Generac Power Systems 005012-1 owner manual Coolant Recommendations, Torque Specifications

Page 10

Section 2 — Installation

40kW Liquid-cooled Generators

3.Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator.

4.Remove pipe plug from Port 2.

5.Install brass hose fitting into Port 2.

6.Install pipe plug into Port 1.

7.Connect carburetor gas hose to brass fitting.

8.Tighten all clamps and plugs.

9.Make sure fuel supply is of the proper pressure and type for configuration.

10.Reverse the procedure to convert back to natural gas.

NOTE:

Port 1 is for NG only and Port 2 is for LP vapor only. No provision for dual fuel has been made.

DANGER

Serious injury or damage may occur if not con- figured properly. Please consult an Authorized Service Dealer with any questions.

1.15 COOLANT RECOMMENDATIONS

Use a mixture of half low silicate ethylene glycol base anti-freeze and half de-ionized water. Cooling system capacity is about 20 U.S. quarts (19.3 liters). Use only de-ionized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the rec- ommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.

Do not use any chromate base rust inhibitor with ethylene glycol base anti-freeze or chro- miumhydroxide (“green slime”) forms and will cause overheating. Engines that have been oper- ated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or additives will also cause overheating. It is also recommend that any solu- ble oil inhibitor is NOT USED for this equipment.

1.13 TORQUE SPECIFICATIONS

Tighten the bolts from the middle out, in a criss- cross pattern.

Cylinder Head

50 ft.lb./105 ft.lb./105 ft.lb.

Intake Manifold

48 in.lb./84 in.lb./84 in.lb.

Exhaust Manifold

25 ft.lb.

1.14 ENGINE OIL RECOMMENDATIONS

The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE, SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:

 

Temperature

Oil Grade (Recommended)

 

 

Above 80° F (27° C)

SAE 15W-40

 

 

32° to 80° F (-1° to 27° C)

SAE 15W-40

 

 

Below 32° F (0° C)

SAE 15W-40

 

NOTE:

5W-30 full synthetic oil is highly recommended in any element with temperatures above 90° F or below 30° F.

Any attempt to crank or start the engine before it has been properly serviced with the recom- mended oil may result in an engine failure.

1.16 BEFORE INSTALLATION

Before installing this equipment, check the ratings of both the generator and the transfer switch. Read “Emergency Isolation Method” and “Total Circuit Isolation Method”.

The generator’s rated wattage/amperage capacity must be adequate to handle all electrical loads that the unit will power. The critical (essential) loads may need to be grouped together and wired into a sepa- rate “emergency” distribution panel.

This generator can be installed in conjunction with an engineered “GTS” type transfer switch, if neces- sary.

The standard transfer switch has no sensing or con- trolling circuit boards. Instead, the generator control console houses a “Printed Circuit Board Assembly”, which controls all phases of operation, including engine start up and load transfer.

2.1STANDBY GENERATOR

INSTALLATION

DANGER

Connecting this generator to an electrical system normally supplied by an electric utility shall be by means of a transfer switch, so as to isolate the electric system from the utility distribution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.

