Generac Power Systems 005012-1 owner manual Miscellaneous Maintenance, ‹ 4.5.13 Coolant Change

Page 20

Section 4 — Maintenance

40kW Liquid-cooled Generators

7.Start engine and check for oil leaks.

Figure 4.2 - Oil Filter

Oil Filter

‹4.5.11 CHANGING THE ENGINE AIR CLEANER

To replace the engine air cleaner, (part number 0A4637), remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover.

See the “Service Schedule,” for air cleaner mainte- nance.

‹4.5.12 SPARK PLUGS

Reset the spark plug gap or replace the spark plugs as necessary.

1.Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to clean.

2.Remove the spark plugs and check the condi- tion. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule, for recommended inspection.

3.Check the spark plug gap using a wire feeler gauge. Adjust the gap to 1.01 mm (0.040 inch) by carefully bending the ground electrode (Figure 4.3).

Figure 4.3 – Setting the Spark Plug Gap

SET PLUG GAP AT 1.01 mm

(0.040 inch)

‹4.5.13 COOLANT CHANGE

Every year, have an authorized service deal- er drain, flush and refill the cooling system. See SPECIFICATIONS for cooling system recommenda- tions.

4.6MISCELLANEOUS MAINTENANCE

‹4.6.1 CLEANING THE GENERATOR

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.

Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.

Once each year, have the generator cleaned and inspected by an Authorized Service Dealer. That dealer will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹4.6.2 BATTERY

All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:

DO NOT use jumper cables and a booster battery to crank or start the generator engine.

DO NOT recharge a weak battery while it is installed in the generator. Remove battery from generator and recharge in a well-ventilated area, away from fuel vapors, sparks, heat or flames.

Battery electrolyte fluid is an extremely caustic sulfuric solution that can cause severe burns. DO NOT permit fluid to contact eyes, skin, clothing, painted surfaces, wiring insulation, etc. If any bat- tery fluid is spilled, flush the affected area with clear water immediately.

Always wear safety glasses, rubber apron and gloves when handling a battery.

18

Image 20
Contents Liquid-cooled, Prepackaged Standby Generators Authorized Service Dealer Location ‹ Operation and Maintenance‹ HOW to Obtain Service IntroductionTable of Contents  Warning   Electrical Hazards  Transfer Switch GeneratorAutomatic System Operation Generator AC Connection Systems‹ 1.7.1 LOW OIL Pressure Switch ‹ 1.7.2 High Coolant Temperature SwitchGenerator Fuel System Engine Protective DevicesUnpacking Specifications Reconfiguring the Fuel SystemLifting the Generator Fuel ConsumptionTorque Specifications Before InstallationStandby Generator Installation Coolant RecommendationsGenerator Location Generator Mounting Support‹ 2.1.1 Nfpa Standards ‹ 2.1.2 Other Published StandardsBasic Standby Electric System Total Circuit Isolation MethodEmergency Circuit Isolation Method Grounding the GeneratorGenerator AC Neutral Connections Transfer Switch Signal ConnectionsBattery Installation Preparation Before START-UP Using AN Engineered GTS Transfer Switch ‹ 3.2.1 AUTO/OFF/MANUAL Switch‹ 3.2.2 Fault Indicator LED Control Console ComponentsEngine Governor Adjustments ‹ 3.2.5 SET Exercise Time SwitchManual Transfer START-UP ‹ 3.2.6 System Ready LEDWeekly Exercise Cycle Retransfer and ShutdownAutomatic Operation Cooling System Overload Protection for Engine DC Electrical SystemChecking Fluid Levels ‹ 4.5.2 Check Battery ‹ 4.5.1 Check Engine OIL Level‹ 4.5.3 Exercise System ‹ 4.5.4 Inspect Cooling SystemMiscellaneous Maintenance ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.6.1 Cleaning the Generator ‹ 4.5.13 Coolant Change‹ 4.6.3 Battery Maintenance ‹ 4.6.4 Battery ReplacementScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionElectrical Data Electrical Data Electrical Data Electrical Data Engine Block Assy Wire Hold Down BatteryBOOT, Contactor Cables Battery Post Covwer BlackDetail Assy Wire 14AWG 7.5 #0 GRN/YEL Duct Intake MID ALDuct Discharge RH AL Duct Discharge LH ALPage Assy 2A 12V UL Battery Control BOX HSBDecal AVR Cover Cover Front Panel HSBComes with Engine Cover Flywheel Access Countersunk Assembly ResistorFlexplate 3.9L HSB Plug STD Pipe 3/8To a 17 Tank Coolant Recovery Radiator Copper BrassVENTURI,3.9L Cryslr HSB 22FAN Radiator Support L/H SideTo Engine Base AIR Cleaner Plate Hold Down AIR CleanerPlate AIR Cleaner TOP Flange Fuel InletLocktight Rotor 390 15KW 1P Direct HSB 2.5L Ford Rotor 390 20KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumNUT TOP Lock FL M12-1.75 Exhaust Flange 2 PipeWasher Lock M12 Exhaust Blanket 800MMInstallation Diagram 40kW Liquid-cooled Generators 40kW Liquid-cooled Generators This Warranty Shall not Apply to the Following

005012-1 specifications

Generac Power Systems 005012-1 is a high-performance generator designed to provide reliable backup power for homes and businesses. Known for its innovative features and advanced technology, this generator is engineered to ensure consistent performance during power outages.

At the heart of the 005012-1 is its robust engine. With a Generac 999cc V-Twin OHV engine, it delivers impressive power output and durability. This engine is designed to run efficiently, making the generator an optimal choice for extended use during outages. The Quiet Test feature allows the generator to run at a lower volume during self-diagnostic tests, ensuring minimal disturbance to its surroundings.

One of the standout features of the 005012-1 is its ability to automatically detect power loss and start up within seconds. This automatic transfer switch ensures that when the primary power source fails, the generator takes over seamlessly, keeping essential appliances and systems operational. This rapid response time is crucial for maintaining comfort and safety during outages.

The generator is equipped with a user-friendly control panel that includes an LCD display. This panel provides real-time information about power usage, operational status, and maintenance reminders, enabling users to stay informed and address any issues promptly. Additionally, the model offers flexible monitoring options through mobile connectivity, allowing users to check the generator's status remotely via smartphone or other devices.

Designed for longevity, the 005012-1 features a durable aluminum enclosure that protects the generator from the elements, ensuring reliable operation in various conditions. Its compact design allows for easy installation and integration into existing power systems without occupying excessive space.

Fuel efficiency is another hallmark of the 005012-1, as it operates on propane or natural gas, providing flexibility in fuel choice. This versatility not only aids in reducing operational costs but also appeals to environmentally conscious users seeking cleaner energy solutions.

Overall, Generac Power Systems 005012-1 stands out as a dependable and technologically advanced generator, combining power, efficiency, and user-friendly features. Its commitment to reliability makes it a top choice for those looking to safeguard their homes and businesses against unexpected power interruptions.