Installation Information
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
| Table P. INPUT/OUTPUT Ratings for Powerware |
|
| |||||||||||
|
| Configuration |
|
|
|
| Units |
| Rating 50/60 Hz |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| Basic Unit Rating at 0.9 lagging pF load |
| kVA |
| 120 |
|
| 120 |
|
| |||
|
|
|
| kW |
| 108 |
|
| 108 |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| Input and Bypass Input |
|
|
| VOLTS |
| 208/220 |
| 480 |
|
| ||
|
|
| Output |
|
|
| VOLTS |
| 208/220 |
| 480 |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AC Input from UPM |
|
|
| Amps |
| 333/315 |
| 144 |
|
| ||
|
|
| Full Load Current for each Module |
|
| D |
|
|
|
| |||||
|
| All | (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| Minimum Conductor Size for each Module |
|
| AWG or kcmil |
| See Table | E through |
|
| ||||
|
|
| Number per Phase for each Module |
|
|
| (each) |
| Table G for wire size. |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| AC Input to Tie Cabinet Bypass (optional) |
| F |
|
|
|
|
|
|
|
|
| |
|
|
| Full Load Current |
|
| Amps |
| 333/315 |
| 144 |
|
| |||
|
|
| (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1+1 | AC Output to Critical Load |
|
| G | Amps |
| 333/315 |
| 144 |
|
| ||
|
| Full Load Current |
|
|
|
|
|
| |||||||
|
|
| (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| System Neutral Bonding Jumper |
| AWG or kcmil |
| 1/0 |
|
| 4 |
|
| |||
|
|
| Minimum Conductor Size |
|
|
|
|
|
|
| |||||
|
|
|
|
|
| (1) |
|
| (1) |
|
| ||||
|
|
| Number (See Note 27) |
|
|
| (each) |
|
|
|
|
|
|
| |
|
|
| AC Input to Tie Cabinet Bypass (optional) |
| F |
|
|
|
|
|
|
|
|
| |
|
|
| Full Load Current |
|
| Amps |
| 666/630 |
| 288 |
|
| |||
|
|
| (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
|
| |
|
| 2+0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AC Output to Critical Load |
|
| G |
|
|
|
|
|
|
|
|
| |
|
| and | Full Load Current |
|
| Amps |
| 666/630 |
| 288 |
|
| |||
|
| 2+1 | (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| System Neutral Bonding Jumper |
| AWG or kcmil |
| 3/0 |
|
| 1/0 |
|
| |||
|
|
| Minimum Conductor Size |
|
|
|
|
|
|
| |||||
|
|
|
|
|
| (1) |
|
| (1) |
|
| ||||
|
|
| Number (See Note 27) |
|
|
| (each) |
|
|
|
|
|
|
| |
|
|
| AC Input to Tie Cabinet Bypass (optional) |
| F |
|
|
|
|
|
|
|
|
| |
|
|
| Full Load Current |
|
| Amps |
| 999/945 |
| 432 |
|
| |||
|
|
| (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
|
| |
|
| 3+0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| AC Output to Critical Load |
|
| G |
|
|
|
|
|
|
|
|
| |
|
| and | Full Load Current |
|
| Amps |
| 999/945 |
| 432 |
|
| |||
|
| 3+1 | (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
|
| |
|
|
| System Neutral Bonding Jumper |
| AWG or kcmil |
| 1/0 |
|
| 2/0 |
|
| |||
|
|
| Minimum Conductor Size |
|
|
|
|
|
|
| |||||
|
|
|
|
|
| (2) |
|
| (1) |
|
| ||||
|
|
| Number (See Note 27) |
|
|
| (each) |
|
|
|
|
|
|
| |
|
|
| AC Input to Tie Cabinet Bypass (optional) |
| F |
|
|
|
|
|
|
|
|
| |
|
|
| Full Load Current |
|
| Amps |
| 1332/1260 |
| 576 |
|
| |||
|
|
| (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 4+0 | AC Output to Critical Load |
|
| G |
|
|
|
|
|
|
|
|
|
|
| Full Load Current |
|
| Amps |
| 1332/1260 |
| 576 |
|
| ||||
|
|
| (3) Phases, (1) |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| System Neutral Bonding Jumper |
| AWG or kcmil |
| 2/0 |
|
| 2/0 |
|
| |||
|
|
| Minimum Conductor Size |
|
|
|
|
|
|
| |||||
|
|
|
|
|
| (2) |
|
| (1) |
|
| ||||
|
|
| Number (See Note 27) |
|
|
| (each) |
|
|
|
|
|
|
| |
|
| NOTE: Callout letters D, F, and G map to Drawing 164201604 |
| ||||||||||||
|
|
| and 6 of 6. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DESCRIPTION: POWER WIRING INSTALLATION NOTES |
| |||||||||||
|
|
|
|
| |||||||||||
|
|
|
| DRAWING NO: |
|
|
| SHEET: | 13 of 15 |
| |||||
|
|
|
| REVISION: B |
|
|
| DATE: 032406 |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|