Generac Power Systems 005012-1 owner manual Generator, Transfer Switch, Automatic System Operation

Page 6

Section 1 - General Information

40kW Liquid-cooled Generators

1.1GENERATOR

This equipment is a liquid-cooled, engine-driven generator set. The generator is designed to supply electrical power that operates critical electrical loads during utility power failure. The unit has been facto- ry-installed in a weather resistant, all metal enclosure and is intended for outdoor installation only. Use this generator as a source of electrical power for the operation of 120 and/or 240VAC, single-phase loads.

If this generator is used to power electrical load circuits normally powered by a utility power source, it is required by code to install a trans- fer switch. The transfer switch must effectively isolate the electric system from the utility distri- bution system when the generator is operating (NEC 701). Failure to isolate an electrical system by such means results in damage to the genera- tor and may also result in injury or even death to utility power workers due to backfeed of electrical energy.

1.2TRANSFER SWITCH

This generator system is intended to be used with the manufacturer's transfer switch. It will be avail- able in either a NEMA 1 enclosure or a NEMA 3R enclosure. The NEMA 1 enclosure is intended for indoor use only. The NEMA 3R enclosure is weather proof and can be used indoors or outdoors. Follow these rules:

1.3AUTOMATIC SYSTEM OPERATION

When this generator, along with a transfer switch, has been installed and interconnected, a circuit board in the generator panel constantly monitors UTILITY power source voltage. Should that voltage drop below a preset value, and remain at such a low state for a preset amount of time, the generator cranks and starts. After the generator starts, the transfer switch transfers load circuits so the generator can power them.

When utility source voltage has been restored, the switch re-transfers back to the UTILITY source volt- age and the generator then shuts down.

Please reference the transfer switch manual for spe- cific information.

1.4GENERATOR AC CONNECTION

SYSTEMS

The generator was shipped from the factory with its stator AC output leads connected in a single-phase, three-wire generator AC connection system (Figure 1.1). The stator assembly in this system consists of a pair of stationary windings, with two leads brought out of each winding. Each single winding can sup- ply 120VAC, 60 Hertz. When the two windings are connected in series, a 240VAC, 60 Hertz AC output results. Typically the two HOT leads in the circuit are wires 11 and 44. The NEUTRAL leads are the junction of Wires 22 and 33. The NEUTRAL is not grounded.

Install the transfer switch on a firm, sturdy sup- porting structure.

To prevent switch distortion, level the switch if necessary. This can be done by placing washers between the switch enclosure and the mounting surface.

Never install the switch where water or any corro- sive substance might drip onto the enclosure.

Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and cor- rosive vapors.

An Authorized Dealer can supply an appropriate transfer switch for the generator.

Figure 1.1 - Generator AC Connection System

1.5MAIN CIRCUIT BREAKER

The generator’s main circuit breaker is included with the unit as shipped from the factory. The breaker for this unit is described in Figure 1.2.

Figure 1.2 - Main Circuit Breaker

Model

Rating

Phase

Actual Current

C/B Rating*

Circuit Breaker

005012-1

37,000 NG

1

154.2

200

200A QN2

 

40,000 LP

1

166.7

200

200A QN2

 

 

* Amp Rating of C/B structured under model.

 

