Installation Information
28.See Drawing
29.Setup of the CAN Bridge card for parallel operation must be performed by an authorized Eaton Customer Service Engineer. Contact service to schedule a date.
30.For parallel system circuit breaker ratings, see appropriate information in Table N.
31.For parallel system ratings, see the appropriate information in Table O through Table Q.
Table N. Recommended UPM Output (MOB), Main Output (MIS), and Bypass (MBP)
Circuit Breaker Ratings
Output Voltage
UPM Model | Configuration |
| 208V/220V |
|
| 480V |
| |
|
| MOB | MIS | MBP | MOB | MIS | MBP | |
|
|
|
|
|
|
|
| |
| 1+1 | 500 | 500 | 500 | 200 | 200 | 200 | |
|
|
|
|
|
|
|
| |
2+0 and 2+1 | 500 | 1000 | 1000 | 200 | 400 | 400 | ||
3+0 and 3+1 | 500 | 1600 | 1600 | 200 | 600 | 600 | ||
|
|
|
|
|
|
|
| |
| 4+0 | 500 | 2000 | 2000 | 200 | 800 | 800 | |
|
|
|
|
|
|
|
| |
| 1+1 | 500 | 500 | 500 | 200 | 200 | 200 | |
|
|
|
|
|
|
|
| |
2+0 and 2+1 | 500 | 1000 | 1000 | 200 | 400 | 400 | ||
|
|
|
|
|
|
| ||
3+0 and 3+1 | 500 | 1600 | 1600 | 200 | 600 | 600 | ||
|
|
|
|
|
|
|
| |
| 4+0 | 500 | 2000 | 2000 | 200 | 800 | 800 | |
|
|
|
|
|
|
|
| |
| 1+1 | 600 | 600 | 600 | 250 | 250 | 250 | |
|
|
|
|
|
|
|
| |
2+0 and 2+1 | 600 | 1200 | 1200 | 250 | 500 | 500 | ||
|
|
|
|
|
|
| ||
3+0 and 3+1 | 600 | 2000 | 2000 | 250 | 800 | 800 | ||
| ||||||||
|
|
|
|
|
|
|
| |
| 4+0 | 600 | 2400 | 2400 | 250 | 1000 | 1000 | |
|
|
|
|
|
|
|
|
|
|
|
| DESCRIPTION: | POWER WIRING INSTALLATION NOTES |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| DRAWING NO: |
|
| SHEET: 11 of 15 |
| |
|
|
|
| REVISION: A |
|
| DATE: 091505 |
| |
|
|
|
|
|
|
|
|
|
|
EATON Powerware® 9390 UPS | 164201604 Rev B powerware.com |