Generac Power Systems 005012-1 owner manual Unpacking

Page 8

Section 1 — General Information

40kW Liquid-cooled Generators

‹1.7.3 LOW COOLANT LEVEL SWITCH

Should engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shutdown. To prevent such overheating without automatic shut down, the engine has a low coolant level sensor. If the engine coolant drops too low, the engine automatical- ly shuts down and turns on the high coolant tempera- ture/low coolant level LED (Figure 1.6 on page 6).

Figure 1.6 - Low Coolant Level Sensor

‹1.7.4 OVERSPEED SHUTDOWN

The engine control board receives AC frequency signals from an engine run winding in the alterna- tor. Should AC frequency exceed about 72 Hertz for three seconds or 75 Hertz instantaneously, the engine shuts down and the overspeed LED turns on. Should AC frequency exceed about 72 Hertz, circuit board action will automatically shutdown the engine (Figure 1.7).

Figure 1.7 - Printed Circuit Board Assembly

 

LED1

 

R44

 

C27

Q2

 

C9

2

 

 

J2

C26

U7

C4

D10

 

 

C21

C30

 

 

 

C2

 

 

RL1

RL2

 

R1

 

R25

R48

 

 

D17

 

R49

 

 

 

U1

 

 

 

J1

 

L3

 

 

.REV 0E4906 PCB#

D19

 

 

‹1.7.5 RPM SENSOR LOSS

If the engine control board does not receive a proper rpm signal from the starter during cranking or run- ning, it shuts down the engine on rpm sensor loss and flashes the overspeed LED.

‹1.7.6 OVERCRANK SHUTDOWN

The engine control board uses a cyclic cranking pro- cess when attempting to start the engine. The first crank cycle is a 15-second crank followed by a seven- second rest. This is followed by five more crank cycles each with a seven-second crank followed by a seven-second rest.

If the engine fails to start after all six attempts, the start attempt is stopped and the overcrank LED turned on.

‹1.7.7 LOW BATTERY

The engine control board continually monitors the battery voltage and turns on the low battery LED if the battery voltage falls below 11.0 VDC for one minute. Low battery voltage is a non-latching alarm, which will automatically clear if the battery voltage rises above 11.0 VDC.

The control system will not attempt to start the engine if there is a low battery condition, however, if the engine is already running when the low battery condition occurs, the engine will continue to run as long as possible.

Battery voltage is NOT monitored during the crank cycle.

‹1.7.8 ALARM RESET

If the engine control board shuts down the genera- tor for any of the above reasons, the engine remains stopped until the alarm is cleared by placing the AUTO/OFF/MANUAL switch into the OFF position.

‹1.7.9 DC FUSE

These fuses are located on the front panel of the con- trol system. They protect the panel wiring and com- ponents from damaging overload. Always remove the 15 amp main fuse before working on the generator. The unit will not start or crank if this fuse is blown. Replace the fuse with one of the same size, type, and rating (main AGC-15, battery charger AG4).

1.8UNPACKING

‹1.8.1 UNPACKING PRECAUTIONS

Handle shipping cartons and crates with care. Use care to avoid damage from dropping, bumping, col- lision, etc..

‹1.8.2 INSPECTION

After unpacking, carefully inspect the generator for any damage that may have occurred during ship- ment. If loss or damage is noted at the time of deliv- ery, have the person(s) making delivery note all dam- age on the freight bill or affix their signature under the consignor’s memo of loss or damage.