4

Image 6
Contents Liquid-cooled, Prepackaged Standby Generators ‹ HOW to Obtain Service Authorized Service Dealer Location‹ Operation and Maintenance IntroductionTable of Contents  Warning   Electrical Hazards  Automatic System Operation Transfer SwitchGenerator Generator AC Connection SystemsGenerator Fuel System ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch Engine Protective DevicesUnpacking Lifting the Generator SpecificationsReconfiguring the Fuel System Fuel ConsumptionStandby Generator Installation Torque SpecificationsBefore Installation Coolant Recommendations‹ 2.1.1 Nfpa Standards Generator LocationGenerator Mounting Support ‹ 2.1.2 Other Published StandardsEmergency Circuit Isolation Method Basic Standby Electric SystemTotal Circuit Isolation Method Grounding the GeneratorTransfer Switch Signal Connections Battery InstallationGenerator AC Neutral Connections Preparation Before START-UP ‹ 3.2.2 Fault Indicator LED Using AN Engineered GTS Transfer Switch‹ 3.2.1 AUTO/OFF/MANUAL Switch Control Console ComponentsManual Transfer START-UP Engine Governor Adjustments‹ 3.2.5 SET Exercise Time Switch ‹ 3.2.6 System Ready LEDRetransfer and Shutdown Automatic OperationWeekly Exercise Cycle Overload Protection for Engine DC Electrical System Checking Fluid LevelsCooling System ‹ 4.5.3 Exercise System ‹ 4.5.2 Check Battery‹ 4.5.1 Check Engine OIL Level ‹ 4.5.4 Inspect Cooling System‹ 4.6.1 Cleaning the Generator Miscellaneous Maintenance‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.5.13 Coolant Change‹ 4.6.3 Battery Maintenance ‹ 4.6.4 Battery ReplacementScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionElectrical Data Electrical Data Electrical Data Electrical Data Engine Block BOOT, Contactor Cables Assy WireHold Down Battery Battery Post Covwer BlackDetail Duct Discharge RH AL Assy Wire 14AWG 7.5 #0 GRN/YELDuct Intake MID AL Duct Discharge LH ALPage Decal AVR Cover Assy 2A 12V UL BatteryControl BOX HSB Cover Front Panel HSBComes with Engine Flexplate 3.9L HSB Cover Flywheel Access CountersunkAssembly Resistor Plug STD Pipe 3/8To a 17 VENTURI,3.9L Cryslr HSB 22FAN Tank Coolant RecoveryRadiator Copper Brass Radiator Support L/H SideTo Engine Plate AIR Cleaner TOP Base AIR Cleaner PlateHold Down AIR Cleaner Flange Fuel InletLocktight Rotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumWasher Lock M12 NUT TOP Lock FL M12-1.75Exhaust Flange 2 Pipe Exhaust Blanket 800MMInstallation Diagram 40kW Liquid-cooled Generators 40kW Liquid-cooled Generators This Warranty Shall not Apply to the Following

005012-1 specifications

Generac Power Systems 005012-1 is a high-performance generator designed to provide reliable backup power for homes and businesses. Known for its innovative features and advanced technology, this generator is engineered to ensure consistent performance during power outages.

At the heart of the 005012-1 is its robust engine. With a Generac 999cc V-Twin OHV engine, it delivers impressive power output and durability. This engine is designed to run efficiently, making the generator an optimal choice for extended use during outages. The Quiet Test feature allows the generator to run at a lower volume during self-diagnostic tests, ensuring minimal disturbance to its surroundings.

One of the standout features of the 005012-1 is its ability to automatically detect power loss and start up within seconds. This automatic transfer switch ensures that when the primary power source fails, the generator takes over seamlessly, keeping essential appliances and systems operational. This rapid response time is crucial for maintaining comfort and safety during outages.

The generator is equipped with a user-friendly control panel that includes an LCD display. This panel provides real-time information about power usage, operational status, and maintenance reminders, enabling users to stay informed and address any issues promptly. Additionally, the model offers flexible monitoring options through mobile connectivity, allowing users to check the generator's status remotely via smartphone or other devices.

Designed for longevity, the 005012-1 features a durable aluminum enclosure that protects the generator from the elements, ensuring reliable operation in various conditions. Its compact design allows for easy installation and integration into existing power systems without occupying excessive space.

Fuel efficiency is another hallmark of the 005012-1, as it operates on propane or natural gas, providing flexibility in fuel choice. This versatility not only aids in reducing operational costs but also appeals to environmentally conscious users seeking cleaner energy solutions.

Overall, Generac Power Systems 005012-1 stands out as a dependable and technologically advanced generator, combining power, efficiency, and user-friendly features. Its commitment to reliability makes it a top choice for those looking to safeguard their homes and businesses against unexpected power interruptions.