Installation Information

11.Per NEC article 300-20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be run in the same conduit as the phase conductors.

12.Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed in Table J. All Powerware 9390 products can accommodate a double size neutral.

13.Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, THW-2.

 

 

Table J. Power Cable Conduit Requirements

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Model

Voltage

Terminal

Number of

 

Minimum Conduit

 

Number of

 

 

 

 

 

Wires in

 

 

 

 

 

 

 

 

Trade Size (inches)

 

Conduits

 

 

 

 

 

 

 

 

 

Conduit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

2-1/2

 

 

 

2

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware

208/220

AC Input to Bypass

5

 

2-1/2

 

 

 

2

 

 

 

 

 

9390---120/100

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

5

 

2-1/2

 

 

 

2

 

 

 

 

 

9390---160/100

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

5

 

2

 

 

 

1

 

 

 

 

 

 

DC

(Positive), (Negative), Gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

2-1/2

 

 

 

1

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware

480

AC Input to Bypass

5

 

2-1/2

 

 

 

1

 

 

 

 

 

9390---120/100

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

5

 

2-1/2

 

 

 

1

 

 

 

 

 

9390---160/100

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

5

 

2

 

 

 

1

 

 

 

 

 

 

DC

(Positive), (Negative), Gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

2-1/2

 

 

 

2

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware

208/220

AC Input to Bypass

5

 

2-1/2

 

 

 

2

 

 

 

 

 

9390---120/120

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

5

 

2-1/2

 

 

 

2

 

 

 

 

 

9390---160/120

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

5

 

2

 

 

 

1

 

 

 

 

 

 

DC

(Positive), (Negative), Gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to UPS

4

 

1-1/2

 

 

 

2

 

 

 

 

 

 

 

(A, B, C, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware

480

AC Input to Bypass

5

 

1-1/2

 

 

 

2

 

 

 

 

 

9390---120/120

AC

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and

 

Output

5

 

1-1/2

 

 

 

2

 

 

 

 

 

9390---160/120

 

(A, B, C, Neut, Gnd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

5

 

2

 

 

 

1

 

 

 

 

 

 

DC

(Positive), (Negative), Gnd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

DRAWING NO: 164201604---5

 

SHEET: 6 of 15

 

 

 

 

 

 

 

 

REVISION:

A

 

 

DATE:

091505

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S

164201604 Rev B powerware.com

A-17

Page 185
Image 185
Powerware 100160 kVA manual Description Power Wiring Installation Notes