Powerware 100160 kVA manual Interface Terminals

Models: 100160 kVA

1 226
Download 226 pages 24.03 Kb
Page 203
Image 203

Installation Information

1

TB1

10

1

TB2

10

INTERFACE TERMINALS

UPS

REMOTE

EPO NC

 

 

 

JUMPER REQUIRED

EPO COMMON

 

 

 

IF NOT USED

 

 

 

 

 

 

 

 

 

 

REMOTE EPO NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EPO COMMON

 

 

 

 

 

 

 

 

 

 

 

 

BATTERY BREAKER AUX

BATTERY BREAKER AUX RETURN

BATTERY UVR (+)

BATTERY UVR (---)

BUILDING ALARM 1

BUILDING ALARM 1 RETURN

BUILDING ALARM 2

BUILDING ALARM 2 RETURN

ON BYPASS RETURN

ON BYPASS NO

ALARM RELAY NC

ALARM RELAY COMMON

ALARM RELAY NO

ALARM RELAY COMMON

ON INVERTER NC

ON INVERTER RETURN

NOTE: 1. All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal as shown. Building alarm inputs can be programmed for use with either normally-open or normally-closed contacts. All control wiring and relay and switch contacts are customer-supplied.

2.The building alarms can be programmed to display the alarm functional name.

3.A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed EPO contact is not used.

 

 

DESCRIPTION: INTERFACE WIRING INSTALLATION

 

 

 

 

 

 

NOTES AND TERMINAL LOCATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAWING NO:

164201604---8

 

 

SHEET: 3 of 13

 

 

 

 

 

REVISION: B

 

DATE:

032406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EATON Powerware® 9390 UPS (100–160 kVA) Installation and Operation Manual S 164201604 Rev B powerware.com

A-35

Page 203
Image 203
Powerware 100160 kVA manual Interface Terminals