15.1 Model Numbers

The UPS systems are housed in free-standing cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz with various output power ratings.

Models

Powere Rating

Frequency

 

 

 

Powerware 9390-120/100

100 kVA

50/60 Hz

 

 

 

Powerware 9390-120/120

120 kVA

50/60 Hz

 

 

 

Powerware 9390-160/100

100 kVA

50/60 Hz

 

 

 

Powerware 9390-160/120

120 kVA

50/60 Hz

 

 

 

Powerware 9390-160/160

160 kVA

50/60 Hz

 

 

 

The following sections detail the input, output, environmental, and battery specifications for the UPS.

15.2 Single Module Specifications

15.2.1 UPS System Input

Operating Input Voltage

208

Vac for operation from 177 Vac to 229 Vac

(Nominal +10/–15%)

220

Vac for operation from 187 Vac to 242 Vac

 

480

Vac for operation from 408 Vac to 528 Vac

Operating Input

¦5 Hz

Frequency Range

 

 

Operating Input Current

See Appendix A, Table E through Table G.

 

Reduced for Generator

 

Adjustable

Input Current Harmonic

5% THD at full load

Content

 

 

Power Factor

Minimum 0.99

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

Battery Voltage

384

Vdc (208V/220V units only)

 

432

Vdc

 

480

Vdc

 

 

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com