8

Image 10
Contents Liquid-cooled, Prepackaged Standby Generators ‹ HOW to Obtain Service Authorized Service Dealer Location‹ Operation and Maintenance IntroductionTable of Contents  Warning   Electrical Hazards  Automatic System Operation Transfer SwitchGenerator Generator AC Connection SystemsGenerator Fuel System ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch Engine Protective DevicesUnpacking Lifting the Generator SpecificationsReconfiguring the Fuel System Fuel ConsumptionStandby Generator Installation Torque SpecificationsBefore Installation Coolant Recommendations‹ 2.1.1 Nfpa Standards Generator LocationGenerator Mounting Support ‹ 2.1.2 Other Published StandardsEmergency Circuit Isolation Method Basic Standby Electric SystemTotal Circuit Isolation Method Grounding the GeneratorBattery Installation Transfer Switch Signal ConnectionsGenerator AC Neutral Connections Preparation Before START-UP ‹ 3.2.2 Fault Indicator LED Using AN Engineered GTS Transfer Switch‹ 3.2.1 AUTO/OFF/MANUAL Switch Control Console ComponentsManual Transfer START-UP Engine Governor Adjustments‹ 3.2.5 SET Exercise Time Switch ‹ 3.2.6 System Ready LEDAutomatic Operation Retransfer and ShutdownWeekly Exercise Cycle Checking Fluid Levels Overload Protection for Engine DC Electrical SystemCooling System ‹ 4.5.3 Exercise System ‹ 4.5.2 Check Battery‹ 4.5.1 Check Engine OIL Level ‹ 4.5.4 Inspect Cooling System‹ 4.6.1 Cleaning the Generator Miscellaneous Maintenance‹ 4.5.11 Changing the Engine AIR Cleaner ‹ 4.5.13 Coolant Change‹ 4.6.3 Battery Maintenance ‹ 4.6.4 Battery ReplacementScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionElectrical Data Electrical Data Electrical Data Electrical Data Engine Block BOOT, Contactor Cables Assy WireHold Down Battery Battery Post Covwer BlackDetail Duct Discharge RH AL Assy Wire 14AWG 7.5 #0 GRN/YELDuct Intake MID AL Duct Discharge LH ALPage Decal AVR Cover Assy 2A 12V UL BatteryControl BOX HSB Cover Front Panel HSBComes with Engine Flexplate 3.9L HSB Cover Flywheel Access CountersunkAssembly Resistor Plug STD Pipe 3/8To a 17 VENTURI,3.9L Cryslr HSB 22FAN Tank Coolant RecoveryRadiator Copper Brass Radiator Support L/H SideTo Engine Plate AIR Cleaner TOP Base AIR Cleaner PlateHold Down AIR Cleaner Flange Fuel InletLocktight Rotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumWasher Lock M12 NUT TOP Lock FL M12-1.75Exhaust Flange 2 Pipe Exhaust Blanket 800MMInstallation Diagram 40kW Liquid-cooled Generators 40kW Liquid-cooled Generators This Warranty Shall not Apply to the Following

005012-1 specifications

Generac Power Systems 005012-1 is a high-performance generator designed to provide reliable backup power for homes and businesses. Known for its innovative features and advanced technology, this generator is engineered to ensure consistent performance during power outages.

At the heart of the 005012-1 is its robust engine. With a Generac 999cc V-Twin OHV engine, it delivers impressive power output and durability. This engine is designed to run efficiently, making the generator an optimal choice for extended use during outages. The Quiet Test feature allows the generator to run at a lower volume during self-diagnostic tests, ensuring minimal disturbance to its surroundings.

One of the standout features of the 005012-1 is its ability to automatically detect power loss and start up within seconds. This automatic transfer switch ensures that when the primary power source fails, the generator takes over seamlessly, keeping essential appliances and systems operational. This rapid response time is crucial for maintaining comfort and safety during outages.

The generator is equipped with a user-friendly control panel that includes an LCD display. This panel provides real-time information about power usage, operational status, and maintenance reminders, enabling users to stay informed and address any issues promptly. Additionally, the model offers flexible monitoring options through mobile connectivity, allowing users to check the generator's status remotely via smartphone or other devices.

Designed for longevity, the 005012-1 features a durable aluminum enclosure that protects the generator from the elements, ensuring reliable operation in various conditions. Its compact design allows for easy installation and integration into existing power systems without occupying excessive space.

Fuel efficiency is another hallmark of the 005012-1, as it operates on propane or natural gas, providing flexibility in fuel choice. This versatility not only aids in reducing operational costs but also appeals to environmentally conscious users seeking cleaner energy solutions.

Overall, Generac Power Systems 005012-1 stands out as a dependable and technologically advanced generator, combining power, efficiency, and user-friendly features. Its commitment to reliability makes it a top choice for those looking to safeguard their homes and businesses against unexpected power interruptions.