Installation Information

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table P. INPUT/OUTPUT Ratings for Powerware 9390---120/120 and 9390---160/120 Parallel Systems

 

 

 

 

Configuration

 

 

 

 

Units

 

Rating 50/60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic Unit Rating at 0.9 lagging pF load

 

kVA

 

120

 

 

120

 

 

 

 

 

 

kW

 

108

 

 

108

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input and Bypass Input

 

 

 

VOLTS

 

208/220

 

480

 

 

 

 

 

Output

 

 

 

VOLTS

 

208/220

 

480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input from UPM

 

 

 

Amps

 

333/315

 

144

 

 

 

 

 

Full Load Current for each Module

 

 

D

 

 

 

 

 

 

All

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Conductor Size for each Module

 

 

AWG or kcmil

 

See Table

E through

 

 

 

 

 

Number per Phase for each Module

 

 

 

(each)

 

Table G for wire size.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

 

F

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

 

Amps

 

333/315

 

144

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1+1

AC Output to Critical Load

 

 

G

Amps

 

333/315

 

144

 

 

 

 

Full Load Current

 

 

 

 

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Neutral Bonding Jumper

 

---

AWG or kcmil

 

1/0

 

 

4

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)

 

 

(1)

 

 

 

 

 

Number (See Note 27)

 

 

 

(each)

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

 

F

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

 

Amps

 

666/630

 

288

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

2+0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical Load

 

 

G

 

 

 

 

 

 

 

 

 

 

 

and

Full Load Current

 

 

Amps

 

666/630

 

288

 

 

 

 

2+1

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Neutral Bonding Jumper

 

---

AWG or kcmil

 

3/0

 

 

1/0

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)

 

 

(1)

 

 

 

 

 

Number (See Note 27)

 

 

 

(each)

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

 

F

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

 

Amps

 

999/945

 

432

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

3+0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Output to Critical Load

 

 

G

 

 

 

 

 

 

 

 

 

 

 

and

Full Load Current

 

 

Amps

 

999/945

 

432

 

 

 

 

3+1

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Neutral Bonding Jumper

 

---

AWG or kcmil

 

1/0

 

 

2/0

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)

 

 

(1)

 

 

 

 

 

Number (See Note 27)

 

 

 

(each)

 

 

 

 

 

 

 

 

 

 

AC Input to Tie Cabinet Bypass (optional)

 

F

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

 

Amps

 

1332/1260

 

576

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4+0

AC Output to Critical Load

 

 

G

 

 

 

 

 

 

 

 

 

 

 

Full Load Current

 

 

Amps

 

1332/1260

 

576

 

 

 

 

 

(3) Phases, (1) Neutral---if required, (1) Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System Neutral Bonding Jumper

 

---

AWG or kcmil

 

2/0

 

 

2/0

 

 

 

 

 

Minimum Conductor Size

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)

 

 

(1)

 

 

 

 

 

Number (See Note 27)

 

 

 

(each)

 

 

 

 

 

 

 

 

 

NOTE: Callout letters D, F, and G map to Drawing 164201604 ---4, sheets 4 of 6, 5 of 6,

 

 

 

 

and 6 of 6.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION: POWER WIRING INSTALLATION NOTES

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201604---5

 

 

 

SHEET:

13 of 15

 

 

 

 

 

REVISION: B

 

 

 

DATE: 032406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A-24EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com