6

Image 8
Contents Liquid-cooled, Prepackaged Standby Generators Authorized Service Dealer Location ‹ Operation and Maintenance‹ HOW to Obtain Service IntroductionTable of Contents  Warning   Electrical Hazards  Transfer Switch GeneratorAutomatic System Operation Generator AC Connection Systems‹ 1.7.1 LOW OIL Pressure Switch ‹ 1.7.2 High Coolant Temperature SwitchGenerator Fuel System Engine Protective DevicesUnpacking Specifications Reconfiguring the Fuel SystemLifting the Generator Fuel ConsumptionTorque Specifications Before InstallationStandby Generator Installation Coolant RecommendationsGenerator Location Generator Mounting Support‹ 2.1.1 Nfpa Standards ‹ 2.1.2 Other Published StandardsBasic Standby Electric System Total Circuit Isolation MethodEmergency Circuit Isolation Method Grounding the GeneratorGenerator AC Neutral Connections Transfer Switch Signal ConnectionsBattery Installation Preparation Before START-UP Using AN Engineered GTS Transfer Switch ‹ 3.2.1 AUTO/OFF/MANUAL Switch‹ 3.2.2 Fault Indicator LED Control Console ComponentsEngine Governor Adjustments ‹ 3.2.5 SET Exercise Time SwitchManual Transfer START-UP ‹ 3.2.6 System Ready LEDWeekly Exercise Cycle Retransfer and ShutdownAutomatic Operation Cooling System Overload Protection for Engine DC Electrical SystemChecking Fluid Levels ‹ 4.5.2 Check Battery ‹ 4.5.1 Check Engine OIL Level‹ 4.5.3 Exercise System ‹ 4.5.4 Inspect Cooling SystemMiscellaneous Maintenance ‹ 4.5.11 Changing the Engine AIR Cleaner‹ 4.6.1 Cleaning the Generator ‹ 4.5.13 Coolant Change‹ 4.6.3 Battery Maintenance ‹ 4.6.4 Battery ReplacementScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionElectrical Data Electrical Data Electrical Data Electrical Data Engine Block Assy Wire Hold Down BatteryBOOT, Contactor Cables Battery Post Covwer BlackDetail Assy Wire 14AWG 7.5 #0 GRN/YEL Duct Intake MID ALDuct Discharge RH AL Duct Discharge LH ALPage Assy 2A 12V UL Battery Control BOX HSBDecal AVR Cover Cover Front Panel HSBComes with Engine Cover Flywheel Access Countersunk Assembly ResistorFlexplate 3.9L HSB Plug STD Pipe 3/8To a 17 Tank Coolant Recovery Radiator Copper BrassVENTURI,3.9L Cryslr HSB 22FAN Radiator Support L/H SideTo Engine Base AIR Cleaner Plate Hold Down AIR CleanerPlate AIR Cleaner TOP Flange Fuel InletLocktight Rotor 390 15KW 1P Direct HSB 2.5L Ford Rotor 390 20KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumNUT TOP Lock FL M12-1.75 Exhaust Flange 2 PipeWasher Lock M12 Exhaust Blanket 800MMInstallation Diagram 40kW Liquid-cooled Generators 40kW Liquid-cooled Generators This Warranty Shall not Apply to the Following

005012-1 specifications

Generac Power Systems 005012-1 is a high-performance generator designed to provide reliable backup power for homes and businesses. Known for its innovative features and advanced technology, this generator is engineered to ensure consistent performance during power outages.

At the heart of the 005012-1 is its robust engine. With a Generac 999cc V-Twin OHV engine, it delivers impressive power output and durability. This engine is designed to run efficiently, making the generator an optimal choice for extended use during outages. The Quiet Test feature allows the generator to run at a lower volume during self-diagnostic tests, ensuring minimal disturbance to its surroundings.

One of the standout features of the 005012-1 is its ability to automatically detect power loss and start up within seconds. This automatic transfer switch ensures that when the primary power source fails, the generator takes over seamlessly, keeping essential appliances and systems operational. This rapid response time is crucial for maintaining comfort and safety during outages.

The generator is equipped with a user-friendly control panel that includes an LCD display. This panel provides real-time information about power usage, operational status, and maintenance reminders, enabling users to stay informed and address any issues promptly. Additionally, the model offers flexible monitoring options through mobile connectivity, allowing users to check the generator's status remotely via smartphone or other devices.

Designed for longevity, the 005012-1 features a durable aluminum enclosure that protects the generator from the elements, ensuring reliable operation in various conditions. Its compact design allows for easy installation and integration into existing power systems without occupying excessive space.

Fuel efficiency is another hallmark of the 005012-1, as it operates on propane or natural gas, providing flexibility in fuel choice. This versatility not only aids in reducing operational costs but also appeals to environmentally conscious users seeking cleaner energy solutions.

Overall, Generac Power Systems 005012-1 stands out as a dependable and technologically advanced generator, combining power, efficiency, and user-friendly features. Its commitment to reliability makes it a top choice for those looking to safeguard their homes and businesses against unexpected power interruptions.