should physically position the heat riser to the prop- er position dependent on the temperature.

9

Image 11
Contents Air-cooled Recreational Vehicle Generators Introduction Authorized Service Dealer LocationInside Front Cover Part II Installation Instructions Warning   Electrical Hazards  Model Generator IdentificationGenerator AC Connection System SafetySpecifications Generator Applicability‹ 1.5.6 Generator ‹ 1.5.2 Optional Propane Fuel System‹ 1.5.3 Fuel Consumption ‹ 1.5.4 Engine OIL RequirementsAutomatic Choke Gasoline only Generator Control PanelOptional Remote START/STOP Panel Starting the Generator Before Starting the Engine‹ 2.7.1 Letting the Engine Stabilize SUMMER/WINTER Heat Riser SystemStopping the Generator ‹ 2.8.1 do not Overload the Generator ‹ 2.9. LOW OIL Pressure Switch‹ 2.9.2 High Temperature Switch Protection Systems‹ 2.10.2 Operation in High Grass or Brush Additional InformationChecking the Engine OIL Level Changing the Engine OIL AND/OR OIL Filter Maintaining the Engine AIR Cleaner‹ 3.3.1 Cleaning the Foam Precleaner Checking the Engine Spark Plug Clean AIR IntakeSpark Arrestor Muffler Cleaning the GeneratorBattery Maintenance Fuel Filter Gasoline onlyExercising the Generator OUT of Service Procedure‹ 3.13.1 Removal from Service Drive Belt‹ 3.13.2 Return to Service Part  General Hazards   Fire Hazards  Standards Booklets Purpose and Scope ManualEquipment Description Generator Engine Operating Speed0F1127 ‹ 2.1.2 Generator Support Location and Support‹ 2.1.1 Generator Location ‹ 2.2.1 Compartment Size Generator Compartments‹ 2.1.4 Generator Restraint ‹ 2.2.2 Compartment Construction‹ 2.2.4 Acoustics ‹ 2.2.3 Sound Insulating MaterialsTypical Noise Abatement ‹ 2.2.5 Compartment Floor Cutouts‹ 2.3.2 Cooling AIR Inlet Openings Cooling and Ventilating AIR‹ 2.3.1 Generator Airflow ‹ 2.3.3 Compensating for Restrictions ‹ 2.3.4 Testing the InstallationGasoline Fuel System ‹ 2.5.1 Parts not Included in Fuel System LP GAS Fuel System‹ 2.4.2 Generator Fuel Supply Line ‹ 2.5.5 Gaseous Carburetion ‹ 2.5.2 Some Important Considerations‹ 2.5.3 Vapor Withdrawal ‹ 2.5.8 Leakage Tests Exhaust System‹ 2.5.6 Fuel Supply Lines ‹ 2.5.7 Excess Flow Valve‹ 2.7.1 Electrical Junction BOX ‹ 2.6.3 Exhaust System Safety‹ 2.6.1 Mufflers and Spark Arrestors ‹ 2.6.2 Type of Exhaust System‹ 2.7.3 Generator AC Connections ‹ 2.7.2 Wiring‹ 2.7.7 Ground Fault Circuit Interrupters ‹ 2.7.6 Power Supply CordOptional Accessories Battery InstallationInitial Start Post Installation TestsTesting Under Load Before Initial START-UPInstallation Checklist Problem Cause Correction Troubleshooting GuideElectrical Data Electrical Data Exploded Views and Parts Lists Description Exploded Views and Parts Lists QTY Description Exploded Views and Parts Lists Description QTY Exploded Views and Parts Lists SCROLL, Flywheel Exploded Views and Parts Lists Ring SET, Piston DIA Exploded Views and Parts Lists MANIFOLD, Intake PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule CONSUMER/PERSONAL Applications

02010-2, 04164-3 specifications

Guardian Technologies has made a significant impact in the air purification industry with its range of innovative products, particularly the models 02010-2 and 04164-3. These air purifiers are designed to enhance indoor air quality by leveraging advanced technologies, making them popular choices for both home and office environments.

The Guardian Technologies 02010-2 is an impressive model known for its portable design and effective purification capabilities. It features a 3-in-1 air cleaning system that includes a HEPA filter, a charcoal filter, and a UV-C light. The HEPA filter is essential for capturing allergens such as pollen, dust mites, and pet dander, making it ideal for allergy sufferers. The charcoal filter helps eliminate odors, capturing smoke and volatile organic compounds, while the UV-C light helps reduce germs and bacteria, ensuring a cleaner atmosphere.

This model is compact, allowing it to fit seamlessly into small spaces, while still providing powerful purification performance. With a whisper-quiet operation, it can be used in bedrooms or workspaces without causing disruption. Additionally, it features an adjustable fan speed, enabling users to customize the airflow according to their preference, along with an energy-efficient design that helps reduce power consumption.

On the other hand, the Guardian Technologies 04164-3 introduces a more advanced air purification system with similar foundational features but enhances the user experience with added functionalities. This model typically incorporates a combination of a HEPA filter and a UV-C light as well, but it often boasts smart capabilities. These may include an air quality sensor that helps monitor particulate levels in real-time, automatically adjusting the purification level when needed. This intelligent feature ensures that the air quality remains at optimal levels without requiring constant manual adjustments.

Both models prioritize user convenience, sporting features like filter replacement indicators, ensuring timely maintenance of the purification system. They are designed for ease of use and portability, allowing consumers to move them effortlessly from room to room.

In summary, Guardian Technologies’ models 02010-2 and 04164-3 stand out in the air purifier market due to their advanced filtration systems, ease of use, and smart technologies. These air purifiers are key investments for anyone looking to improve their indoor air quality effectively.