Installation Information

7.The basic environmental requirements for operation of the UPS system are:

Ambient Temperature Range:

0---40˚C (32---104˚F)

Recommended Operating Range:

20---25˚C (68---77˚F)

Maximum Relative Humidity:

95%, noncondensing

The UPS ventilation requirements are shown in Table C.

Table C. Air Conditioning or Ventilation Requirements During Full Load Operation

Ratings

 

Voltage

Heat Rejection

Input

 

Output

BTU/hr ¢ 1000/hr (kg-cal/hr)

 

 

 

 

 

 

 

100 kVA

208/220

 

208/220

29.6 (7.45)

 

 

 

 

 

100 kVA

480

 

480

27.4 (6.90)

 

 

 

 

 

120 kVA

208/220

 

208/220

35.5 (8.94)

 

 

 

 

 

120 kVA

480

 

480

32.8 (8.28)

 

 

 

 

 

160 kVA

208/220

 

208/220

47.3 (11.9)

 

 

 

 

 

160 kVA

480

 

480

43.8 (11.0)

 

 

 

 

 

Ventilation required for cooling air exhaust: approximately 9.44 liter/sec (2000 cfm).

 

 

 

 